Peter Huber Kältemaschinenbau CS 100-H by Van der Heijden — Recirculating chillers with Noise level 71 dB.

The CS 100-H is a 37-litre-bath recirculating chiller with 6 kW heating and a -20…85 °C working range, distinguished from the CS 100 by its heating function. It serves as a temperature-control unit for industrial processes requiring both cooling and active heating, with a 400 V three-phase supply and 70 l/min pump.

Noise level
71 dB

Peter Huber Kältemaschinenbau Cs Chiller Series — Model Comparison & Selection

Model Noise level, dBAmbient temperature limit, °CMinimum fill volume, m³Power supplyPump connectionTemperature range, °C
CS 100-H by Van der Heijden Current 715–320.175400V 3~ 50HzG3/4 AG male-20–85
CS 100 by Van der Heijden 705–320.16400V 3~ 50HzG3/4 AG male-20–15
CS 200 by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–15
CS 200-H by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–85
CS 20-H by Van der Heijden 575–320.024230V 1~ 50HzG3/8 AG male-20–85
CS 25 by Van der Heijden 605–320.024230V 1~ 50HzG1/2 AG male-20–15
CS 50 by Van der Heijden 635–320.1400V 3~ 50HzG3/4 AG male-20–15
CS 75 by Van der Heijden 665–320.16400V 3~ 50HzG3/4 AG male-20–15
Huber CS 200-H 785–320.225460V 3~ 60HzG1 AG male-20–85
Huber CS 25 605–320.024208V 2~ 60HzG1/2 AG male-20–15
Huber CS 250HT OD 78-20–500.16460V 3~ 60HzG3/4 AG male10–22
Huber CS 330-H OD 78-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550-H OD 79-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550 OD 79-20–500.16460V 3~ 60HzG1 AG male-20–15
Huber LCS 80 77-20–500.04460V 3~ 60HzG1 AG male-45–15

Full specifications

Core Performance & Functional Specifications
Noise level 71 dB(A)
Bath volume 37 l
Heating capacity 6 kW
Minimum fill volume 175 l
Pump connection G3/4 AG male
Temperature range -20...85 °C
Dimensions, Weight & Mechanical Design
Weight 335 kg
Electrical, Power & Drive Specifications
Current consumption 25 A (max.)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Digital interface RS232
Materials, Media & Process Compatibility
Refrigerant R-449A (A1, H280) (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...32 °C
Protection rating IP52
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

The CS 100-H is an immersion circulator chiller with a 37-litre bath volume and a minimum filling capacity of 175 litres for the external circuit. Within the Cs Chiller series, it sits between the CS 100 (no heating, 70 dB(A)) and the larger CS 125/CS 125-H (75 dB(A)) and CS 200 (78 dB(A)). The -H suffix denotes the heating modification: 6 kW of heating capacity is added to the cooling function, enabling active temperature control across the full -20…85 °C range. The unit is air-cooled with a high-efficiency fan motor and uses R-449A refrigerant in the first stage.

Behavior under load and media

Cooling capacity is rated at 20 °C ambient and derates as ambient temperature rises, so selection must use site-specific ambient data. The circulation pump delivers up to 70 l/min at 3.7 bar maximum delivery pressure through G3/4 AG male connections; external piping pressure drop must be checked against this budget. The recommended thermofluid is a 50:50 water-monoethylene glycol mixture, which must be used to match performance and material compatibility. Flow rate is adjusted via a manual bypass valve on the backside of the chiller, requiring rear access for balancing during commissioning.

Installation, control and operation

The unit requires a 400 V 3~ 50 Hz supply with a 3x32A fuse and draws up to 25 A maximum. Three-phase devices under 63 A are delivered with cable but without a plug, so the installer must provide a suitable plug or hard-wired connection. Voltage and frequency tolerances are interdependent: -5% voltage with +2% frequency is not allowed, so supply quality must be verified. The interface is RS232. Protection rating is IP52, so the unit is protected against dust and dripping water but not against water jets or immersion. Ambient temperature must be between 5 °C and 32 °C. The equipment emits Class A Group 1 disturbances under EN55011, intended for industrial environments. The US-SNAP end-use is industrial process refrigeration.

Integration & Operating Notes

Electrical
Supply must be 400 V 3~ 50 Hz with 3x32A fusing

The unit draws up to 25 A and requires a 3x32A fuse. The electrical installation must be sized for this current, and the supply must be verified for voltage and frequency tolerances: -5% voltage with +2% frequency is not allowed.

CS 100-H Immersion Circulator Datasheet, page 1
Mounting
Ambient temperature must stay within 5…32 °C

Installation in a plant room outside this range will affect cooling capacity and may cause unreliable operation. Cooling capacity is rated at 20 °C ambient and drops as ambient rises, so site ambient conditions must be accounted for in selection.

CS 100-H Immersion Circulator Datasheet, page 1
Process Limits
Use 50:50 water-monoethylene glycol as thermofluid

The recommended thermofluid is a 50:50 mixture of water and monoethylene glycol. Using other fluids may compromise heat transfer, material compatibility, or freeze protection within the -20…85 °C range.

CS 100-H Immersion Circulator Datasheet, page 2
Maintenance
Ensure unobstructed air flow and cleaning access for condenser

The condenser is air-cooled with a high-efficiency fan motor. Adequate air flow and access for cleaning are needed to sustain cooling performance; blocked or dirty condensers will reduce capacity.

CS 100-H Immersion Circulator Datasheet, page 1
Electrical
Three-phase units under 63 A are delivered without a plug

The unit comes with a cable but no plug. The installer must provide a suitable plug or hard-wired connection rated for the supply and current.

CS 100-H Immersion Circulator Datasheet, page 2

Selection & Integration Q&A

When should I choose the CS 100-H instead of the CS 100 or CS 125-H?

Choose the CS 100-H when active heating (6 kW) is required alongside cooling over -20…85 °C. The CS 100 lacks heating; the CS 125-H offers higher capacity but is larger and louder (75 dB(A) vs 71 dB(A)).

What are the requirements for the electrical supply and protection of the CS 100-H?

It requires a 400 V 3~ 50 Hz supply with a 3x32A fuse and draws up to 25 A. The cable is supplied without a plug, so a suitable plug or hard-wired connection must be provided. Verify that voltage and frequency tolerances do not combine -5% voltage with +2% frequency.

What ambient and installation conditions must be met for reliable operation?

Install in an ambient temperature between 5 °C and 32 °C, with protection against water jets or immersion (IP52). Ensure rear access for the manual bypass valve used to adjust flow. Cooling capacity is rated at 20 °C ambient and derates at higher temperatures.

What maintenance and accessories are needed beyond the base delivery?

The condenser requires unobstructed air flow and periodic cleaning. The base delivery includes a cable but no plug; the installer must provide a plug or hard-wired connection. The recommended thermofluid is a 50:50 water-monoethylene glycol mixture, which must be procured separately.