Peter Huber Kältemaschinenbau Unistat 825w Dynamisches
Peter Huber Kältemaschinenbau Unistat 825w Dynamisches — Temperature control units.
The Unistat 825w Dynamisches is a water-cooled, free-standing temperature control unit with a variable-speed pressure pump and Pilot ONE controller, covering -85 to 250 °C. Within the Unistat 8xx series it is distinguished by its water cooling and dynamic performance, requiring a 400 V 3-phase supply and cooling water at 1–6 bar. It serves precise temperature control of externally closed or open applications in industrial processes.
Peter Huber Kältemaschinenbau Unistat Series — Model Comparison & Selection
| Model | Noise level, dB | Ambient temperature limit, °C | Display resolution | Power supply | Pump connection | Pump type |
|---|---|---|---|---|---|---|
| Unistat 825w Dynamisches Current | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | Pressure pump, variable |
| Unistat 1005w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | Pressure pump, variable |
| Unistat 1015w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat 705w Dynamisches | — | 5–40 | 0, 01 | 230V 1~ 50Hz | M24x1, 5 AG male | Pressure pump, variable |
| Unistat 815w Dynamisches | 60 | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | Pressure pump, variable |
| Unistat 905w Dynamisches | — | 5–40 | 0, 01 K | 208V 3~ 60Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat 912w Dynamisches | 65 | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat 915w Dynamisches | 64 | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat 920w Dynamisches | 71 | 5–40 | 0, 01 | 400V 3~ 50Hz | M38x1, 5 AG male | magnetically coupled, st |
| Unistat 930w Dynamisches | — | 5–40 | 0, 01 | 460V 3~ 60Hz | M38x1, 5 AG male | magnetically coupled, st |
| Unistat 950w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | flange DN40 PN10/40 EN10 | magnetically coupled, st |
| Unistat P815 Dynamisches | 64 | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P815w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P825 Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P825w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P905 Dynamisches | — | 5–35 | 0, 01 | 460V 3~ 60Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P905w Dynamisches | — | 5–40 | 0, 01 | 460V 3~ 60Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P912w Dynamisches | 65 | 5–40 | 0, 01 | 460V 3~ 60Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P915w Dynamisches | 64 | 5–40 | 0, 01 | 400V 3~ 50Hz | M30x1, 5 AG male | magnetically coupled, st |
| Unistat P920w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M38x1, 5 AG male | magnetically coupled, st |
| Unistat P925w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M38x1, 5 AG male | magnetically coupled, st |
| Unistat P930w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | M38x1, 5 AG male | magnetically coupled, st |
| Unistat P950w Dynamisches | — | 5–40 | 0, 01 | 400V 3~ 50Hz | flange DN40 PN10/40 EN10 | magnetically coupled, st |
Full specifications
| Control output | POKO ONE |
| Filling volume | 3 l |
| Heating capacity | 3 kW |
| Pump connection | M30x1, 5 AG male |
| Pump speed adjustable | Yes |
| Pump type | Pressure pump, variable speed |
| External sensor connection | Pt100 |
| Temperature range | -85...250 °C |
| Weight | 223 kg |
| Current consumption | 15 A (max.) |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Maximum viscosity | 50 mm²/s |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 231 l/h (at 15°C, flow 0°C) |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The Unistat 825w Dynamisches is a water-cooled ('w' suffix) free-standing unit in the Unistat 8xx series, which also includes the 815w, 705w, 1005w and 1015w. Unlike the 705w, it uses a plate heat exchanger for cooling water separation.
- It is equipped with a variable-speed pressure pump (max. 40 l/min, 0.9 bar) and a Pilot ONE controller with POKO ONE control output. The pump connection is M30x1.5 male; cooling water connections are G1/2 male.
- The unit is rated IP20 and safety class III/FL per DIN 12876, and is classified as pressure equipment category I.
Thermal performance and media
- The working range is -85 to 250 °C with 3 kW heating capacity. Cooling power falls sharply at low temperatures: from 2.4 kW at -40 °C to 0.2 kW at -85 °C, so deep-cooling duty must be sized accordingly.
- The pump tolerates a maximum kinematic viscosity of 50 mm²/s, which constrains heat transfer fluid selection at low temperatures. Minimum filling volume is 3 l; the expansion tank holds 3.6 l.
- For externally closed applications the expansion vessel must remain unlocked; for externally open (bath) applications it must be locked to prevent fluid loss.
Installation and operation
- The unit requires a 400 V 3-phase 50 Hz supply with max. 15 A current and a 3x16 A fuse. Three-phase devices under 63 A are delivered with cable but without a plug, so a plug must be fitted on site by an electrician.
- Cooling water must be supplied at 5–20 °C inlet temperature, with a differential pressure of at least 1 bar and a maximum pressure of 6 bar. Consumption is 231 l/h at 15 °C cooling water and 0 °C flow.
- Ambient temperature must be 5–40 °C. The unit is EMC Class A, Group 1 (EN55011) for industrial environments. It must not be installed in an ATEX zone.
- The Pilot ONE controller offers Ethernet, USB (host and device) and RS232 interfaces. Power failure behavior can be set to Off/Standby or automatic restart.
Safety and compliance
- The refrigerant R-452A (GWP 2141, 0.95 kg, 2.0 t CO2e) and second-stage R-23 (GWP 14800, 0.39 kg, 5.8 t CO2e) require F-gas compliance and servicing by approved refrigeration contractors.
- The unit is not permissible for medical devices or direct foodstuff temperature control.
Integration & Operating Notes
The unit draws up to 15 A per phase and requires a 400 V 3~ 50 Hz supply protected by a 3x16 A fuse. Voltage and frequency tolerances are ±5% and ±2% but must not combine unfavorably (e.g., -5% voltage with +2% frequency is not allowed). A plug is not included and must be fitted by an electrician.
The cooling water circuit requires a minimum differential pressure of 1 bar and must not exceed 6 bar. Inlet temperature must be between 5 °C and 20 °C; if pipes can drop below dew point they must be insulated. Consumption is 231 l/h at 15 °C water and 0 °C flow. Shut off cooling water even for short downtimes.
The unit must not be installed or started within an ATEX zone; explosion protection requires an Ex px cabinet. It must be transported and stored upright only, and leveling feet or casters with parking brakes must be secured before commissioning. Allow about 2 hours acclimation when moving between cold and warm environments before power-on.
For externally closed applications the expansion vessel must remain unlocked; locking it will damage the application due to overpressure. For externally open (bath) applications the expansion vessel must be locked to prevent fluid loss. The heat transfer fluid must have a fire point of ≥65 °C if ethanol is used, and only supervised operation is permitted.
In Process Safety mode, when the overtemperature trigger value is reached, the controller releases maximum cooling capacity instead of switching off all poles. This mode requires the compressor to be set to Permanently ON. Power failure behavior can be configured to Off/Standby or automatic restart; choose according to whether unattended restart is acceptable.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Hoses and connections must be periodically checked for leaks and quality and replaced as needed. The hat-type strainer/dirt trap requires cleaning with draining of the cooling circuit. A drip tray must be installed below the unit.
Selection & Integration Q&A
Choose the 825w for its water cooling and higher cooling capacity at low temperatures; the 815w is air-cooled and the 705w lacks a plate heat exchanger. The 825w is suited for deep cooling to -85 °C with water cooling available, while the 705w may suffice for less demanding applications.
Cooling water must be 5–20 °C, with 1–6 bar differential pressure and G1/2 male connections; consumption is 231 l/h at 15 °C water and 0 °C flow. Electrical supply is 400 V 3~ 50 Hz, max. 15 A, fused at 3x16 A; a plug is not included and must be fitted by an electrician.
Ambient temperature must be 5–40 °C; the unit is IP20 and must not be installed in an ATEX zone. It must be transported and stored upright, and leveling feet or casters with brakes must be secured. Allow 2 hours acclimation after temperature changes before power-on.
Refrigerant circuit work must be by approved contractors; periodically check hoses and clean the strainer. A drip tray must be installed. A power plug is not included; heat transfer fluid and cooling water hoses are not included and must be selected per viscosity and temperature limits.