Peter Huber Kältemaschinenbau Minichiller 1000w-H OLÉ Kompakter
Peter Huber Kältemaschinenbau Minichiller 1000w-H OLÉ Kompakter — Recirculating chillers.
The Minichiller 1000w-H OLÉ Kompakter is a compact recirculating chiller with a pressure-suction pump and OLÉ controller, covering -20 to 100 °C. Its 'w' suffix denotes a water-cooled condenser, distinguishing it from air-cooled siblings. It serves as a precise temperature-control source for laboratory and pilot processes requiring a stable fluid supply.
Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Minichiller 1000w-H OLÉ Kompakter Current | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | — | — |
| Minichiller 1200w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 280 OLÉ Kompakter | 53 | OLÉ | I / NFL | -5–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300 OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w-H OLÉ Kompakter | 51 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 600-H OLÉ Kompakter | 56 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 600 Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 110-120V 1~ 60Hz |
| Minichiller 600 OLÉ Kompakter | 56 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 60Hz |
| Minichiller 600w OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
Full specifications
| Pump connection | M16x1 AG male |
| Pump speed adjustable | no |
| Pump type | Pressure- and suction pump |
| Temperature range | -20...100 °C |
| Weight | 37 kg |
| Current consumption | 12 A (max) |
| Fuse rating | 16 A |
| Power supply | 208-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 15 kW (at 1 °C) |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 24 л/час (at 15°C, flow -20°C) at 15°C, flow -10°C: 30 л/час · at 15°C, flow 0°C: 36 l/h · at 15°C, flow 15°C: 39 l/h |
| Cooling water differential pressure | 3 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The 'w' in the model code indicates water cooling of the condenser, unlike the air-cooled Minichiller 1000-H OLÉ Kompakter. This makes the unit dependent on a facility cooling-water supply.
- The 'OLÉ' controller provides an OLED display and USB/RS232 interfaces, while the base 1000-H Kompakter uses a different controller.
- The pressure-suction pump is not speed-adjustable; whisper mode is not available on this variant.
Behavior under load and media
- Cooling capacity is rated 15 kW at 1 °C; actual capacity depends on site conditions.
- The pump delivers up to 24 l/min at 0.7 bar pressure and 18 l/min at 0.4 bar suction.
- The plastic pump is not resistant to acetone or polyglycols; alternative fluids require a more resistant pump.
- Cooling water consumption varies with flow temperature: 39 l/h at 15 °C, 36 l/h at 0 °C, 30 l/h at -10 °C, and 24 l/h at -20 °C.
Installation, connection and operation
- The unit requires a cooling-water differential pressure between 3 and 6 bar and an inlet temperature of 5–20 °C.
- Electrical supply is 208–240 V, 1~/2~, 50/60 Hz, with a maximum current of 12 A and a 16 A fuse.
- The OLÉ controller supports USB (Device) and RS232 interfaces for remote monitoring and software updates.
- A drip tray must be installed below the unit, and electrical lines below must be protected against liquid ingress.
Integration & Operating Notes
Condensation water and thermal fluid can escape; the responsible body must install a drip tray below the temperature control unit to contain leaks and prevent slip hazards.
Condensation can form at the cooling water connections; electrical lines directly below the temperature control unit must be protected against liquid ingress to avoid shock hazard.
The chiller requires cooling water with a differential pressure between 3 and 6 bar and an inlet temperature between 5 °C and 20 °C; outside these limits cooling capacity drops or condensation and corrosion risk increases.
Do not install valves or quick-release couplings in the feed/discharge lines to and from the application; they can cause overpressure damage, especially to glass apparatus.
Sea water must not be used for water cooling; only drinking water or filtered river/sea water is permitted. Anti-corrosion agents are mandatory if salts such as chlorides or bromide are added.
The unit must not be installed or started up within an ATEX zone because operation there can cause explosion; ensure the installation location is outside hazardous areas.
The unit uses R-290 (A3, H220) refrigerant; observe the refrigerant charge and room size to avoid exceeding the limit value per m³ of ambient air, and avoid ignition sources.
The unit has a level indicator with sight glass; low fill level can cause pump cavitation and poor temperature control, so check regularly during operation.
Selection & Integration Q&A
Choose the 'w' variant when a facility cooling-water supply with 3–6 bar differential and 5–20 °C inlet is available; it rejects heat to water and avoids room heat load. The air-cooled sibling is preferable where no water supply exists.
Cooling water must be drinking or filtered river/sea water (no sea water) at 5–20 °C and 3–6 bar differential, with connections G1/2 male. Electrical supply is 208–240 V, 1~/2~, 50/60 Hz, 12 A max, 16 A fuse.
Ambient temperature must be 5–40 °C, IP20 protection, no ATEX zone. Install a drip tray below, protect electrical lines below from liquid, and avoid moving the unit while operating.
A drip tray is mandatory. Anti-corrosion agents are required if salts are added to the water circuit. The plastic pump is not resistant to acetone or polyglycols. USB and RS232 cables are not included; order separately.