Peter Huber Kältemaschinenbau CS 100 by Van der Heijden
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau CS 100 by Van der Heijden

Peter Huber Kältemaschinenbau CS 100 by Van der Heijden — Recirculating chillers with Noise level 70 dB.

The CS 100 is a three-phase 400 V circulating chiller with a 37 l bath and a working range of -20 to 15 °C, positioned as the smallest and quietest unit in the Cs Chiller series. It requires a 160–175 l loop fill and a 5–32 °C plant room, and serves industrial process refrigeration with R-449A refrigerant.

Noise level
70 dB

Peter Huber Kältemaschinenbau Cs Chiller Series — Model Comparison & Selection

Model Noise level, dBAmbient temperature limit, °CMinimum fill volume, m³Power supplyPump connectionTemperature range, °C
CS 100 by Van der Heijden Current 705–320.16400V 3~ 50HzG3/4 AG male-20–15
CS 100-H by Van der Heijden 715–320.175400V 3~ 50HzG3/4 AG male-20–85
CS 200 by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–15
CS 200-H by Van der Heijden 785–320.225400V 3~ 50HzG1 AG male-20–85
CS 20-H by Van der Heijden 575–320.024230V 1~ 50HzG3/8 AG male-20–85
CS 25 by Van der Heijden 605–320.024230V 1~ 50HzG1/2 AG male-20–15
CS 50 by Van der Heijden 635–320.1400V 3~ 50HzG3/4 AG male-20–15
CS 75 by Van der Heijden 665–320.16400V 3~ 50HzG3/4 AG male-20–15
Huber CS 200-H 785–320.225460V 3~ 60HzG1 AG male-20–85
Huber CS 25 605–320.024208V 2~ 60HzG1/2 AG male-20–15
Huber CS 250HT OD 78-20–500.16460V 3~ 60HzG3/4 AG male10–22
Huber CS 330-H OD 78-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550-H OD 79-20–500.16460V 3~ 60HzG1 AG male-20–85
Huber CS 550 OD 79-20–500.16460V 3~ 60HzG1 AG male-20–15
Huber LCS 80 77-20–500.04460V 3~ 60HzG1 AG male-45–15

Full specifications

Core Performance & Functional Specifications
Noise level 70 dB(A)
Bath volume 37 l
Minimum fill volume 160 l
Pump connection G3/4 AG male
Temperature range -20...15 °C
Dimensions, Weight & Mechanical Design
Weight 265 kg
Electrical, Power & Drive Specifications
Current consumption 12 A
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Digital interface RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...32 °C
Protection rating IP52
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior and media

Installation and operation

Integration & Operating Notes

Electrical
Provide a 3x16 A protected three-phase feed and fit the site plug

The chiller is delivered with a cable but without a plug because it draws 12 A on a 400 V 3~ 50 Hz supply. The installer must size upstream protection to 3x16 A and provide a mating plug; voltage and frequency must stay within ±5% and ±2% respectively, and not at the unfavorable combination simultaneously.

CS 100 Circulating Bath — Technical Datasheet, pages 1–2
Process Limits
Plan loop volume for 160–175 l and use 50:50 water–glycol

The minimum filling capacity of 160 l (up to 175 l) is far larger than the 37 l internal bath, so the external loop, expansion volume and fluid quantity must be engineered before commissioning. The recommended thermofluid is a 50:50 water–monoethylene glycol mixture to match freeze protection and heat transfer.

CS 100 Circulating Bath — Technical Datasheet, pages 1–2
Mounting
Keep rear clearance for the manual bypass flow adjustment

Flow rate is adjusted via a manual bypass valve on the backside of the chiller, so the installation layout must leave the rear accessible for commissioning and later adjustment. The unit weighs 265 kg and produces about 70 dB(A), so floor loading and acoustic separation from occupied areas should be considered.

CS 100 Circulating Bath — Technical Datasheet, page 1
Cooling & Media
Hold the plant room within 5–32 °C or derate capacity

Cooling capacity is rated at 20 °C ambient and drops as ambient temperature rises, so the plant room must be kept within the 5–32 °C window and selection must use the actual room temperature rather than the 20 °C rating. Refrigerant R-449A is classified A1 with GHS H280, so ventilation and handling precautions follow that classification.

CS 100 Circulating Bath — Technical Datasheet, pages 1–2
Electrical
Class A industrial EMC and RS232 interface

The unit is EN55011 Class A Group 1, intended for industrial environments; in residential areas additional EMC measures may be required. An RS232 interface is available for control and monitoring, and the equipment is compliant with US-SNAP for industrial process refrigeration, so the end use must match that application.

CS 100 Circulating Bath — Technical Datasheet, page 2

Selection & Integration Q&A

When should I choose the CS 100 rather than the CS 100-H or CS 125?

Pick the CS 100 when the -20 to 15 °C range and 37 l bath suffice and 70 dB(A) is the quietest option in the series; the CS 100-H, CS 125 and CS 200 step up in capacity and sound level (71–78 dB(A)).

What hydraulic and electrical provisions must be ready before the CS 100 arrives?

Provide G3/4 female mating fittings for the G3/4 male pump connections, a 160–175 l loop filled with 50:50 water–monoethylene glycol, and a 400 V 3~ 50 Hz feed protected at 3x16 A with a site-fitted plug.

What ambient and placement limits apply to the CS 100 installation?

Operate within 5–32 °C ambient, knowing capacity is rated at 20 °C and falls as ambient rises. Keep the rear accessible for the manual bypass valve, allow for 265 kg weight and about 70 dB(A), and respect IP52 and Class A EMC.

What is not included in base delivery and what service access is needed?

The three-phase cable is supplied but the plug is not, and the thermofluid charge must be provided on site. Rear access is required for the bypass flow adjustment; no maintenance intervals or consumables are stated in the supplied datasheet.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
CS 100 Circulating Bath — Technical Datasheet
Datasheet ·198,0 КБ ·2 pp.
View PDF