Peter Huber Kältemaschinenbau Huber CS 250HT OD
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Huber CS 250HT OD

Peter Huber Kältemaschinenbau Huber CS 250HT OD — Recirculating chillers with Noise level 78 dB.

The Huber CS 250HT OD is a 460 V three-phase recirculating chiller with a 10–22 °C working range, designed for outdoor mounting down to -20 °C ambient. Its 34 kW cooling capacity at 20 °C ambient derates to 23 kW at 50 °C, so sizing must use site ambient. It serves as a central cooling source for processes requiring a stable, pump-circulated water-glycol loop.

Noise level
78 dB

Peter Huber Kältemaschinenbau Cs Chiller Series — Model Comparison & Selection

Model Noise level, dBAmbient temperature limit, °CMinimum fill volume, m³Power supplyPump connectionTemperature range, °C
Huber CS 250HT OD Current 78-20–500.16460V 3~ 60HzG3/4 AG male10–22
CS 100 by Van der Heijden 705–320.16400V 3~ 50HzG3/4 AG male-20–15
CS 100-H by Van der Heijden 715–320.175400V 3~ 50HzG3/4 AG male-20–85
CS 200 by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–15
CS 200-H by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–85
CS 20-H by Van der Heijden 575–320.024230V 1~ 50HzG3/8 AG male-20–85
CS 25 by Van der Heijden 605–320.024230V 1~ 50HzG1/2 AG male-20–15
CS 50 by Van der Heijden 635–320.1400V 3~ 50HzG3/4 AG male-20–15
CS 75 by Van der Heijden 665–320.16400V 3~ 50HzG3/4 AG male-20–15
Huber CS 200-H 785–320.225460V 3~ 60HzG1 AG male-20–85
Huber CS 25 605–320.024208V 2~ 60HzG1/2 AG male-20–15
Huber CS 330-H OD 78-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550-H OD 79-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550 OD 79-20–500.16460V 3~ 60HzG1 AG male-20–15
Huber LCS 80 77-20–500.04460V 3~ 60HzG1 AG male-45–15

Full specifications

Core Performance & Functional Specifications
Noise level 78 dB(A) (sound pressure level)
Bath volume 37 l
Minimum fill volume 160 l
Pump connection G3/4 AG male
Temperature range 10...22 °C
Dimensions, Weight & Mechanical Design
Weight 510 kg (net)
Electrical, Power & Drive Specifications
Current consumption 27 A (max)
Power supply 460V 3~ 60Hz
Interfaces, Connections & Control
Digital interface RS232
Operating Conditions, Environment & Protection
Ambient temperature limit -20...50 °C (permissible)
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Electrical
Supply must stay within combined voltage/frequency envelope

The ±5% voltage tolerance applies only with ±2% frequency tolerance, and -5% voltage with +2% frequency is explicitly not allowed. Verify site power quality before connection to avoid damage or malfunction.

Huber CS 250HT OD Technical Data, page 2
Electrical
Cable supplied without plug; installer provides termination

Three-phase devices under 63 A are delivered with a cable but no plug, so the installer must supply a suitable plug or hard-wired connection rated for 27 A and protected by 3×35 A fuses.

Huber CS 250HT OD Technical Data, page 2
Process Limits
External circuit volume must fall within 160–175 l

The chiller has a minimum filling capacity of 160 l and a maximum of 175 l; the external loop plus internal volume must be sized within this range to ensure proper pump operation and temperature stability.

Huber CS 250HT OD Technical Data, page 1
Cooling & Media
Use 50:50 water–monoethylene glycol thermofluid

The recommended thermofluid is a 50:50 mixture of water and monoethylene glycol; using other fluids may impair heat transfer or freeze protection. The open tank has a digital level indicator for monitoring.

Huber CS 250HT OD Technical Data, page 2
Mounting
Outdoor mounting permitted down to -20 °C ambient

The unit is suitable for outside mounting with a minimum environmental temperature of -20 °C and maximum of +50 °C, and electrical components are IP54 rated. Ensure the installation location meets these limits.

Huber CS 250HT OD Technical Data, page 1
Control & I/O
Remote panel on 20 m cable allows separated mounting

The operating panel is delivered as a remote control connected via a 20 m cable, so it can be mounted up to 20 m away from the chiller; plan cable routing accordingly.

Huber CS 250HT OD Technical Data, page 1
Maintenance
Monitor fluid level via digital indicator

The atmospheric open tank has a digital level indicator; maintain the fluid level within the specified filling capacity to prevent pump cavitation or overflow.

Huber CS 250HT OD Technical Data, page 1

Selection & Integration Q&A

When should I choose the CS 250HT OD over the smaller CS 125 or CS 100 models?

Choose the CS 250HT OD when you need higher cooling capacity (34 kW at 20 °C ambient) and can accommodate a 160–175 l circuit volume. The CS 125 and CS 100 are smaller siblings with lower noise (75 and 70 dB(A)) but are not specified for the same capacity or outdoor range.

What are the power supply and protection requirements for this chiller?

It requires 460 V 3~ 60 Hz, draws up to 27 A, and needs 3×35 A fuses. Voltage tolerance is ±5% only with ±2% frequency tolerance; -5% voltage with +2% frequency is not allowed. A cable is supplied but no plug.

Can the CS 250HT OD be installed outdoors, and what ambient limits apply?

Yes, it is suitable for outside mounting from -20 °C to +50 °C ambient, with electrical components rated IP54. Cooling capacity derates from 34 kW at 20 °C ambient to 23 kW at 50 °C ambient, so size for the actual site ambient.

What maintenance and accessories are required beyond the base delivery?

The base delivery includes a cable but no plug; the installer must provide a suitable plug or hard-wired connection. The recommended thermofluid is a 50:50 water–monoethylene glycol mixture, which must be supplied separately. Monitor fluid level via the digital indicator and maintain 160–175 l fill.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Huber CS 250HT OD Technical Data
Datasheet ·114,5 КБ ·2 pp.
View PDF