Peter Huber Kältemaschinenbau TC50E-F
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau TC50E-F

Peter Huber Kältemaschinenbau TC50E-F — Immersion coolers with Noise level 60 dB.

The TC50E-F is an air-cooled immersion cooler with a 900 mm Pt100 probe, covering -50 to 50 °C using flammable R-290 refrigerant. It is the compact 0.2 kW-at--30 °C member of the TC series, distinguished from the TC100/TC100E variants by lower capacity and a 60 dB(A) noise level. It is used for direct low-temperature cooling of baths and process fluids where no pump is required.

Noise level
60 dB

Peter Huber Kältemaschinenbau Eintauchkuehler Kuehlfallen Series — Model Comparison & Selection

Model Noise level, dBControllerPower supplyRefrigerantSafety classTemperature range, °C
TC50E-F Current 60MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
CT50 Single OLÉ 59OLÉ220-240V 1~/2~ 50/60HzR-290 (A3, H220)III / FL-50–50
TC100 55ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC100E-F 55MPC110-120V 1~ 60HzR-1150 (A3, H220)I / NFL-100–40
TC100-F 58ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC45 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E-F 54MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45-F 59ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC50 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50-F 60ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Pump speed adjustable no
Pump type no pump
External sensor connection Pt100
Temperature range -50...50 °C
Temperature stability mfr ±0, 5 K
Alarm message mfr optic, acoustic
Dimensions (W x D x H) mfr 260 x 330 x 415 mm
Refrigeration machine mfr air-cooled, natural refrigerant
Dimensions, Weight & Mechanical Design
Weight 25 kg (net)
Electrical, Power & Drive Specifications
Current consumption 3 A (max.)
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller MPC
Temperature display LED Display
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Refrigerant quantity 1st stage mfr 0, 06 kg (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity mfr 0, 2 kW (at -30 °C)
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Thermal behavior

Installation, control and operation

Integration & Operating Notes

Electrical
Fuse the circuit between 10 A and 16 A

The supply is 208-240 V single- or two-phase at 50/60 Hz with a maximum current of 3 A, but the datasheet requires circuit fusing no lower than 10 A and no higher than 16 A; a smaller protective device may trip on compressor inrush, and a larger one no longer protects the unit.

TC50E-F Immersion Circulator Datasheet, Technical Data
Electrical
Do not combine voltage and frequency deviations of opposite sign

Voltage and frequency tolerances are coupled: ±5 % voltage is permitted only together with ±2 % frequency, and a -5 % voltage with +2 % frequency is explicitly not allowed. Verify the site supply against this rule before commissioning, since a supply inside each individual band can still violate the combined limit.

TC50E-F Immersion Circulator Datasheet, Technical Data
Process Limits
Size the heat load at the real operating point, not at 0 °C

Cooling capacity is 0.3 kW at 0 °C, 0.26 kW at -20 °C and 0.2 kW at -30 °C, all valid at 20 °C room temperature. Capacity drops further as ambient rises, so the process load and pull-down time must be calculated at the lowest intended temperature and the actual room condition.

TC50E-F Immersion Circulator Datasheet, Technical Data
Process Limits
The unit cannot heat above 50 °C

The working range is -50 to 50 °C. Processes that require heating above 50 °C, or that may exothermically exceed it, are outside the unit's capability and need a different circulator; the upper limit also bounds any bath or fluid the probe is immersed in.

TC50E-F Immersion Circulator Datasheet, Technical Data
Process Limits
Probe reach is limited to 900 mm plus a 1150 mm flexible lead

The Pt100 probe is 13 mm in diameter and 900 mm long, connected by a 1150 mm flexible lead. The immersion depth and the distance from the bath or vessel to the unit must be checked against these dimensions before the mounting position is fixed.

TC50E-F Immersion Circulator Datasheet, Technical Data
Electrical
Specify the country-specific plug when ordering

Single- and two-phase devices from 100 V to 240 V are delivered with a power cable and a country-specific plug that must be stated at order. Confirm the plug type against the site socket before purchase, as it is not a universal accessory.

TC50E-F Immersion Circulator Datasheet, Technical Data
Electrical
Class A equipment is for industrial environments only

The unit is classified Class A, Group 1 to EN55011 and may cause radio interference in residential areas. Plan the installation for an industrial EMC environment, or add filtering if it must share a supply with sensitive electronics.

TC50E-F Immersion Circulator Datasheet, Technical Data
Cooling & Media
R-290 is flammable: plan ventilation and ignition-source control

The first stage holds 0.06 kg of R-290 (A3, H220), a flammable natural refrigerant. Site approval, ventilation and avoidance of ignition sources in the vicinity must be addressed; the equipment is compliant with US-SNAP for industrial process refrigeration and with applicable EU laws.

TC50E-F Immersion Circulator Datasheet, Technical Data and Compliance
Control & I/O
Continuous compressor operation is normal, not a fault

The refrigeration unit runs continuously and the MPC controller regulates temperature through a solenoid valve in the cooling circuit. Service personnel should not interpret a non-cycling compressor as a control failure; alarms are indicated optically and acoustically on the unit.

TC50E-F Immersion Circulator Datasheet, Operation

Selection & Integration Q&A

When should I choose the TC50E-F rather than the TC100E-F or the CT50 Single OLÉ?

Pick the TC50E-F when the load is at or below its 0.2 kW at -30 °C and 0.3 kW at 0 °C, and 60 dB(A) is acceptable. The TC100/TC100E/TC100E-F siblings run at 55 dB(A) and suit higher loads or quieter sites; the CT50 Single OLÉ sits at 59 dB(A).

What supply and protective device does the TC50E-F need, and what comes with the cable?

208-240 V single- or two-phase, 50/60 Hz, max. 3 A, fused 10-16 A. Voltage and frequency deviations must not have opposite signs. The power cable and country-specific plug are supplied only if specified at order.

Where can the unit be installed and how must it be positioned relative to the bath?

Ambient must stay within 5-40 °C with the datasheet space clearances around the air-cooled condenser. The 13 mm probe is 900 mm long on a 1150 mm flexible lead, so the vessel must be within that reach; Class A EMC means industrial locations only.

What is not included in the base delivery that I need to plan for?

No pump is fitted, so circulation must come from the bath or an external loop. The country-specific plug must be ordered, and the Pt100 probe is fixed to the unit; no separate sensor, cable or mounting accessory is listed in the datasheet.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
TC50E-F Immersion Circulator Datasheet
Datasheet ·66,6 КБ ·2 pp.