Peter Huber Kältemaschinenbau Minichiller 1200w-H OLÉ Kompakter
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Minichiller 1200w-H OLÉ Kompakter

Peter Huber Kältemaschinenbau Minichiller 1200w-H OLÉ Kompakter — Recirculating chillers.

Water-cooled recirculating chiller with a pressure/suction pump and a fixed-speed plastic pump head, rated for -20 to 100 °C process temperature. The 'w' suffix denotes water cooling (G1/2 male, 3–6 bar differential), distinguishing it from air-cooled siblings in the Minichiller 1000/1200 series. It serves as a compact secondary cooling source for laboratory and pilot circuits where facility water is available.

Peter Huber Kältemaschinenbau Minichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Minichiller 1200w-H OLÉ Kompakter Current —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1000 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1000w-H Kompakter —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Minichiller 1000w-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1000w Kompakter —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Minichiller 1200-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1200 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 1200w-H Kompakter —Pilot ONEIII / FL-20–100——
Minichiller 280 OLÉ Kompakter 53OLÉI / NFL-5–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 300 OLÉ Kompakter 53OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 300w-H OLÉ Kompakter 51OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 300w OLÉ Kompakter 53OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Minichiller 600-H OLÉ Kompakter 56OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 600 Kompakter —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D110-120V 1~ 60Hz
Minichiller 600 OLÉ Kompakter 56OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 60Hz
Minichiller 600w OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 800 OLÉ Kompakter —OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Minichiller 800w-H OLÉ Kompakter —OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz

Full specifications

Core Performance & Functional Specifications
Maximum delivery flow rate 24 l/min (pressure pump max; 0, 7 bar)
Pump connection M16x1 AG male
Pump speed adjustable no
Pump type Pressure- and suction pump
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 37 kg
Electrical, Power & Drive Specifications
Current consumption 12 A (max)
Fuse rating 16 A
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 24 л/час (at 15°C, flow -20°C)
at 15°C, flow -10°C: 30 л/час · at 15°C, flow 0°C: 36 l/h · at 15°C, flow 15°C: 39 l/h
Cooling water differential pressure 3 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Cooling water differential pressure must stay between 3 and 6 bar

Below 3 bar the water-cooled refrigeration circuit cannot operate correctly; above 6 bar the cooling water circuit is overpressured. Verify the facility supply at the G1/2 male connections under flow, not only static pressure.

Datasheet Minichiller 1200w-H OLÉ, Specifications
Electrical
Voltage and frequency tolerances are coupled, not independent

A ±5% voltage tolerance is permitted only with a simultaneous ±2% frequency tolerance; combinations such as -5% voltage with +2% frequency are explicitly not allowed. Confirm the site supply against this combined envelope before commissioning.

Datasheet Minichiller 1200w-H OLÉ, Specifications
Process Limits
No valves or quick-release couplings in the application lines

Do not install valves or quick-release couplings in the feed/discharge lines from the unit to the application or from the application back to the unit; closing them can overpressure the application, especially glass apparatus.

Operation Manual, Installation
Cooling & Media
Plastic pump incompatible with acetone and polyglycols

The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer), so these must not be used as heat transfer fluids. For freeze protection, mix water with glysantine or ethylene glycol rather than using pure water.

Datasheet Minichiller 1200w-H OLÉ, Specifications
Control & I/O
Pt100 option is display-only and factory-fitted

The optional Pt100 sensor connection (#10519) displays process temperature but does not control it, and is available only factory-fitted at additional cost. Engineers needing external process temperature control must select a different configuration.

Datasheet Minichiller 1200w-H OLÉ, Overview
Electrical
Specify country-specific plug at ordering

Single/two-phase devices (100 V to 240 V) are supplied with a power cable and country-specific plug that must be specified when ordering; failing to specify it can delay commissioning.

Datasheet Minichiller 1200w-H OLÉ, Specifications
Maintenance
Do not move the unit while operating

Moving a unit in operation risks burns, freezing and escaping thermal fluid. Shut down and allow temperature equalization before relocation.

Operation Manual, Operation

Selection & Integration Q&A

When should I choose the 1200w-H OLÉ over the air-cooled 1000-H OLÉ or the 1000w-H?

Pick the 1200w-H OLÉ when facility cooling water (5–20 °C, 3–6 bar differential) is available and you need the larger 1200-size water-cooled unit. Choose an air-cooled 1000-H variant if no water supply exists; choose the 1000w-H if the smaller 1000-size capacity suffices.

What facility water supply and electrical supply must be in place before commissioning?

Cooling water at 5–20 °C with 3–6 bar differential pressure at G1/2 male connections, sized with margin because flow demand rises as water temperature increases. Electrical: 208–240 V, 1~/2~, 50/60 Hz within the coupled ±5% voltage / ±2% frequency envelope, 16 A fuse, country-specific plug specified at order.

Where can the unit be installed and what environmental limits apply?

Dry location, IP20, ambient 5–40 °C, not in an ATEX zone. Install a drip tray below, protect electrical lines below against liquid ingress, and verify R-290 charge versus room volume. Do not move the unit while operating.

What is not included in base delivery and what maintenance/consumables should be planned?

The country-specific plug must be specified at ordering; the Pt100 display option (#10519) is factory-fitted at extra cost. Plan anti-corrosion dosing if salts are added to the water circuit, and glysantine or ethylene glycol for freeze protection. No maintenance interval is stated in the supplied digests.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Minichiller Operation Manual
Manual ·2,9 МБ ·84 pp.
View PDF
PDF
Minichiller 1200w-H OLÉ
Datasheet ·107,2 КБ ·2 pp.
View PDF