Peter Huber Kältemaschinenbau Grande Fleur w-eo Dynamisches
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Grande Fleur w-eo Dynamisches

Peter Huber Kältemaschinenbau Grande Fleur w-eo Dynamisches — Temperature control units.

The Grande Fleur w-eo Dynamisches is a water-cooled temperature control unit for external open loops only, with no expansion tank of its own. It covers -40 to 200 °C with 1.5 kW heating and 0.6 kW cooling at 20–200 °C, falling to 0.04 kW at -40 °C. The variable-speed pressure pump delivers up to 47 l/min at 0.9 bar.

Peter Huber Kältemaschinenbau Unistate Bis 45C Series — Model Comparison & Selection

Model Noise level, dBDisplay resolutionPower supplyPump connectionPump typeTemperature range, °C
Grande Fleur w-eo Dynamisches Current ——————
Grande Fleur Dynamisches ——————
Grande Fleur w Dynamisches —0, 01208-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable -40–200
Petite Fleur-eo Dynamisches 580, 01 K220-240V 1~/2~ 50/60HzM16x1 AG malePressure pump, variable -40–200
Petite Fleur w Dynamisches —0, 01220-240V 1~/2~ 50/60HzM16x1 AG malePressure pump, variable -40–200
Unistat 410w Dynamisches 610, 01 K220-240V 1~/2~ 50/60HzM24x1, 5 AG malePressure pump, variable -45–250
Unistat 425w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat 430w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P405w Dynamisches —0, 01460V 3~ 60HzM30x1, 5 AG malemagnetically coupled, st-45–250
Unistat P425 Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P425w Dynamisches 610, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P430 Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250
Unistat P430w Dynamisches 650, 01400V 3~ 50HzM30x1, 5 AG malemagnetically coupled, st-40–250

Full specifications

Description

Construction and series positioning

Thermal behavior

Control, connection and operation

Integration & Operating Notes

Cooling & Media
Cooling water must be 5–20 °C at 2–6 bar differential

Supply cooling water within 5–20 °C and 2–6 bar differential pressure; lower pressure or warmer water reduces the published cooling capacity, which is rated at 20 °C room temperature and 2 bar differential. Insulate pipes where water can fall below dew point.

Grande Fleur w-eo Technical Data, page 2
Cooling & Media
Cooling-water circuit contains copper, 1.4401, EPDM and PTFE

The cooling-water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only cooling water compatible with these materials may be connected; aggressive or untreated water can corrode the circuit.

Grande Fleur w-eo Technical Data, page 2
Electrical
Voltage and frequency tolerances must be met simultaneously

Supply is 110–120 V 1~ 60 Hz with ±5% voltage and ±2% frequency tolerance; combinations such as -5% voltage with +2% frequency are not permitted, so verify the site supply before commissioning.

Grande Fleur w-eo Technical Data, page 2
Electrical
Country-specific plug must be specified at ordering

Single-phase devices are delivered with a power cable and a country-specific plug that must be stated on the order; confirm the plug type against the site outlet to avoid a rework at installation.

Grande Fleur w-eo Technical Data, page 2
Mounting
Install in a dry, protected location at 5–40 °C ambient

The IP20 enclosure requires a dry indoor location with ambient temperature between 5 and 40 °C; the unit is EMC Class A, Group 1 to EN55011, so additional EMC precautions may be needed in residential or sensitive environments.

Grande Fleur w-eo Technical Data, page 2
Process Limits
Thermal fluid viscosity must stay below 50 mm²/s

The maximum permissible kinematic viscosity of the heat-transfer fluid is 50 mm²/s; select a fluid that remains below this limit across the full -40...200 °C operating range, otherwise pump delivery and temperature control degrade.

Grande Fleur w-eo Technical Data, page 1
Process Limits
Set overtemperature cut-out to the fluid and application

Adjustable overtemperature protection per DIN 12876 with safety class III/FL must be set for the specific thermal fluid and process; the alarm reports optically, acoustically and via relay, so wire the relay into the plant interlock.

Grande Fleur w-eo Technical Data, page 1
Maintenance
Use DIN 3863/3870 mating fittings on M24x1.5 pump ports

Pump connections are M24x1.5 male with bore shape Y (60°) per DIN 3863; procure hoses with ball socket per DIN 3863 and sleeve nut per DIN 3870 so the circuit seals correctly and can be serviced without adapters.

Grande Fleur w-eo Technical Data, page 2

Selection & Integration Q&A

When should I choose the Grande Fleur w-eo Dynamisches instead of the Grande Fleur Dynamisches or Grande Fleur-eo Dynamisches?

Pick the w-eo when the loop is external and open and site cooling water at 5–20 °C, 2–6 bar is available; it has no expansion tank, so the application must absorb volume change. The Grande Fleur Dynamisches is rated 61 dB(A) and the -eo variant shares the 47 l/min pump flow.

What must the external circuit and cooling-water supply provide for this unit?

An open external loop of at least 1.5 l filling capacity that handles thermal expansion, plus cooling water at 5–20 °C and 2–6 bar differential through G1/2 male ports. The cooling-water circuit contains copper, 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water may be used.

What site conditions and supply tolerances apply to installation?

Install indoors at 5–40 °C ambient in an IP20-protected dry location. Supply is 110–120 V 1~ 60 Hz with ±5% voltage and ±2% frequency tolerance applied simultaneously; combinations such as -5% voltage with +2% frequency are not allowed. EMC is Class A, Group 1 to EN55011.

What fittings and accessories are needed beyond the base delivery?

The base unit ships with a power cable and country-specific plug only if specified at ordering. Pump ports are M24x1.5 male and require hoses with ball socket per DIN 3863 and sleeve nut per DIN 3870; the external open loop and its expansion volume are not part of delivery.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Grande Fleur w-eo
Datasheet ·112,3 КБ ·2 pp.
View PDF