Peter Huber Kältemaschinenbau Minichiller 300 OLÉ Kompakter
Peter Huber Kältemaschinenbau Minichiller 300 OLÉ Kompakter — Recirculating chillers with Noise level 53 dB.
The Minichiller 300 OLÉ Kompakter is a compact recirculating chiller with a pressure-and-suction pump and OLED display, covering -20 to 40 °C with 0.3 kW cooling at 15 °C. It is the smallest OLÉ-controlled variant in the series, distinguished from the 1000-series siblings by its 0.3 kW capacity. It serves as a point-of-use cooling source for laboratory and industrial circuits requiring sub-ambient temperature control.
Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Minichiller 300 OLÉ Kompakter Current | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 1000 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | — | — |
| Minichiller 1200w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 280 OLÉ Kompakter | 53 | OLÉ | I / NFL | -5–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w-H OLÉ Kompakter | 51 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 600-H OLÉ Kompakter | 56 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 600 Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 110-120V 1~ 60Hz |
| Minichiller 600 OLÉ Kompakter | 56 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 60Hz |
| Minichiller 600w OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
Full specifications
| Noise level | 53 dB(A) |
| Pump connection | M16x1 AG male |
| Pump speed adjustable | no |
| Pump type | Pressure- and suction pump |
| Temperature range | -20...40 °C |
| Weight | 23 kg |
| Power supply | 220-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Maximum return flow temperature | 80 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The Minichiller 300 OLÉ Kompakter is the base-capacity model in the Minichiller OLÉ line; siblings (1000, 1000-H, 1000w-H) offer higher cooling capacities but share the same compact chassis format.
- The OLÉ controller provides an OLED display with 0.1 K resolution, USB (device) and RS232 interfaces, and a fixed-speed pressure-and-suction pump (no speed adjustment).
- The pump connection is M16x1 male; a hose connector NW12 and M16x1 sleeve nuts are included.
- The unit uses flammable refrigerant R-290 (A3, H220) with a charge of only 0.041 kg (GWP 0.02, CO2 equivalent 0.0 t).
Thermal behavior and media
- Cooling capacity is strongly temperature-dependent: 0.3 kW at 15 °C, 0.2 kW at 0 °C, 0.14 kW at -10 °C, and 0.07 kW at -20 °C. Load calculations must use the capacity at the lowest required operating temperature.
- Rated output data are valid at 20 °C room temperature; higher ambient temperatures reduce cooling capacity.
- The plastic pump is not resistant to acetone or polyglycols; for sub-zero operation, water should be mixed with glysantine or ethylene glycol for freeze protection.
- The maximum return-flow temperature is 80 °C.
Installation, control and operation
- The unit is IP20 and must be installed in an ambient temperature of 5 to 40 °C, away from ATEX zones. A drip tray for condensation water and thermal fluid must be provided below the unit.
- Electrical lines directly below the unit must be protected against liquid ingress because condensation can form.
- The supply must be 220–240 V, 1~/2~, 50/60 Hz, with voltage tolerance ±5 % and frequency tolerance ±2 %; the combination of -5 % voltage and +2 % frequency is not permitted. A country-specific plug must be specified at ordering.
- Minimum fuse 10 A, maximum fuse 16 A; maximum current 2.8 A.
- The unit is EMC Class A, Group 1 (EN55011), intended for industrial environments.
- Do not install valves or quick-release couplings in the feed/discharge lines to the application. Do not move the unit while operating.
- The optional Pt100 sensor input only displays (does not control) process temperature.
Integration & Operating Notes
The unit must not be installed or started within an ATEX zone because operation there can cause explosion. A condensation water / thermal fluid drip tray must be installed below the temperature control unit by the responsible body. Electrical lines directly below the unit must be protected against liquid ingress.
The combination of -5 % voltage and +2 % frequency is not allowed. The supply must be 220–240 V, 1~/2~, 50/60 Hz. Minimum fuse 10 A, maximum fuse 16 A at 2.8 A max current. A country-specific plug must be specified when ordering.
Cooling capacity is 0.3 kW at 15 °C, 0.2 kW at 0 °C, 0.14 kW at -10 °C, and 0.07 kW at -20 °C. The load must be checked at the lowest operating temperature. Rated output data are valid at 20 °C room temperature; higher ambient temperatures reduce capacity.
The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For sub-zero operation, water should be mixed with glysantine or ethylene glycol for freeze protection. Only drinking water or filtered river/sea water may be used as cooling water; sea water must not be used.
The addition of anti-corrosion agents is mandatory if salts such as chlorides or bromide have been added to the water circuit. The refrigerant charge is 0.041 kg with GWP 0.02, giving a CO2 equivalent of 0.0 t, which simplifies leak-check and F-gas documentation obligations.
The optional Pt100 sensor input only displays the process temperature and does not control it. The OLÉ controller provides an OLED display with 0.1 K resolution, USB (device) and RS232 interfaces. The pump speed is not adjustable.
Selection & Integration Q&A
Choose the 300 when your heat load at the lowest operating temperature is below 0.07 kW at -20 °C or 0.3 kW at 15 °C. The 1000-series siblings offer higher cooling capacity for larger loads; the 300 is the smallest OLÉ-controlled variant.
The pump connection is M16x1 male; a hose connector NW12 and M16x1 sleeve nuts are included. Do not install valves or quick-release couplings in the feed/discharge lines to the application. Ensure the circuit can withstand the pump pressure.
Anti-corrosion agents are mandatory if salts are added to the water circuit. For sub-zero use, mix water with glysantine or ethylene glycol. A country-specific plug must be specified at ordering. The Pt100 sensor is optional and only displays temperature.