Peter Huber Kältemaschinenbau Unichiller 055T
Peter Huber Kältemaschinenbau Unichiller 055T — Recirculating chillers.
The Unichiller 055T is a recirculating chiller for externally closed circuits, rated -20 to 40 °C with R-290 refrigerant and a 400 V three-phase supply. Its cooling capacity falls from 5.5 kW at 15 °C to 0.2 kW at -20 °C, so it suits moderate-temperature process cooling rather than deep-freeze duty. The Pilot ONE controller and G1 1/4 male pump connection integrate it into industrial cooling loops.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 055T Current | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Minimum fill volume | 5 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | C3 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 281 kg |
| Current consumption | 7 A |
| Fuse rating | 16 A |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The 055T is the largest model in the Unichiller series listed here; siblings 030T, 030Tw, 030Tw-H and 040T are smaller-capacity units. The 055T is distinguished by its higher cooling capacity (5.5 kW at 15 °C) and 281 kg weight.
- It is a free-standing, air-cooled chiller with a G1 1/4 male pump connection and a non-adjustable C3 pump. The refrigerant is R-290 (A3, H220), a flammable natural refrigerant, which imposes ventilation and ignition-source controls.
- The unit is IP20 and intended for indoor installation only, at 5–40 °C ambient and up to 2000 m altitude.
Behavior under load and media
- Cooling capacity is strongly temperature-dependent: 5.5 kW at 15 °C, 2.3 kW at 0 °C, 0.8 kW at -10 °C and 0.2 kW at -20 °C. Sizing must use the actual operating temperature, not the nominal maximum.
- Capacity is specified at 20 °C room temperature; higher ambient reduces available cooling.
- The hydraulic circuit must be externally closed; minimum fill volume is 5 l and expansion volume is 7.5 l.
- The unit is classified to DIN 12876 with safety class I / NFL, and the rating depends on whether the thermal fluid is combustible.
Installation, control and operation
- Electrical supply is 400 V 3~ 50 Hz, max current 7 A, 16 A fuse. Three-phase devices below 63 A are delivered with a cable but without a plug; a suitable plug must be provided on site.
- Voltage and frequency tolerances are ±5 % and ±2 %, but not simultaneously in opposite directions.
- The Pilot ONE controller provides Ethernet, USB (host and device) and RS232 interfaces, and a Pt100 external sensor connection.
- Power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, rather than switching off all poles.
- Leveling feet must be activated and parking brakes applied before start-up. Wall clearance of 50–200 cm per side is required for maintenance. Cooling water supply (if water-cooled) must be shut off even for short downtimes.
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance and ensure adequate airflow. Insufficient clearance can lead to overheating and restricted service access.
The unit is delivered with a cable but without a plug because three-phase devices below 63 A are supplied that way. The installer must fit a plug rated for 400 V 3~ 50 Hz and 16 A, and ensure the supply can deliver 7 A per phase.
The chiller is designed for externally closed applications. The minimum filling capacity is 5 l and the expansion volume is 7.5 l; operating with less fluid or in an open circuit can cause pump cavitation and inadequate cooling.
The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. The refrigerant R-290 (A3, H220) requires that the refrigerant charge and room size be checked to avoid exceeding the limit per m³ of ambient air, and ignition sources must be avoided.
The Pilot ONE controller allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For processes that must not restart automatically, select OFF/Standby; for unattended cooling, Power Failure Auto resumes operation after power returns.
Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The 4-year warranty requires registration; failure to register may void extended coverage.
Selection & Integration Q&A
Choose the 055T when you need up to 5.5 kW cooling at 15 °C and can accept the larger footprint and 281 kg weight. The 030T and 040T offer lower capacity but may suffice for smaller loads; the 055T is justified when process heat rejection exceeds their limits.
The 055T requires a 400 V 3~ 50 Hz supply with a 16 A fuse and draws up to 7 A. It is delivered with a cable but without a plug, so a suitable three-phase plug must be provided on site. Voltage and frequency tolerances are ±5 % and ±2 %, not simultaneously in opposite directions.
Install indoors at 5–40 °C ambient and up to 2000 m altitude, with illuminance at least 300 lx. Maintain 50–200 cm wall clearance per side for maintenance. The unit is IP20, so protect from water; if water-cooled, protect electrical lines below against condensate.
The base delivery includes a hose coupling for the G1 1/4 male pump connection but no plug. Refrigerant circuit work must be by certified contractors. The 4-year warranty requires registration. No other consumables are specified; regular maintenance per the manual is required.