BINDER MKF 1020 CO₂
BINDER ·Made in Germany · In Active Production

BINDER MKF 1020 CO₂

BINDER MKF 1020 CO₂ — Climate chambers with Temperature -48…180 °C.

The MKF 1020 CO₂ is a 991 L alternating climate chamber with a working range of -48…180 °C and 10…98 % RH, extending the MKF series downward by 8 K versus the standard MKF 1020. Its 11.5 kW 400 V 3 N/PE 50 Hz supply and 1400 W heat compensation support rapid temperature cycling (6.2 K/min heating, 4.8 K/min cooling) for large-volume test loads.

Temperature
-48…180 °C

BINDER MKF Series — Model Comparison & Selection

Model Temperature, °CHeight, cmInterior volume, LLoad per rack, kgMax heat compensation, WNominal power, kW
MKF 1020 CO₂ Current -48–180200.599140140011.5
MKF 1020 -40–180200.599140150012.5
MKF 115 -40–180172.5115304004.8
MKF 240 -40–180171.5228304006.8
MKF 240 CO₂ -50...180171.3228309006.8
MKF 400 -40–180171417308008
MKF 400 CO₂ -50...180172.74173016007.9
MKF 56 -40–180144.560152502.8
MKF 720 -40–180200.573440100011
MKF 720 CO₂ -48–180200.573440110011

Full specifications

Core Performance & Functional Specifications
Temperature -48...180 °C
Interior volume 991 L (MKF1020O2-400V, 50 Hz)
Load per rack 40 kg (MKF1020O2-400V, 50 Hz)
Maximum heat compensation 1400 W
Nominal power 11.5 kW (MKF1020O2-400V, 50 Hz)
Article Number mfr 9020
Dimensions, Weight & Mechanical Design
Depth 1480 mm (MKF1020O2-400V, 50 Hz)
Height 2005 mm (MKF1020O2-400V, 50 Hz)
Width 1580 mm (MKF1020O2-400V, 50 Hz)
Electrical, Power & Drive Specifications
Power frequency 50 Hz (MKF1020O2-400V)
Rated voltage 400 V
Unit fuse 32.0 A (MKF1020O2-400V, 50 Hz)
Operating Conditions, Environment & Protection
Humidity range 10...98 % RH
Cooling down time from 180°C to -40°C mfr 70 min
Humidity fluctuation with humidity dependent on set value mfr 2 % r.F.
Standards, Safety & General Data
Average heating-up rate according to IEC 60068-3-5 between -40°C and 180°C mfr 6.2 K/min

Description

Construction and series positioning

Behavior under load and in different media

Installation, connection and control

Integration & Operating Notes

Electrical
Supply must be protected by a type B RCD

The chamber label and manual require operation only with residual current circuit breakers type B; standard type A or AC devices may not detect DC fault currents from the CO₂ refrigeration drive and are not permitted.

Instruction Manual, Section 1.5
Mounting
Room volume must be verified per EN 378-1

Because the refrigerant is CO₂ (R 744) at up to 120 bar, the installation room volume must be calculated according to EN 378-1:2016+A1:2020; do not install in unventilated recesses and observe minimum distances from Chapter 3.4.

Instruction Manual, Section 1.8
Process Limits
Humidity sensor is damaged by permanent exposure to solvents

The humidity sensor has tabulated maximum workplace concentrations for ammonia, acetone, ethanol, formaldehyde, ozone and others; permanent load above these limits will degrade or destroy the sensor, so test loads emitting such substances must be evaluated before humid operation.

Instruction Manual, Section 1.14
Maintenance
Service message at 8760 h or two years requires BINDER reset

After 8760 operating hours or two years the controller displays a service message; once acknowledged it reappears every two weeks until reset by BINDER Service, so plan the service interval to avoid recurring production interruptions.

Instruction Manual, Section 23.2
Maintenance
Replace door gasket only when chamber is cold

The door gasket must be replaced only when cold; attempting replacement while warm can damage the gasket and compromise the seal, so allow the chamber to cool to ambient before service.

Instruction Manual, Section 23.2
Cooling & Media
Clean condenser every 1–2 years and fan grid weekly in dusty air

Condensers should be cleaned every 1 to 2 years by a qualified technician; with increased dust, check the fan grid behind the left maintenance access flap weekly and suction-clean if visibly dirty after disconnecting the chamber.

Instruction Manual, Section 23.2

Selection & Integration Q&A

When should I choose the MKF 1020 CO₂ instead of the standard MKF 1020 or the MKF 240 CO₂?

Pick the MKF 1020 CO₂ when you need 991 L capacity and a -48 °C lower limit; the standard MKF 1020 stops at -40 °C. Choose the MKF 240 CO₂ only if -50 °C is required and 240 L suffices.

What electrical supply and protection must be provided for this chamber?

A 400 V 3 N/PE 50 Hz supply with 32.0 A fuse and a type B RCD; voltage tolerance is ±10 %. Nominal power is 11.5 kW, so size the feeder and upstream protection for the full load.

What water connections are required, and which related accessories are not included?

Freshwater (pipe or internal can) and wastewater connections are required. The condensate recycling lever, hose burst/reflux safety kit, and connection kit for freshwater pipe are options not in base delivery.

What are the maintenance intervals and which service tasks must be planned?

Annual maintenance and steam humidifier service at least yearly; condenser cleaning every 1–2 years; electrical safety test per EN 50678/50699 before first start and after repair; service message at 8760 h or two years until BINDER reset.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Data Sheet Model MKF CO₂ 1020 en
Datasheet ·828,4 КБ ·9 pp.
View PDF
PDF
0715 EN MKF CO2 E6 UM 10 2026
Manual ·11,3 МБ ·155 pp.
View PDF