No photo available yet
Peter Huber Kältemaschinenbau Unistat P540w Dynamisches
Peter Huber Kältemaschinenbau Unistat P540w Dynamisches — Temperature control units.
The Unistat P540w Dynamisches is a water-cooled, free-standing temperature control unit with a magnetically coupled stainless-steel pump and Pilot ONE controller, covering -55 to 250 °C. It is the high-capacity 'P' variant for applications with high pressure drop, delivering up to 201 l/min and 5.3 bar. It serves precise temperature control of externally closed or open circuits in industrial processes.
Peter Huber Kältemaschinenbau Unistat Series — Model Comparison & Selection
| Model | Noise level, dB | Display resolution | Heating capacity, W | Pump connection | Pump type | Temperature range, °C |
|---|---|---|---|---|---|---|
| Unistat P540w Dynamisches Current | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 527w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 530w Dynamisches | 59 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 540w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | Pressure pump, variable | -60–200 |
| Unistat 620w Dynamisches | 68 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 635w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 640w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 645w Dynamisches | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 650w Dynamisches | 73 | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 680w Dynamisches | — | 0, 01 | 96000 | DN50 PN16 (DIN EN 1092-1 | magnetically coupled, st | -60–200 |
| Unistat GL 530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat P510 Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P520 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P527w Dynamisches | 57 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P530w Dynamisches | 62 | 0.01 | 12000 | M38x1,5 AG male | magnetically coupled, st | -55–250 |
| Unistat P545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P610 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615 Dynamisches | — | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P620w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P635w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P645w Dynamisches | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat P650w Dynamisches | — | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
Full specifications
| Control output | POKO ONE |
| Heating capacity | 24 kW |
| Pump connection | M38x1, 5 AG male |
| Pump speed adjustable | Yes |
| Pump type | magnetically coupled, stainless steel |
| External sensor connection | Pt100 |
| Temperature range | -55...250 °C |
| Weight | 473 kg |
| Current consumption | 56 A (max.) |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Maximum viscosity | 100 mm²/s |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water consumption | 1480 l/h (at 15°C, flow 0°C) |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
The Unistat P540w Dynamisches is a free-standing, water-cooled unit (suffix 'w') with a 'P' designation for applications with high pressure drop. It uses a magnetically coupled stainless-steel pump with adjustable speed, a Pilot ONE controller, and POKO ONE control output. The cooling water circuit is built from copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. With a net weight of 473 kg and dimensions 730x804x1738 mm, it requires planned floor space and handling equipment. Unlike air-cooled siblings, it relies on a cooling water supply of 5–20 °C at 1–4 bar differential pressure (max 6 bar).
Performance and behavior
- Temperature range: -55 to 250 °C; heating capacity 24 kW.
- Cooling power with ethanol: 30 kW at 0 °C, falling to 1.5 kW at -50 °C, so low-temperature capacity is limited.
- Pump: max delivery 201 l/min, max delivery pressure 5.3 bar; delivery drops to 42 l/min at 5.0 bar, so the external circuit pressure drop must be matched to the pump curve.
- Maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.
- Refrigerant R-452A, charge 3.6 kg, GWP 2141, CO2 equivalent 7.7 t.
Installation, connection and control
- Electrical: 400 V 3~ 50 Hz, max current 56 A, fuses 3x63 A. Three-phase devices under 63 A are delivered with cable but without plug. Leakage current >3.5 mA requires attention to protective earthing and RCD selection. Voltage tolerance ±5% with simultaneous frequency tolerance ±2%.
- Cooling water: G3/4 male connection; consumption 1480 l/h at 15 °C, flow 0 °C. Insulate cooling water pipes if water temperature falls below the condensation point.
- Pump connection: M38x1.5 male; use ball socket per DIN 3863 and sleeve nut per DIN 3870.
- Controller: Pilot ONE with Ethernet, USB (Host and Device), RS232; external Pt100 sensor connection; display resolution 0.01 K.
- Safety class III/FL; ambient temperature 5–40 °C; protection rating IP20.
- The unit must not be installed in an ATEX zone. Transport upright only; allow 2 hours acclimation after temperature changes. For externally closed applications, the expansion vessel must remain unlocked; for externally open applications, it must be locked.
Integration & Operating Notes
The unit draws up to 56 A per phase and requires 3x63 A fuses. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%. Leakage current exceeds 3.5 mA, so protective earthing and RCD selection must be engineered accordingly. A plug is not included; the installer must provide a suitable connection.
The cooling water circuit requires a differential pressure between 1 and 4 bar and a maximum pressure of 6 bar. Consumption is 1480 l/h at 15 °C. Higher water temperatures reduce cooling power. If water temperature falls below the condensation point, insulate the cooling water pipes in the unit. Shut off cooling water during downtimes, even overnight.
The magnetically coupled pump can be overloaded by viscous fluids. The maximum permissible kinematic viscosity is 100 mm²/s. For FL-rated fluids, the fire point must be ≥65 °C; ethanol requires supervised operation. Low-temperature cooling capacity is limited: 1.5 kW at -50 °C with ethanol.
Horizontal transport damages the compressor. Only move an emptied unit. Casters are not for transport and carry only 25% of total mass. Leveling feet must be activated and parking brakes engaged before commissioning. After moving between cold and warm environments, allow about 2 hours acclimation before switching on to prevent condensation-induced electrical faults.
In Process Safety mode, when the overtemperature trigger value is reached, the controller releases maximum cooling capacity instead of switching off all poles. This mode requires the compressor to be set to Permanently ON. Power Failure Auto can resume temperature control automatically after a power outage if it was active; choose this behavior according to whether unattended restart is acceptable.
Hoses and connections must be checked periodically for leaks and quality and replaced as required. The mechanical seal should be inspected. The hat-type strainer/dirt trap requires cleaning, including draining the cooling circuit. Refrigerant-circuit work must be carried out by approved refrigeration/air-conditioning contractors.
Selection & Integration Q&A
Choose the P540w when the external circuit has high pressure drop and requires up to 201 l/min at 5.3 bar, and when water cooling is available. Smaller siblings like the 510w or 520w offer lower capacity; select them for lower heat loads or where cooling water is limited.
Cooling water: 5–20 °C, differential pressure 1–4 bar, max 6 bar, connection G3/4 male. Pump connection is M38x1.5 male; use ball socket per DIN 3863 and sleeve nut per DIN 3870. Insulate pipes if water temperature is below the condensation point.
Periodically check hoses and connections for leaks and replace as needed; clean the strainer; inspect mechanical seal. A plug is not included (cable only). A drip tray must be installed by the operator. Refrigerant-circuit work requires approved contractors.