The TC45 is an air-cooled immersion cooler with a stainless-steel condensing probe (48 mm dia. × 105 mm, 1050 mm flexible connection) and a 0.041 kg R-290 charge, covering -45 to 100 °C. It delivers 0.05 kW at -40 °C and 0.24 kW at 0 °C. It serves as a direct-contact cold trap or bath cooler in laboratory and pilot processes.

Peter Huber Kältemaschinenbau Eintauchkuehler Kuehlfallen Series — Model Comparison & Selection

Model Noise level, dBControllerPower supplyRefrigerantSafety classTemperature range, °C
TC45 Current —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
CT50 Single OLÉ 59OLÉ220-240V 1~/2~ 50/60HzR-290 (A3, H220)III / FL-50–50
TC100 55ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC100E-F 55MPC110-120V 1~ 60HzR-1150 (A3, H220)I / NFL-100–40
TC100-F 58ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC45E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E-F 54MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45-F 59ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC50 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E-F 60MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50-F 60ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50

Full specifications

Core Performance & Functional Specifications
Pump speed adjustable no
Pump type no pump
Temperature range -45...100 °C
Dimensions (W x D x H) mfr 190 x 295 x 360 mm
Refrigeration machine mfr air-cooled, natural refrigerant
Dimensions, Weight & Mechanical Design
Weight 16 kg
Electrical, Power & Drive Specifications
Power supply 208-240V 1~/2~ 50/60Hz
Current consumption max. mfr 1, 4 A (max.)
Interfaces, Connections & Control
Controller ON-OFF-controller
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Refrigerant quantity 1st stage mfr 0, 041 kg (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity mfr 0, 05 kW (at -40 °C)
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

The TC45 is a self-contained immersion cooler: a stainless-steel housing with two handles, an air-cooled refrigerating unit, and a flexible stainless-steel condensing probe. Its working range of -45 to 100 °C and ON-OFF controller distinguish it from larger siblings (TC100, TC100E, TC100E-F, CT50 Single OLÉ), which are oriented toward higher capacity or lower noise. The TC45 is the compact, low-charge option for direct probe immersion.

Behavior under load

The cooling capacity is strongly temperature-dependent: 0.24 kW at 0 °C, 0.18 kW at -20 °C, 0.1 kW at -30 °C, and 0.05 kW at -40 °C. Rated data apply at 20 °C room temperature; capacity falls as ambient rises. The refrigeration unit runs continuously rather than cycling, so the ON-OFF controller modulates the process rather than the compressor. The unit has no pump and no adjustable pump speed, so circulation must be provided externally if required.

Installation and operation

Supply is 208–240 V, 1~/2~, 50/60 Hz with a maximum current of 1.4 A; a country-specific plug must be specified at ordering. Voltage tolerance is ±5% only with ±2% frequency tolerance, and the combination -5% voltage with +2% frequency is not allowed. Ambient must stay within 5–40 °C. The R-290 (A3, H220) refrigerant charge is 0.041 kg, keeping F-gas obligations minimal, but ignition sources and ventilation must be controlled. EMC classification is Class A, Group 1 (industrial environment). Space requirements around the air-cooled condenser must be respected.

Integration & Operating Notes

Electrical
Supply tolerance is narrow and asymmetric

The unit accepts 208–240 V at 50/60 Hz, but voltage may deviate only ±5% while frequency deviates ±2%, and the combination of -5% voltage with +2% frequency is explicitly not allowed. Verify site power quality before connection; a supply outside this window can prevent safe operation.

TC45 Technical Datasheet, Specifications
Process Limits
Cooling capacity collapses at the cold end

Capacity falls from 0.24 kW at 0 °C to 0.05 kW at -40 °C, so the heat load must be checked at the coldest setpoint, not at nominal. A load sized for 0 °C will be grossly undersized near -40 °C.

TC45 Technical Datasheet, Performance
Mounting
Probe geometry constrains vessel fit

The probe is 48 mm nominal diameter and 105 mm long, with a 1050 mm flexible connection. Check the vessel opening, immersion depth, and routing of the flexible section before installation; the probe cannot be bent beyond the flexible connection.

TC45 Technical Datasheet, Installation
Cooling & Media
R-290 charge requires ignition-source control

The refrigerant is R-290 (propane, A3 flammable, H220) with a 0.041 kg charge. Although the charge is small, the installation area must be assessed for ignition sources and ventilation per the safety class I / NFL marking.

TC45 Technical Datasheet, Safety
Electrical
Plug must be ordered with the unit

Single/two-phase devices are delivered with a power cable and a country-specific plug that must be specified at ordering. Without the correct plug, commissioning is delayed.

TC45 Technical Datasheet, Installation
Control & I/O
ON-OFF control with continuous refrigeration

The controller is an ON-OFF type, while the refrigeration unit runs continuously. There is no pump and no pump-speed adjustment, so external circulation or agitation is needed if the process requires mixing.

TC45 Technical Datasheet, Operation

Selection & Integration Q&A

When should I choose the TC45 over the larger TC100/TC100E or the CT50 Single OLÉ?

Pick the TC45 when the load is small and the coldest setpoint is near -40 °C, where it delivers 0.05 kW. Choose a TC100-series sibling when higher capacity or lower noise (55 dB(A) vs. the TC45's compact format) is needed; the CT50 Single OLÉ is a different series with 59 dB(A).

What adjacent equipment does the TC45 require, and what is not included?

It has no pump, so external circulation or agitation must be provided if the bath or trap needs mixing. A country-specific plug must be specified at ordering; the power cable is included but the plug type is not universal. No controller interface or drive is supplied.

What maintenance and consumables are needed, and what is excluded from base delivery?

The R-290 charge is only 0.041 kg, so leak checks are simple; no regular refrigerant top-up is specified. The base delivery excludes the country-specific plug unless ordered, and no pump or external circulation accessories are included. Consult the operating conditions for condenser-cleaning intervals.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
TC45 Technical Datasheet
Datasheet ·87,9 КБ ·1 pp.
View PDF