Peter Huber Kältemaschinenbau CT50 Single OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau CT50 Single OLÉ

Peter Huber Kältemaschinenbau CT50 Single OLÉ — Immersion coolers with Noise level 59 dB.

The CT50 Single OLÉ is an air-cooled immersion cooler cold trap with a -50 to 50 °C working range and no circulation pump, using flammable R-290 refrigerant. It is the single-stage OLÉ-controlled variant in the series, distinguished from TC100 siblings by its smaller footprint and controller. It condenses and freezes vapors in vacuum and process lines.

Noise level
59 dB

Peter Huber Kältemaschinenbau Eintauchkuehler Kuehlfallen Series — Model Comparison & Selection

Model Noise level, dBControllerPower supplyRefrigerantSafety classTemperature range, °C
CT50 Single OLÉ Current 59OLÉ220-240V 1~/2~ 50/60HzR-290 (A3, H220)III / FL-50–50
TC100 55ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC100E-F 55MPC110-120V 1~ 60HzR-1150 (A3, H220)I / NFL-100–40
TC100-F 58ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC45 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E-F 54MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45-F 59ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC50 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E-F 60MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50-F 60ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50

Full specifications

Core Performance & Functional Specifications
Noise level 59 dB(A)
Alarm output optic, acoustic
Dimensions (w × D × H) 330 x 450 x 576 mm
Pump type no pump
Temperature range -50...50 °C
Refrigeration machine mfr air-cooled, natural refrigerant
Dimensions, Weight & Mechanical Design
Weight 32 kg
Electrical, Power & Drive Specifications
Current consumption 5 A (max.)
Power supply 220-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller OLÉ
Temperature display OLED Display
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Refrigerant quantity 1st stage mfr 0, 06 kg (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling Rate >= 4 min (+20...-50°C)
+20...-45°C: >= 2, 5 min
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

The CT50 Single OLÉ is a single-stage, air-cooled immersion cooler (cold trap) with an integrated OLÉ controller and OLED display. Unlike the TC100/TC100E/TC100-F siblings, which are larger units with different noise signatures, this model is a compact 330 x 450 x 576 mm, 32 kg package. It has no circulation pump, so it is a direct-contact cold surface rather than a pumped-loop chiller. The refrigerant is R-290 (propane, A3, H220), a flammable natural refrigerant; charge is 0.06 kg in the first stage.

Working range and behavior

The rated operating temperature range is -50 to 50 °C. Cooling-rate data are given as time-to-temperature: at least 4 minutes from +20 to -50 °C and at least 2.5 minutes from +20 to -45 °C. These are the only performance points supplied; no capacity curve is available. Output data are valid at 20 °C room temperature, and capacity may drop as ambient rises. The unit is intended for batch cooling of a trap surface, not continuous pumped duty.

Installation, control and operation

Supply is 220-240 V, 1~/2~, 50/60 Hz, max current 5 A, with a 10-16 A fuse. Voltage tolerance is ±5% and frequency ±2%, but simultaneous opposite-sign deviations are not permitted. The enclosure is IP20, so it must be installed dry indoors. Ambient must stay 5-40 °C. The controller supports autostart after power failure. An optional factory-fitted Pt100 sensor connection can display (not control) process temperature. Single/two-phase units ship with a power cable and country-specific plug that must be specified at ordering. EMC classification is Class A, Group 1, so additional measures may be needed in residential environments.

Integration & Operating Notes

Electrical
Supply must stay within ±5% voltage and ±2% frequency

The datasheet permits ±5% voltage and ±2% frequency tolerance but explicitly forbids simultaneous opposite-sign deviations. Verify the site supply before commissioning; out-of-tolerance supply can prevent the compressor from starting or cause invalid operating conditions.

CT50 Single OLÉ — Technical Data Sheet, Specifications
Electrical
Country-specific plug must be ordered with the unit

Single/two-phase devices are delivered with a power cable and a country-specific plug that must be specified at ordering. Confirm the plug type and cable length against the installation site before release, since retrofitting a plug is site work.

CT50 Single OLÉ — Technical Data Sheet, page 2
Mounting
IP20 enclosure requires dry indoor placement

The IP20 rating means no protection against water or dust ingress. Install in a dry indoor location; do not place where condensate, splashes or washdown occur. Air-cooled operation also requires the space clearances stated in the operating conditions.

CT50 Single OLÉ — Technical Data Sheet, Specifications
Process Limits
Ambient above 20 °C derates cooling performance

Output data are valid at 20 °C room temperature, and the datasheet states cooling capacity may drop as ambient rises. The permitted ambient window is 5-40 °C. Size the trap for the actual room temperature, not the 20 °C reference, if the installation room runs warm.

CT50 Single OLÉ — Technical Data Sheet, Specifications
Safety
Flammable R-290 refrigerant governs site safety measures

The first stage uses R-290 (propane, A3, H220) with a 0.06 kg charge. A3 classification means flammable refrigerant; site ventilation, ignition-source control and service access must follow the refrigerant safety requirements. Do not braze or open the circuit without qualified refrigeration service.

CT50 Single OLÉ — Technical Data Sheet, Specifications
Control & I/O
Autostart restarts cooling after mains interruption

The OLÉ controller supports autostart after power failure, so the cold trap will resume operation when mains returns. If the process must not restart unattended, provide external sequencing or supervision; the alarm output is optic and acoustic only.

CT50 Single OLÉ — Technical Data Sheet, Overview
Control & I/O
Pt100 option displays process temperature only

An optional Pt100 sensor connection can display (not control) process temperature and is only available factory-fitted at additional charge. If process-temperature monitoring is required, it must be included in the original order; it cannot be added in the field.

CT50 Single OLÉ — Technical Data Sheet, Overview
Compliance
Class A EMC may need measures in residential areas

The unit is EMC Class A, Group 1 to EN55011, intended for industrial environments. In residential or light-industrial locations, additional filtering or separation from sensitive equipment may be required to avoid disturbance.

CT50 Single OLÉ — Technical Data Sheet, page 2

Selection & Integration Q&A

When should I choose the CT50 Single OLÉ instead of a TC100-series sibling?

Choose the CT50 when a compact single-stage cold trap with OLÉ controller and -50 to 50 °C range fits the space and duty. The TC100 siblings are larger units with different noise signatures; select them when higher capacity or a different controller is required. The CT50 has no pump, so it suits direct-contact trapping, not pumped loops.

What supply and protective device does the CT50 Single OLÉ require at the installation site?

220-240 V, 1~/2~, 50/60 Hz, max current 5 A, with a 10-16 A fuse. Voltage tolerance ±5% and frequency ±2%, but not simultaneous opposite-sign deviations. Specify the country-specific plug at ordering; the unit ships with a power cable.

Where can the CT50 Single OLÉ be installed and what ambient conditions apply?

Indoors, dry, IP20 enclosure, ambient 5-40 °C. Output data are valid at 20 °C room temperature and capacity may drop as ambient rises. Respect the space clearances for air-cooled operation and service access. R-290 flammable refrigerant requires appropriate site safety measures.

What is included in base delivery and what must be ordered separately?

Base delivery includes the unit with power cable and country-specific plug (specify at ordering). The Pt100 sensor connection for displaying process temperature is an optional factory-fitted extra at additional charge and cannot be added later. No pump is fitted; no other accessories are listed in the datasheet.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
CT50 Single OLÉ — Technical Data Sheet
Datasheet ·200,3 КБ ·2 pp.
View PDF