BINDER MKF 720
BINDER ·Made in Germany · In Active Production

BINDER MKF 720

BINDER MKF 720 — Climate chambers with Temperature -40…180 °C.

The BINDER MKF 720 is a 734 L alternating climate chamber with a -40…180 °C range and 10…98 %RH humidity control, driven by an 11 kW refrigeration system. It is the mid-large 400 V standard variant (MKF720-400V, Art. 9020-0381) in the MKF series, distinguished from the -C version by its fixed 50 Hz supply. It serves cyclic temperature-humidity testing of large loads up to 40 kg per rack, with 1,000 W heat compensation at setpoint.

Temperature
-40…180 °C

BINDER MKF Series — Model Comparison & Selection

Model Temperature, °CHeight, cmInterior volume, LLoad per rack, kgMax heat compensation, WNominal power, kW
MKF 720 Current -40–180200.573440100011
MKF 1020 -40–180200.599140150012.5
MKF 1020 CO₂ -48–180200.599140140011.5
MKF 115 -40–180172.5115304004.8
MKF 240 -40–180171.5228304006.8
MKF 240 CO₂ -50...180171.3228309006.8
MKF 400 -40–180171417308008
MKF 400 CO₂ -50...180172.74173016007.9
MKF 56 -40–180144.560152502.8
MKF 720 CO₂ -48–180200.573440110011

Full specifications

Core Performance & Functional Specifications
Temperature -40...180 °C
Interior volume 734 L (MKF720-400V and MKF720-480V-C)
Load per rack 40 kg (MKF720-400V and MKF720-480V-C)
Maximum heat compensation 1000 W
Nominal power 11 kW (MKF720-400V and MKF720-480V-C)
Article Number mfr 9020
Dimensions, Weight & Mechanical Design
Height 2005 mm (MKF720-400V and MKF720-480V-C)
Width 1580 mm (MKF720-400V and MKF720-480V-C)
Electrical, Power & Drive Specifications
Power frequency 50 Hz (MKF720-400V)
Rated voltage 400 V
Unit fuse 32.0 A (MKF720-400V and MKF720-480V-C)
Operating Conditions, Environment & Protection
Humidity range 10...98 % RH
Cooling down time from 180°C to -40°C mfr 120 min
Humidity fluctuation with humidity dependent on set value mfr 2.5 % r.F.
Standards, Safety & General Data
Average heating-up rate according to IEC 60068-3-5 between -40°C and 180°C mfr 4.8 K/min

Description

Construction and series positioning

Thermal and humidity behavior

Installation, control and operation

Integration & Operating Notes

Electrical
Supply must be 400 V 3 N/PE 50 Hz with 32 A fusing

The 11 kW nominal load and 32.0 A unit fuse require a dedicated three-phase supply with neutral and PE; the standard model has no voltage/frequency changer, so a 480 V 60 Hz site needs the -C variant instead. Verify upstream protection and cable sizing against the 32 A fuse before connection.

Data Sheet Model MKF 720 en.pdf; Factory Specification Sheet
Process Limits
Live load heat dissipation must stay below 1,000 W

Maximum heat compensation is 1,000 W; a test specimen dissipating more than this will prevent the chamber from holding low setpoints and may cause sustained deviation. Calculate specimen power before programming low-temperature or humidity profiles, and consider reducing load or duty cycle.

Factory Specification Sheet
Process Limits
Humidity control is limited to 10…95 °C chamber temperature

Although the chamber reaches -40…180 °C dry, humidity operation is restricted to 10…95 °C and 10…98 %RH. Programs combining humidity with temperatures outside this window will not control RH; sequence such steps as dry phases or accept that humidity is inactive.

Factory Specification Sheet
Process Limits
Humidity sensor is damaged by ammonia and ozone above limits

The humidity sensor tolerates ammonia up to 20 ppm workplace threshold (permanent 5500 ppm) and ozone up to 0.1 ppm (permanent 0.5 ppm). Process atmospheres or cleaning agents releasing these species above the limits will degrade or destroy the sensor; verify specimen outgassing before humidity testing.

Operating Manual MKF/MKFT (E5) 10/2026, p.20 table
Mounting
Rear power switch must be on in addition to main switch

From size 115 on, the chamber has a rear power switch as well as the main power switch; both must be on for commissioning and troubleshooting. Account for rear access clearance when positioning the 1,580 mm wide cabinet so the switch and water connections remain reachable.

Operating Manual MKF/MKFT (E5) 10/2026, p.24-25, p.135
Cooling & Media
Water cooling option requires inlet and outlet plumbing

The water cooling option is available for the MKF 720 and needs cooling water inlet and outlet connections plus a connection kit and hose burst protection kit. Without it, heat is rejected to ambient air, so room ventilation and condenser airflow must be adequate; plan plumbing before installation if water cooling is specified.

Operating Manual MKF/MKFT (E5) 10/2026, p.34, p.127
Maintenance
Annual maintenance and leak test are mandatory

Schedule maintenance at least once a year, including the leak test per Regulation (EU) 517/2014, steam humidifier service (interval depends on water quality and steam output), and condenser cleaning every 1–2 years. Document the leak test in the service log book; electrical safety testing per EN 50678/VDE 0701 and EN 50699/VDE 0702 is recommended before first start and after repair.

Operating Manual MKF/MKFT (E5) 10/2026, p.134
Maintenance
8760-hour service message requires BINDER reset

After 8760 operating hours or two years the controller displays a service message; once acknowledged it reappears every two weeks until reset by BINDER Service. Plan the service intervention before the message appears to avoid repeated alarms during long test programs.

Operating Manual MKF/MKFT (E5) 10/2026, p.135
Maintenance
Check condenser fan grid weekly in dusty rooms

With increased dust in ambient air, inspect the fan grid behind the left maintenance access flap every week and clean by suction after disconnecting the chamber. Blocked airflow reduces cooling capacity and can trip high-temperature alarms; in clean rooms the interval can be extended.

Operating Manual MKF/MKFT (E5) 10/2026, p.135
Maintenance
Replace door gasket only when chamber is cold

The door gasket must be replaced only when cold; attempting replacement at elevated temperature can deform or damage the new gasket and compromise sealing. Allow the chamber to cool to ambient before service.

Operating Manual MKF/MKFT (E5) 10/2026, p.134
Control & I/O
Zero-voltage contacts can signal alarms to external systems

The chamber provides zero-voltage switching outputs for external switching or signaling, allowing alarm and state signals to be wired to a supervisory system. Use these contacts rather than switching the main load; define the fail-safe state in the integration design.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Zero-voltage switching outputs'
Process Limits
Disinfection requires drying and ventilation before start-up

After chemical disinfection with the recommended spray (Art. No. 1002-0022), the chamber must be absolutely dry and ventilated before start-up because explosive gases may form. Other disinfectants are excluded from BINDER liability and may corrode the interior.

Operating Manual MKF/MKFT (E5) 10/2026, p.133

Selection & Integration Q&A

When should I choose the MKF 720 standard model instead of the -C version or a larger MKF 1020?

Choose the standard MKF720-400V (Art. 9020-0381) when your site has 400 V 3 N/PE 50 Hz; the -C version (Art. 9020-0359) adds a voltage/frequency changer for 480 V 60 Hz. Move to the MKF 1020 only if 734 L is insufficient; the 1020 CO₂ variant is needed for -48 °C, which the 720 does not reach.

What supply and protection must be provided for the MKF 720, and can it be connected to a 480 V 60 Hz grid?

The standard model requires 400 V 3 N/PE 50 Hz, 11 kW nominal, with a 32.0 A unit fuse. It cannot be connected to 480 V 60 Hz; for that supply specify the MKF720-480V-C with integrated voltage and frequency changer. Provide a dedicated circuit and verify upstream protection against the 32 A fuse.

What are the mounting and duty-cycle limits for the MKF 720 in a production environment?

Allow rear access for the rear power switch and water connections; the cabinet is 1,580 mm wide and 2,005 mm high. Keep ambient dust low or inspect the condenser fan grid weekly. Live loads must not exceed 1,000 W heat compensation, and humidity control is limited to 10…95 °C chamber temperature.

What maintenance and accessories are required beyond the base delivery?

Plan annual maintenance with leak test per EU 517/2014, yearly steam humidifier service, condenser cleaning every 1–2 years, and electrical safety testing per EN 50678/50699. The 8760-hour service message needs BINDER reset. Options not included: water cooling plumbing, compressed air dryer, APT-COM™ 4 software, RS485, analog outputs, Pt 100 sensor, and disinfectant Art. 1002-0022.

Dimensional Drawings & Technical Documentation

Dimensional drawings

MKF 720 — drawing 1

Click drawing to inspect vector dimensions

Technical documentation

PDF
Data Sheet Model MKF 720 en
Datasheet ·1,0 МБ ·10 pp.
View PDF
PDF
MKF+MKFT (E5) 10 2026 en
Manual ·18,1 МБ ·179 pp.
View PDF