Peter Huber Kältemaschinenbau CS 25 by Van der Heijden
Peter Huber Kältemaschinenbau CS 25 by Van der Heijden — Recirculating chillers with Noise level 60 dB.
The CS 25 is a 37-litre circulating bath chiller with a -20…15 °C working range, positioned as the smallest capacity model in the Cs Chiller series. It uses R-449A refrigerant and a 50:50 water-glycol mixture to hold process temperature in closed loops. Its 230 V single-phase supply and G1/2 male pump connection suit pilot-scale or laboratory cooling duties.
Peter Huber Kältemaschinenbau Cs Chiller Series — Model Comparison & Selection
| Model | Noise level, dB | Ambient temperature limit, °C | Minimum fill volume, m³ | Power supply | Pump connection | Temperature range, °C |
|---|---|---|---|---|---|---|
| CS 25 by Van der Heijden Current | 60 | 5–32 | 0.024 | 230V 1~ 50Hz | G1/2 AG male | -20–15 |
| CS 100 by Van der Heijden | 70 | 5–32 | 0.16 | 400V 3~ 50Hz | G3/4 AG male | -20–15 |
| CS 100-H by Van der Heijden | 71 | 5–32 | 0.175 | 400V 3~ 50Hz | G3/4 AG male | -20–85 |
| CS 200 by Van der Heijden | 78 | 5–32 | 0.225 | 400V 3~ 50Hz | G1 AG male | -20–15 |
| CS 200-H by Van der Heijden | 78 | 5–32 | 0.225 | 400V 3~ 50Hz | G1 AG male | -20–85 |
| CS 20-H by Van der Heijden | 57 | 5–32 | 0.024 | 230V 1~ 50Hz | G3/8 AG male | -20–85 |
| CS 50 by Van der Heijden | 63 | 5–32 | 0.1 | 400V 3~ 50Hz | G3/4 AG male | -20–15 |
| CS 75 by Van der Heijden | 66 | 5–32 | 0.16 | 400V 3~ 50Hz | G3/4 AG male | -20–15 |
| Huber CS 200-H | 78 | 5–32 | 0.225 | 460V 3~ 60Hz | G1 AG male | -20–85 |
| Huber CS 25 | 60 | 5–32 | 0.024 | 208V 2~ 60Hz | G1/2 AG male | -20–15 |
| Huber CS 250HT OD | 78 | -20–50 | 0.16 | 460V 3~ 60Hz | G3/4 AG male | 10–22 |
| Huber CS 330-H OD | 78 | -20–50 | 0.16 | 460V 3~ 60Hz | G1 AG male | -20–85 |
| Huber CS 550-H OD | 79 | -20–50 | 0.16 | 460V 3~ 60Hz | G1 AG male | -20–85 |
| Huber CS 550 OD | 79 | -20–50 | 0.16 | 460V 3~ 60Hz | G1 AG male | -20–15 |
| Huber LCS 80 | 77 | -20–50 | 0.04 | 460V 3~ 60Hz | G1 AG male | -45–15 |
Full specifications
| Noise level | 60 dB(A) |
| Bath volume | 37 l |
| Minimum fill volume | 24 l |
| Pump connection | G1/2 AG male |
| Temperature range | -20...15 °C |
| Weight | 110 kg |
| Fuse rating | 16 A |
| Power supply | 230V 1~ 50Hz |
| Ambient temperature limit | 5...32 °C |
| Protection rating | IP52 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The CS 25 is the lowest-capacity modification in the Cs Chiller line; siblings CS 100, CS 100-H, CS 125 and CS 125-H step up in size and noise level (60 dB(A) here versus 70–75 dB(A) for the larger units).
- Bath volume is 37 l with a usable fill window of 24–27 l, so the external loop and expansion volume must be planned inside that range.
- The unit is a single-phase 230 V/50 Hz machine with a 16 A fuse and a maximum current draw of 12.5 A; protection is IP52 and safety class I/NFL.
Behaviour in operation
- The working temperature range is -20…15 °C. The recommended heat-transfer fluid is a 50:50 water–monoethylene glycol mixture to avoid freezing and corrosion at the lower limit.
- Cooling capacity is rated at 20 °C ambient and falls as ambient temperature rises; the installation site must stay between 5 °C and 32 °C.
- Flow rate is set by a manual bypass valve on the rear of the unit, so rear access is required for commissioning and adjustment.
Installation and control
- The pump connection is G1/2 AG male. A digital level indicator shows the fill state and should be kept between the minimum and maximum marks.
- The refrigerant is R-449A (A1, H280), so leak detection and ventilation must account for a pressurized-gas hazard.
- EMC classification is Class A, Group 1 to EN55011, meaning the unit is intended for industrial environments and may cause interference in residential areas.
- A country-specific plug is supplied only if specified at ordering; otherwise the mains connection must be provided on site.
Integration & Operating Notes
The 230 V single-phase 50 Hz supply must be sized for a maximum current of 12.5 A and protected by a 16 A fuse. Voltage and frequency tolerances are interdependent: a -5% voltage deviation is permitted only with -2% frequency deviation, not with +2%, so the site supply quality must be checked before commissioning.
The 37-litre tank accepts a working fill of 24–27 l. The external loop, hoses and expansion volume must be counted so the unit is neither underfilled (pump cavitation, poor temperature stability) nor overfilled (overflow from the atmospheric tank). The digital level indicator should be checked against these limits.
The recommended heat-transfer fluid is a 50:50 water–monoethylene glycol mixture. Using plain water or a different ratio risks freezing, corrosion or reduced heat transfer at the -20 °C lower limit, so the fluid must be specified before the loop is filled.
Operation outside 5–32 °C ambient can prevent proper cooling and may damage the refrigeration circuit. Because cooling capacity is rated at 20 °C ambient and drops as ambient rises, a hot plant room also reduces available capacity below the datasheet values, so the site must be assessed for both limits.
Flow rate is adjusted by a manual bypass valve on the backside of the chiller. The installation layout must leave clear rear access for commissioning and later adjustment, otherwise the loop flow cannot be balanced to the process requirement.
Single-phase devices are delivered with a power cable and a country-specific plug only when this is specified at ordering. If the plug type is not confirmed with the order, the unit may arrive without a usable mains connection for the site, delaying commissioning.
The refrigerant is R-449A with GHS classification H280 (pressurized gas). Room ventilation and any leak-detection provisions must be designed for a pressurized-gas hazard rather than a simple asphyxiation or flammability scenario.
Selection & Integration Q&A
Pick the CS 25 when the duty fits a 37 l bath, a 24–27 l fill and a -20…15 °C range at 60 dB(A). The CS 100/125 and -H variants are larger, noisier units (70–75 dB(A)) for higher capacity; the CS 25 is the smallest modification in the series.
A 230 V single-phase 50 Hz supply protected by a 16 A fuse, sized for 12.5 A maximum current, with the country-specific plug confirmed at ordering. The process loop connects to the G1/2 AG male pump connection, and the fill must land between 24 and 27 l.
The site must stay between 5 and 32 °C ambient; outside this the refrigeration circuit can be damaged. Cooling capacity is rated at 20 °C ambient and drops as ambient rises, so a hot plant room reduces available cooling below datasheet values. IP52 also rules out washdown and heavy dust.
The country-specific mains plug is supplied only if specified at ordering. The 50:50 water–monoethylene glycol fluid must be provided on site, and rear access is needed to set flow via the manual bypass valve. The digital level indicator should be checked to keep fill within 24–27 l.