Peter Huber Kältemaschinenbau Minichiller 600w OLÉ Kompakter
Peter Huber Kältemaschinenbau Minichiller 600w OLÉ Kompakter — Recirculating chillers.
The Minichiller 600w OLÉ Kompakter is a compact recirculating chiller with a pressure/suction pump and OLÉ controller, covering -20 to 40 °C. It is distinguished within the series by its water-cooled condenser, requiring 3–6 bar differential pressure and 5–20 °C cooling water. It serves as a precise temperature control source for laboratory and industrial applications.
Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Minichiller 600w OLÉ Kompakter Current | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1000w Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 1200w-H Kompakter | — | Pilot ONE | III / FL | -20–100 | — | — |
| Minichiller 1200w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 280 OLÉ Kompakter | 53 | OLÉ | I / NFL | -5–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300 OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w-H OLÉ Kompakter | 51 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 300w OLÉ Kompakter | 53 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Minichiller 600-H OLÉ Kompakter | 56 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 600 Kompakter | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 110-120V 1~ 60Hz |
| Minichiller 600 OLÉ Kompakter | 56 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 60Hz |
| Minichiller 800 OLÉ Kompakter | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Minichiller 800w-H OLÉ Kompakter | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
Full specifications
| Maximum delivery flow rate | 24 l/min (pressure pump; 0, 7 bar) |
| Pump connection | M16x1 AG male |
| Pump speed adjustable | no |
| Pump type | Pressure- and suction pump |
| Temperature range | -20...40 °C |
| Weight | 36 kg |
| Power supply | 208-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 24 l/h (at 15°C, flow -20°C) at 15°C, flow -10°C: 30 l/h · at 15°C, flow 0°C: 36 l/h · at 15°C, flow 15°C: 39 l/h |
| Cooling water differential pressure | 3 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Maximum return flow temperature | 80 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and Series Positioning
The Minichiller 600w OLÉ Kompakter is a water-cooled recirculating chiller from the Minichiller series. Unlike sibling models such as the Minichiller 1000 series, this unit uses a water-cooled condenser, which requires a cooling water supply with a differential pressure of 3–6 bar and an inlet temperature of 5–20 °C. The 'w' in the model code denotes water cooling. The OLÉ controller provides an OLED display with 0.1 K resolution and interfaces including USB (Device) and RS232. The pump is a pressure- and suction pump with a maximum delivery flow rate of 24 l/min at 0.7 bar, and it is not speed-adjustable. The unit has a protection rating of IP20 and safety class I/NFL.
Behavior Under Load and Media
Operating temperature range is -20 to 40 °C, with a maximum return line temperature of 80 °C. Cooling water consumption varies with flow temperature: 36 l/h at 0 °C, 30 l/h at -10 °C, 24 l/h at -20 °C, and 39 l/h at 15 °C, all at a cooling water temperature of 15 °C. The plastic pump is not resistant to acetone or polyglycols, so these fluids must not be used. For freeze protection below 0 °C, a mixture of water with glysantine or ethylene glycol is recommended. The refrigerant is R-290 (propane, A3 flammable), requiring assessment of the installation area for flammable refrigerant handling.
Installation, Control and Operation
The unit must be installed indoors in a dry location (IP20) with ambient temperature between 5 and 40 °C. A drip tray for condensation water and thermal fluid must be installed below the unit. Electrical lines directly below the unit must be protected against liquid ingress. The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM; only drinking water or filtered river/sea water may be used (sea water is prohibited). Anti-corrosion agents are mandatory if salts such as chlorides or bromide are added. The unit is classified as EN55011 Class A Group 1, intended for industrial electromagnetic environments. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but not simultaneously in opposite directions. Do not install valves or quick-release couplings in the feed/discharge lines to the application.
Integration & Operating Notes
Condensation can form at the cooling water connections and thermal fluid may escape. A drip tray must be placed below the unit, and any electrical lines running directly underneath must be protected against liquid ingress to prevent shock hazard.
The water-cooled condenser requires a cooling water supply within these limits. Lower differential pressure reduces cooling capacity; higher pressure may damage the circuit. Verify building water system before installation.
The unit accepts 208–240 V 1~/2~ 50/60 Hz. Voltage and frequency tolerances may not be applied simultaneously in opposite directions. Class A Group 1 equipment may cause radio interference in residential areas.
If chlorides or bromide are added to the cooling water circuit, anti-corrosion agents are mandatory to prevent corrosion of copper, stainless steel, and other materials. Only drinking water or filtered river/sea water may be used; sea water is prohibited.
The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). Using these fluids will damage the pump and void reliable operation. For freeze protection below 0 °C, use water mixed with glysantine or ethylene glycol.
The unit must not be installed in an ATEX zone. The refrigerant is R-290 (propane, A3 flammable), so the room volume and refrigerant charge must be checked to avoid exceeding the limit value per m³ of ambient air. Additional safety measures may be required.
Selection & Integration Q&A
Choose this water-cooled model when a cooling water supply (5–20 °C, 3–6 bar differential) is available and you need -20 to 40 °C control with a pressure/suction pump. The 1000 series offers higher cooling capacity but may be air-cooled; select based on heat load and utilities.
The cooling water must be drinking water or filtered river/sea water (no sea water), with inlet temperature 5–20 °C and differential pressure 3–6 bar. Connections are G1/2 male. Do not install valves or quick-release couplings in the feed/discharge lines to the application.
Install indoors, dry location, ambient 5–40 °C, IP20 (not water-resistant). A drip tray is required below the unit. Do not install in ATEX zones. Electrical lines below must be protected from liquid. Class A Group 1 equipment for industrial EMC environments.
A drip tray for condensation/thermal fluid must be provided by the installer. Anti-corrosion agents are mandatory if salts are added to the water circuit. For freeze protection below 0 °C, mix water with glysantine or ethylene glycol. No specific maintenance intervals are given in the available documents.