Peter Huber Kältemaschinenbau Minichiller 300w-H OLÉ Kompakter
Peter Huber Kältemaschinenbau Minichiller 300w-H OLÉ Kompakter — Recirculating chillers with Noise level 51 dB.
The Minichiller 300w-H OLÉ Kompakter is a water-cooled recirculating chiller with a pressure/suction pump and 1 kW heater, covering -20 to 100 °C. Its OLÉ controller and USB/RS232 interface distinguish it from sibling 1000-series models, while the 300w designation indicates a lower-capacity refrigeration circuit. It serves as a compact temperature-control source for laboratory and pilot-scale processes requiring precise fluid conditioning.
Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Minichiller 300w-H OLÉ Kompakter Current | 51 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 1000 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | — | — |
| Minichiller 1200w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 280 OLÉ Kompakter | 53 | OLÉ | I / NFL | -5–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300 OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 600-H OLÉ Kompakter | 56 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 600 Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 110-120V 1~ 60Hz |
| Minichiller 600 OLÉ Kompakter | 56 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 60Hz |
| Minichiller 600w OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
Full specifications
| Noise level | 51 dB(A) |
| Heating capacity | 1 kW |
| Pump connection | M16x1 AG male |
| Pump speed adjustable | no |
| Pump type | Pressure- and suction pump |
| Temperature range | -20...100 °C |
| Weight | 25 kg |
| Power supply | 220-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 15 l/h (flow 15°C) |
| Cooling water differential pressure | 3 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Water-cooled refrigeration machine using natural refrigerant R-290 (A3, H220), with a plastic pressure/suction pump (non-speed-controlled) and integrated 1 kW heater.
- Safety class III/FL with adjustable overtemperature protection and low-level protection; IP20 protection and EN55011 Class A Group 1 (industrial EMC) classification.
- Compared to sibling Minichiller 1000 variants, this 300w model has a smaller refrigeration capacity; the OLÉ controller and USB/RS232 interface are shared with the 1000-H OLÉ and 1000 OLÉ Kompakter siblings, while the 1000w-H Kompakter lacks the OLÉ designation.
Behavior under load and media
- Cooling power drops steeply with decreasing temperature: 0.3 kW at 15 °C to 0.07 kW at -20 °C, so sizing must use the actual operating point, not nominal capacity.
- Temperature range -20 to 100 °C with 0.1 K display resolution on OLED; heating capacity 1 kW.
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol.
- Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM; only drinking water or filtered river/sea water may be used (sea water prohibited).
Installation, connection and control
- Cooling water connection G1/2 male; requires supply pressure between 3 and 6 bar differential and inlet temperature 5–20 °C; pipes must be insulated if condensation conditions occur.
- Pump connection M16x1 AG male; do not install valves or quick-release couplings in feed/discharge lines to the application.
- Power supply 220–240 V 1~/2~ 50/60 Hz; voltage tolerance ±5% only with simultaneous frequency tolerance ±2%, and certain combinations (e.g., -5% voltage with +2% frequency) are not allowed.
- Ambient temperature 5–40 °C; unit must not be installed in an ATEX zone; a drip tray for condensation water and thermal fluid must be installed below the unit; electrical lines directly below the unit must be protected against liquid ingress.
- Control via OLÉ controller with OLED display; interfaces USB (Device) and RS232; pump speed not adjustable.
Integration & Operating Notes
The unit must not be installed or started within an ATEX zone because operation there can cause explosion. A condensation water/thermal fluid drip tray must be installed below the unit, and electrical lines directly below must be protected against liquid ingress due to condensation risk.
Supply pressure below 3 bar or above 6 bar differential will prevent proper operation or damage the water circuit. Inlet temperature outside 5–20 °C reduces capacity and can cause condensation; pipes must be insulated if condensation conditions occur. Only drinking water or filtered river/sea water may be used; sea water is prohibited.
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed. The unit is classified EN55011 Class A Group 1 for industrial electromagnetic environments, not residential use.
The plastic pump is not resistant to acetone and polyglycols (depending on manufacturer), so these fluids must not be used as heat transfer media. For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
The addition of anti-corrosion agents is mandatory if salts such as chlorides or bromide have been added to the water circuit. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so water chemistry must be compatible with these materials.
Moving a temperature control unit that is in operation can cause burns, freezing and escaping thermal fluid. Shut down and allow to reach safe temperature before relocation.
Selection & Integration Q&A
Choose this 300w model when your cooling load is modest and you need the OLÉ controller with USB/RS232. The 1000-series siblings offer higher refrigeration capacity; select them if your load exceeds the 300w capacity at your operating point. The 1000w-H Kompakter lacks the OLÉ controller.
Cooling water must be supplied at 3–6 bar differential pressure and 5–20 °C inlet temperature, with G1/2 male connections. Only drinking water or filtered river/sea water is allowed (no sea water). Do not install valves or quick-release couplings in the feed/discharge lines to the application.
Ambient temperature must be 5–40 °C. The unit is IP20 and must be installed in a dry indoor location, not in an ATEX zone. A drip tray is required below the unit, and electrical lines below must be protected from liquid ingress. The unit is Class A Group 1 for industrial EMC.
Anti-corrosion agents are mandatory if salts (chlorides, bromide) are added to the water circuit. For freeze protection, mix water with glysantine or ethylene glycol. A drip tray for condensation/thermal fluid must be provided by the installer; cooling water connections and pump fittings are not supplied as hoses or couplings.