BINDER MKF 400
BINDER ·Made in Germany · In Active Production

BINDER MKF 400

BINDER MKF 400 — Climate chambers with Temperature -40…180 °C.

The BINDER MKF 400 is a 417 L alternating climate chamber with a working range of -40 to 180 °C and 10–98 % RH, designed for rapid temperature cycling at up to 5 K/min. It is the mid-size 400 V model in the MKF series, positioned between the MKF 240 and MKF 720, and is intended for climatic stress testing and humidity-controlled conditioning in a laboratory or industrial test environment.

Temperature
-40…180 °C

BINDER MKF Series — Model Comparison & Selection

Model Temperature, °CHeight, cmInterior volume, LLoad per rack, kgMax heat compensation, WNominal power, kW
MKF 400 Current -40–180171417308008
MKF 1020 -40–180200.599140150012.5
MKF 1020 CO₂ -48–180200.599140140011.5
MKF 115 -40–180172.5115304004.8
MKF 240 -40–180171.5228304006.8
MKF 240 CO₂ -50...180171.3228309006.8
MKF 400 CO₂ -50...180172.74173016007.9
MKF 56 -40–180144.560152502.8
MKF 720 -40–180200.573440100011
MKF 720 CO₂ -48–180200.573440110011

Full specifications

Core Performance & Functional Specifications
Temperature -40...180 °C
Interior volume 417 L (MKF400-400V, 50 Hz)
Load per rack 30 kg (MKF400-400V, 50 Hz)
Maximum heat compensation 800 W
Nominal power 8 kW (MKF400-400V, 50 Hz)
Article Number mfr 9020
Dimensions, Weight & Mechanical Design
Depth 1400 mm (MKF400-400V, 50 Hz)
Height 1710 mm (MKF400-400V, 50 Hz)
Width 1115 mm (MKF400-400V, 50 Hz)
Electrical, Power & Drive Specifications
Power frequency 50 Hz (MKF400-400V)
Rated voltage 400 V
Unit fuse 16.0 A (MKF400-400V, 50 Hz)
Operating Conditions, Environment & Protection
Humidity range 10...98 % RH
Cooling down time from 180°C to -40°C mfr 115 min
Humidity fluctuation with humidity dependent on set value mfr 2.5 % r.F.
Standards, Safety & General Data
Average heating-up rate according to IEC 60068-3-5 between -40°C and 180°C mfr 5.0 K/min

Description

Construction and positioning

Behavior under load and in different media

Installation, connection, and control

Integration & Operating Notes

Electrical
Requires 400 V 3-phase supply with 16 A fusing

The MKF 400 draws 8 kW nominal power from a 3 N/PE 400 V 50 Hz supply and must be protected by a 16 A fuse. Verify that the site provides this configuration; for 480 V/60 Hz networks, the -C variant with voltage and frequency changer is required. Incorrect voltage or fusing can damage the chamber and void warranty.

Data Sheet Model MKF 400 en.pdf; Operating Manual MKF/MKFT (E5) 10/2026, Section 'Technical data'
Process Limits
Humidity control limited to 10–95 °C chamber temperature

When humidity is active, the temperature range is restricted to 10–95 °C; outside this range, humidity control must be switched off. This affects test profiles that combine low or high temperatures with humidity: ensure that the set points remain within the humidity-compatible range or disable humidity control accordingly.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Humidification / dehumidification system' and 'Technical data'
Maintenance
Annual maintenance and leak test are mandatory

Regular maintenance at least once a year is required, including a leak test per Regulation (EU) 517/2014. The steam humidifier must be maintained at least annually, with intervals depending on water quality and steam production. Condensers should be cleaned every 1–2 years by a qualified technician. Document all service in the log book.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Maintenance and service'
Maintenance
Service message appears after 8760 hours or two years

After 8760 operating hours or two years, a service message appears on the controller. After confirmation, it reappears every two weeks until reset by BINDER Service. Plan for a BINDER Service intervention to reset the message and perform any required maintenance at that time.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Maintenance and service'
Mounting
Rear power switch must be on for operation

For sizes 115 and above, including the MKF 400, a rear power switch is provided in addition to the main power switch. Both must be turned on during commissioning and troubleshooting. Ensure accessible clearance at the rear for operating this switch and for maintenance access.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Chamber description, instrument panel and power switches'
Process Limits
Humidity sensor exposed to ammonia and ozone limits

The humidity sensor has resistance limits for certain gases: ammonia (NH3) maximum workplace threshold 20 ppm / 14 mg/m³ and permanent load 5500 ppm / 4000 mg/m³; ozone (O3) 0.1 ppm / 0.2 mg/m³ and 0.5 ppm / 1 mg/m³. Verify that process atmospheres do not exceed these concentrations to avoid sensor damage.

Operating Manual MKF/MKFT (E5) 10/2026, Section 'Technical description', p.20 table

Selection & Integration Q&A

When should I choose the MKF 400 over the MKF 240 or MKF 720?

Choose the MKF 400 when you need 417 L interior volume and 30 kg per rack load, with the same -40…180 °C range and 5 K/min ramp rates as the series. The MKF 240 offers smaller capacity, while the MKF 720 provides larger volume; select based on test specimen size and throughput requirements.

What are the electrical supply requirements for the MKF 400, and can it be used on a 480 V/60 Hz network?

The standard MKF400-400V requires a 400 V, 3-phase/N/PE, 50 Hz supply with 16 A fusing and 8 kW nominal power. For 480 V/60 Hz networks, specify the MKF400-480V-C variant, which includes a voltage and frequency changer.

What maintenance tasks and intervals are required for the MKF 400?

Annual maintenance including leak test per EU 517/2014; steam humidifier maintenance at least yearly (more often with poor water quality); condenser cleaning every 1–2 years; weekly fan grid check in dusty environments; service message reset by BINDER Service after 8760 h or two years.

What accessories are not included in the base delivery but may be needed for operation?

The base MKF 400 does not include the water cooling option, water circle lever for condensate recycling, compressed air dryer, or external freshwater/wastewater cans (the latter only for MKF 56). Also, the disinfectant spray (Art. No. 1002-0022) and any interface cables for RS485 or analog outputs must be ordered separately.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Data Sheet Model MKF 400 en
Datasheet ·903,4 КБ ·9 pp.
View PDF
PDF
MKF+MKFT (E5) 10 2026 en
Manual ·18,1 МБ ·179 pp.
View PDF