Peter Huber Kältemaschinenbau TC50
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau TC50

Peter Huber Kältemaschinenbau TC50 — Immersion coolers.

The TC50 is an air-cooled immersion cooler with a flexible 1150 mm connection between the refrigerating unit and a 48 mm × 155 mm probe, rated for -50 to 50 °C. It is the smallest model in the series, distinguished by its 0.3 kW cooling capacity at 0 °C and R-290 refrigerant. It is used for direct cooling of process fluids in vessels or baths.

Peter Huber Kältemaschinenbau Eintauchkuehler Kuehlfallen Series — Model Comparison & Selection

Model Noise level, dBControllerPower supplyRefrigerantSafety classTemperature range, °C
TC50 Current —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
CT50 Single OLÉ 59OLÉ220-240V 1~/2~ 50/60HzR-290 (A3, H220)III / FL-50–50
TC100 55ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC100E-F 55MPC110-120V 1~ 60HzR-1150 (A3, H220)I / NFL-100–40
TC100-F 58ON-OFF-Regler220-240V 1~/2~ 50/60HzR-1150 (A3, H220)I / NFL-100–40
TC45 —ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45E-F 54MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC45-F 59ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-45–100
TC50E —MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50E-F 60MPC208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50
TC50-F 60ON-OFF-Regler208-240V 1~/2~ 50/60HzR-290 (A3, H220)I / NFL-50–50

Full specifications

Core Performance & Functional Specifications
Pump speed adjustable no
Pump type no pump
Temperature range -50...50 °C
Dimensions (W x D x H) mfr 260 x 330 x 415 mm
Refrigeration machine mfr air-cooled, natural refrigerant
-20 mfr 0, 26 kW (at -20 °C)
-30 mfr 0, 2 kW (at -30 °C)
Dimensions, Weight & Mechanical Design
Weight 26 kg
Electrical, Power & Drive Specifications
Current consumption 3 A (max.)
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller ON-OFF-controller
Materials, Media & Process Compatibility
Refrigerant R-290 (A3, H220) (1st stage)
Refrigerant quantity 1st stage mfr 0, 06 kg (1st stage)
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity mfr 0, 3 kW (at 0 °C)
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and positioning

Performance and media behavior

Installation, control and operation

Integration & Operating Notes

Mounting
Probe opening and immersion depth must match 48 mm × 155 mm

The vessel or bath opening must accept a 48 mm nominal diameter probe, and the immersion depth must be at least 155 mm to use the full probe length. Check these dimensions before mounting to avoid mechanical interference or insufficient cooling.

Datasheet TC50 Eintauchkühler, page 1
Mounting
Flexible line limits distance between unit and probe to 1150 mm

The refrigerating unit must be positioned within 1150 mm of the probe connection point. Routing must avoid stretching or kinking the flexible line, which could damage the refrigerant circuit.

Datasheet TC50 Eintauchkühler, page 1
Electrical
Supply voltage and frequency tolerances are interdependent

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%; the combination of -5% voltage and +2% frequency is not allowed. Verify the site supply before commissioning to avoid invalid operating conditions.

Datasheet TC50 Eintauchkühler, page 1
Electrical
Country-specific plug must be specified at ordering

Single/two-phase devices are delivered with a power cable and country-specific plug. The plug type must be stated when ordering; otherwise the unit may arrive without a suitable connector for the installation site.

Datasheet TC50 Eintauchkühler, page 1
Process Limits
Ambient temperature must stay within 5–40 °C

Operation outside this range may degrade cooling performance or damage the unit. The installation location must be controlled within this range, and cooling capacity may drop as ambient temperature rises above 20 °C.

Datasheet TC50 Eintauchkühler, page 1
Safety
A3 refrigerant requires ignition-source control and ventilation

R-290 is a flammable refrigerant (A3, H220). Installation must account for A3 safety requirements, including room ventilation and avoidance of ignition sources, even though the charge is only 0.06 kg.

Datasheet TC50 Eintauchkühler, page 1
Compliance
Class A EMC may require additional measures near sensitive loads

The equipment is EMC Class A, Group 1 to EN55011, intended for industrial environments. It may cause interference in residential areas, so additional EMC measures may be needed if installed near sensitive or residential loads.

Datasheet TC50 Eintauchkühler, page 1

Selection & Integration Q&A

When should I choose the TC50 instead of a larger sibling like the TC100?

Choose the TC50 when the required cooling capacity at your process temperature is at or below 0.3 kW at 0 °C (0.26 kW at -20 °C, 0.2 kW at -30 °C) and the 48 mm × 155 mm probe fits your vessel. The TC100 series offers higher capacity but is physically larger; select it only if the TC50's capacity is insufficient.

What ambient conditions and duty-cycle limits apply to the TC50?

The ambient temperature must remain between 5 °C and 40 °C. Cooling capacity is rated at 20 °C room temperature and may drop as ambient temperature rises. The unit is air-cooled, so space requirements for ventilation must be respected; insufficient clearances can impair condenser performance.

What maintenance or accessories are required that are not included in the base delivery?

The base delivery includes the refrigerating unit, probe, and power cable with country-specific plug (if specified). No pump is included. Maintenance requirements are not detailed in the available datasheet; consult the operating manual for service intervals. A suitable fuse (10–16 A) and electrical protection must be provided by the installer.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
TC50 Eintauchkühler
Datasheet ·80,5 КБ ·1 pp.
View PDF