Peter Huber Kältemaschinenbau Chili Dynamisches
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Chili Dynamisches

Peter Huber Kältemaschinenbau Chili Dynamisches — Temperature control units.

The Chili Dynamisches is a closed-loop heating circulator (pressure pump, variable speed) rated 65–300 °C with 0.02 K stability, positioned in the Unistate Bis 425C series as the compact 2.7–3 kW modification. Its M24x1.5 male pump connection and 45 l/min / 0.9 bar delivery suit pressure-sensitive glass reactors and jacketed vessels requiring controlled flow.

Peter Huber Kältemaschinenbau Unistate Bis 425C Series — Model Comparison & Selection

Model Display resolutionPower supplyPump connectionPump typeTemperature range, °CExpansion volume, m³
Chili Dynamisches Current 0.01200-240V 1~/2~ 50/60HzM24x1,5 AG malePressure pump, variable 65–3000.002
Unistat T305 Dynamisches 0, 01200-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable 65–300—
Unistat T305 HT Dynamisches 0, 01200-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable 65–300—
Unistat T305w HT Dynamisches 0, 01200-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable 65–300—
Unistat T320 Dynamisches 0, 01460V 3~ 60HzM30x1, 5 AG malemagnetically coupled, st65–3000.024
Unistat T320w HT Dynamisches 0, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st65–3000.024
Unistat T330 HT Dynamisches 0, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st65–3000.024
Unistat T330w HT Dynamisches 0, 01 K400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st65–3000.024
Unistat T340 Dynamisches 0, 01460V 3~ 60HzM38x1, 5 AG malemagnetically coupled, st65–3000.056
Unistat T340 HT Dynamisches 0, 01400V 3~ 50HzM38x1, 5 AG malemagnetically coupled, st65–3000.056
Unistat T345 Dynamisches 0, 01400V 3~ 50HzM38x1, 5 AG malemagnetically coupled, st65–3000.056
Unistat T345 HT Dynamisches 0, 01400V 3~ 50HzM38x1, 5 AG malemagnetically coupled, st65–3000.056
Unistat T350 HT Dynamisches 0, 01400V 3~ 50HzM38x1, 5 AG malemagnetically coupled, st65–3000.056
Unistat T402 Dynamisches 0, 01400V 3~N 50/60HzM24x1, 5 AG malePressure pump, variable 80–425—
Unistat TR401 Dynamisches 0, 01200-240V 1~/2~ 50/60HzM24x1, 5 (Flow) M24x1, 5Pressure pump, variable 50–4000.005
Unistat TR402 Dynamisches 0, 01200-240V 1~/2~ 50/60HzM24x1, 5 (Flow) M24x1, 5Pressure pump, variable 80–425—

Full specifications

Core Performance & Functional Specifications
Expansion volume 2 l
Filling volume 1.45 l
Heating capacity 2.7 - 3 kW
Pump connection M24x1,5 AG male
Pump speed adjustable Yes
Pump type Pressure pump, variable speed
External sensor connection Pt100
Temperature range 65...300 °C
Temperature stability 0.02 K
Alarm message mfr optic, acoustic, relay
Dimensions (W x D x H) mfr 240 x 427 x 393 mm
Delivery capacity pressure pump max. mfr 45 l/min; 0,9 bar
Dimensions, Weight & Mechanical Design
Weight 23 kg
Electrical, Power & Drive Specifications
Current consumption 15.5 A
Fuse rating 16 A
Power supply 200-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Display resolution 0.01 K
Digital interface Ethernet, USB (Host u. Device), RS232
Materials, Media & Process Compatibility
Maximum viscosity 50 mm²/s
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Working behavior

Control, installation and operation

Integration & Operating Notes

Mounting
Do not install in an ATEX zone

The manual explicitly prohibits installation or startup within an ATEX zone due to explosion risk; site classification must be confirmed before the unit is placed, regardless of the process fluid used.

Chili Operation Manual, page 13
Mounting
Provide a drip tray and lock casters

The responsible body must install a condensation water / thermal fluid drip tray below the unit, and any casters must be locked after installation to prevent crushing of limbs during operation and service.

Chili Operation Manual, pages 15 and 25
Electrical
External UL 489 branch protection is mandatory

The unit does not include branch circuit protection; an external breaker or fuse according to UL 489 must be provided. Supply must be 200–240 V 1~/2~ 50/60 Hz with 16 A fuse, and voltage/frequency tolerance is ±5% / ±2% with some combinations not allowed.

Chili Immersion Circulators Datasheet, page 2
Electrical
Specify country-specific plug at order

Single- and two-phase devices are delivered with a power cable and country-specific plug that must be stated when ordering; hard-wired connection must be performed by an electrician and the power cable must not exceed 3 m.

Chili Immersion Circulators Datasheet, page 2; Chili Operation Manual, page 28
Process Limits
Respect 0.9 bar max delivery pressure on glassware

For pressure-sensitive applications such as glass reactors, the maximum flow pressure of 0.9 bar must be taken into account; the variable-speed pump allows flow to be reduced, but the pressure limit remains the governing constraint for the connected circuit.

Chili Operation Manual, page 31; Chili Immersion Circulators Datasheet, page 1
Process Limits
Keep hose bore at least equal to pump connection

Temperature control hoses should be as short as possible and their inside diameter must at least match the M24x1.5 pump connections; undersized or long hoses increase pressure drop and degrade achievable temperature control performance.

Chili Operation Manual, page 31
Operation
Cool fluid to room temperature before switching off

To prevent overpressure in the system, the thermal fluid must always be adjusted to room temperature before switching off; after pressing Stop the pump continues to run for about 30 seconds, so service or draining must wait for that overrun.

Chili Operation Manual, pages 31 and 37
Environment
Allow 2 h acclimation after cold-to-warm move

When changing from a cold to a warm environment (or vice versa), the unit must acclimate for about 2 hours before switching on; ambient temperature during operation must remain between 5 °C and 40 °C.

Chili Operation Manual, page 25; Chili Immersion Circulators Datasheet, page 1

Selection & Integration Q&A

When should I choose the Chili Dynamisches instead of the Unistat T305 or T320 siblings?

Pick this model for closed-loop heating up to 300 °C with 2.7–3 kW and a compact 240 mm width. The T305/T305 HT/T305w HT/T320 are separate modifications; their ratings must be checked individually and are not interchangeable with this unit's 65–300 °C range.

What must the adjacent circuit and power supply provide for this unit?

Mating hoses need M24x1.5 female fittings with bore shape Y (60°) per DIN 3863, ball socket DIN 3863 and sleeve nut DIN 3870, with inside diameter at least matching the pump connection. Supply: 200–240 V 1~/2~ 50/60 Hz, 16 A fuse, external UL 489 branch protection, max 3 m power cable.

What site and duty-cycle limits apply from the manual?

No ATEX zone; ambient 5–40 °C; drip tray below the unit; casters locked; 2 h acclimation after cold/warm moves; thermal fluid viscosity max 50 mm²/s; fluid cooled to room temperature before switch-off; pump overruns about 30 s after Stop.

What is not included in base delivery and what maintenance/accessories are needed?

External branch circuit protection per UL 489 and the drip tray are site-provided; the country-specific plug must be specified at order. Temperature control hoses and fittings are not part of the unit. Service follows the manual's Service and Maintenance section; no consumables are listed in the verified facts.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Chili® Operation Manual
Manual ·3,0 МБ ·82 pp.
View PDF
PDF
Chili Immersion Circulators
Datasheet ·117,5 КБ ·2 pp.
View PDF