Peter Huber Kältemaschinenbau Minichiller 300w OLÉ Kompakter
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Minichiller 300w OLÉ Kompakter

Peter Huber Kältemaschinenbau Minichiller 300w OLÉ Kompakter — Recirculating chillers with Noise level 53 dB.

The Minichiller 300w OLÉ Kompakter is a water-cooled recirculating chiller with a pressure/suction pump and OLÉ controller, operating from -20 to 40 °C with a maximum return temperature of 80 °C. It is distinguished from larger siblings (1000 series) by its compact 300-class capacity and fixed-speed pump. It serves as a point-of-use cooling source for laboratory and small process circuits requiring precise temperature control.

Noise level
53 dB

Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Minichiller 300w OLÉ Kompakter Current 53OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 1000 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1000w-H Kompakter —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Minichiller 1000w-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1000w Kompakter —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Minichiller 1200-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1200 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1200w-H Kompakter —Pilot ONEIII / FL-20–100——
Minichiller 1200w-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 280 OLÉ Kompakter 53OLÉI / NFL-5–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 300 OLÉ Kompakter 53OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 300w-H OLÉ Kompakter 51OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 600-H OLÉ Kompakter 56OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 600 Kompakter —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D110-120V 1~ 60Hz
Minichiller 600 OLÉ Kompakter 56OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 60Hz
Minichiller 600w OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 800 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 800w-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 53 dB(A)
Maximum delivery flow rate 14 l/min (pressure pump; 0, 25 bar)
Pump connection M16x1 AG male
Pump speed adjustable no
Pump type Pressure- and suction pump
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 23 kg
Electrical, Power & Drive Specifications
Current consumption 2 A (max)
Power supply 220-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 15 l/h (flow 15 °C)
Cooling water differential pressure 3 bar (min)
Cooling Water Pressure 6 bar (max)
Maximum return flow temperature 80 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and Series Positioning

Behavior Under Load and Media

Installation, Control, and Operation

Integration & Operating Notes

Mounting
Install below an ATEX-free zone with drip tray

The unit must not be placed in an ATEX zone due to explosion risk. A drip tray for condensation water and thermal fluid must be installed below the unit to contain leaks. Electrical lines directly below must be protected against liquid ingress.

Operation Manual, pages 13, 15, 28
Process Limits
Return temperature must not exceed 80 °C

Although the operating range is -20 to 40 °C, the permissible temperature in the return line is 80 °C. Exceeding this can overheat the unit. Also, cooling water inlet must be 5–20 °C; higher temperatures reduce cooling power and may require increased flow.

Datasheet, page 2
Cooling & Media
Cooling water differential pressure 3–6 bar required

The water-cooled refrigerating unit requires a cooling water supply with differential pressure between 3 and 6 bar at G1/2 male connections. Consumption is 15 l/h at 15 °C flow. Only drinking water or filtered river/sea water may be used; sea water is prohibited. Anti-corrosion agents are mandatory if salts are added.

Datasheet, page 1; Operation Manual, page 28
Electrical
Voltage tolerance ±5% with frequency ±2% only

The power supply must be 220–240 V 1~/2~ 50/60 Hz with voltage deviation of ±5% and simultaneous frequency tolerance of ±2%. Opposite-sign deviations are not allowed. Max current consumption is 2 A. A country-specific plug must be specified at ordering.

Datasheet, page 2
Process Limits
Plastic pump incompatible with acetone and polyglycols

The circulation pump is made of plastic and is not resistant to acetone or polyglycols (depending on manufacturer). Alternative fluids or a more resistant pump must be used. For freeze protection, water should be mixed with glysantine or ethylene glycol.

Datasheet, page 2
Installation
No valves or quick-release couplings in process lines

Do not install valves or quick-release couplings in the feed/discharge lines between the unit and the application, as this can cause overpressure damage, especially to glass apparatus. The pressure/suction pump has M16x1 AG male connections.

Operation Manual, page 31
Maintenance
Anti-corrosion agents mandatory with salts

If salts such as chlorides or bromide are added to the water circuit, the addition of anti-corrosion agents is mandatory to prevent corrosion damage. Regular maintenance should include checking water quality and refrigerant charge against room size limits.

Operation Manual, page 28

Selection & Integration Q&A

When should I choose the Minichiller 300w OLÉ over the 1000 series siblings?

Choose the 300w OLÉ for lower cooling capacity and compact footprint where the 1000 series is oversized. The 1000 and 1000-H variants offer higher capacity; the 'H' may indicate heating. Select based on required cooling power and whether heating is needed.

What are the cooling water supply requirements for this chiller?

It requires a cooling water circuit with G1/2 male connections, differential pressure 3–6 bar, and inlet temperature 5–20 °C. Consumption is 15 l/h at 15 °C. Only drinking or filtered river water; sea water prohibited. Anti-corrosion agents needed if salts added.

What are the installation environment and duty-cycle limits?

Install at 5–40 °C ambient, IP20, non-ATEX zone, with a drip tray below. Return line temperature must not exceed 80 °C. Do not move while operating. Electrical lines below must be protected from liquid ingress.

What maintenance and accessories are required but not included?

A drip tray for condensation/thermal fluid must be provided by the responsible body. Anti-corrosion agents are mandatory if salts are added. Country-specific plug must be specified at ordering. No valves or quick-release couplings in process lines.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Minichiller Operation Manual
Manual ·2,9 МБ ·84 pp.
View PDF
PDF
Minichiller 300w OLÉ
Datasheet ·102,8 КБ ·2 pp.
View PDF