Peter Huber Kältemaschinenbau Petite Fleur-eo Dynamisches
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Petite Fleur-eo Dynamisches

Peter Huber Kältemaschinenbau Petite Fleur-eo Dynamisches — Temperature control units with Noise level 58 dB.

The Petite Fleur-eo Dynamisches is a variable-speed pressure-pump temperature control unit for external open operation, with no expansion tank. It covers -40 to 200 °C with 1.6–2 kW heating and 0.04 kW cooling at -40 °C, distinguishing it from larger Grande Fleur siblings. It serves low-heat-load processes requiring precise Pilot ONE control.

Noise level
58 dB

Peter Huber Kältemaschinenbau Unistate Bis 45C Series — Model Comparison & Selection

Model Noise level, dBDisplay resolutionPower supplyPump connectionPump typeTemperature range, °C
Petite Fleur-eo Dynamisches Current 580, 01 K220-240V 1~/2~ 50/60HzM16x1 AG malePressure pump, variable -40–200
Grande Fleur Dynamisches ——————
Grande Fleur w Dynamisches —0, 01208-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable -40–200
Grande Fleur w-eo Dynamisches ——————
Petite Fleur w Dynamisches —0, 01220-240V 1~/2~ 50/60HzM16x1 AG malePressure pump, variable -40–200
Unistat 410w Dynamisches 610, 01 K220-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable -45–250
Unistat 425w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat 430w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P405w Dynamisches —0, 01460V 3~ 60HzM30x1, 5 AG malemagnetically coupled, st-45–250
Unistat P425 Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P425w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P430 Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P430w Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250

Full specifications

Core Performance & Functional Specifications
Noise level 58 dB(A) (sound pressure level)
Control output POKO ONE (potential-free contact)
Filling volume 2 l (min)
Maximum delivery flow rate 25 l/min (pressure pump max; 0, 9 bar)
Pump connection M16x1 AG male
Pump speed adjustable Yes
Pump type Pressure pump, variable speed
External sensor connection Pt100
Temperature range -40...200 °C
Alarm message mfr optic, acoustic, relay
Dimensions (W x D x H) mfr 260 x 450 x 504 mm
Heating capacity mfr 1, 6 - 2 kW
Refrigeration machine mfr air-cooled, natural refrigerant
Control input mfr ECS ONE
Dimensions, Weight & Mechanical Design
Weight 43 kg (net)
Electrical, Power & Drive Specifications
Power supply 220-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Display resolution 0, 01 K
Digital interface Ethernet, USB (Host u. Device), RS232
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Maximum viscosity 50 mm²/s (max permissible)
Refrigerant quantity 1st stage mfr 0, 08 kg (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C (permissible)
Protection rating IP20
Cooling capacity mfr 0, 04 kW (at -40 °C)
Standards, Safety & General Data
Safety class III / FL

Description

Construction and positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Mounting
Do not install in ATEX zone without Ex px cabinet

The unit must not be installed or started in a hazardous area unless an Ex px cabinet is used; verify the site classification before installation to avoid a safety violation.

Grande Fleur Operation Manual, page 13
Installation
External loop must provide expansion volume and at least 2 l fill

Since the unit has no expansion tank, the external application must accommodate fluid expansion and ensure a minimum filling volume of 2 l to avoid cavitation and poor temperature control.

Petite Fleur-eo Datasheet, page 1
Electrical
Power cable length limited to 3 m for safe disconnection

Do not use a power cable longer than 3 m so the unit can be disconnected from the mains at any time; plan the power outlet location accordingly.

Grande Fleur Operation Manual, page 31
Control & I/O
Selectable internal/process control mode requires sensor strategy

The Pilot ONE controller allows choosing between internal and process temperature control; for process control, connect an external Pt100 sensor and configure the setpoint accordingly.

Petite Fleur-eo Datasheet, page 1
Maintenance
Check and replace air filter mat at regular intervals

The air filter mat behind the air inlet must be checked and replaced regularly to prevent reduced airflow, which can cause overheating and reduced cooling performance.

Grande Fleur eo Operation Manual, page 16

Selection & Integration Q&A

When should I choose the Petite Fleur-eo Dynamisches over a Grande Fleur variant?

Choose this model for low heat loads (0.04 kW cooling at -40 °C) and space-constrained installations; Grande Fleur siblings offer higher capacities but are larger. This unit is for external open operation only, without expansion tank.

What are the requirements for connecting the external application loop?

Use M16x1 male fittings; ensure the external loop provides at least 2 l fill volume and accommodates expansion. Connect circulation flow to the lower port and return to the higher port to vent air. Check pressure drop against 0.9 bar max.

What maintenance and accessories are required that are not included in base delivery?

The air filter mat must be checked and replaced regularly. A country-specific plug must be specified at order. A drip tray and, if refrigerant charge exceeds 8 g/m³ room air, a gas warning sensor are required. Thermal fluid is not included.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Grande Fleur Operation Manual
Manual ·3,1 МБ ·88 pp.
View PDF
PDF
Grande Fleur eo Operation Manual
Manual ·3,0 МБ ·84 pp.
View PDF
PDF
Petite Fleur-eo
Datasheet ·89,9 КБ ·2 pp.
View PDF