Peter Huber Kältemaschinenbau Unichiller GL 075
Peter Huber Kältemaschinenbau Unichiller GL 075 — Recirculating chillers.
The Unichiller GL 075 is a recirculating chiller with a 7.5 kW cooling capacity at 20 °C, rated for -20 to 40 °C and a 460 V three-phase 60 Hz supply. It uses a fixed-speed pressure pump delivering up to 50 l/min at 3.5 bar through G1 1/4 male connections. It is intended for externally closed cooling circuits in industrial processes.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller GL 075 Current | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | Pressure pump, speed not variable |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and positioning
- The GL 075 is a free-standing recirculating chiller in the Unichiller series, distinguished by its 7.5 kW cooling capacity at 20 °C and 460 V three-phase 60 Hz power supply.
- Unlike sibling models such as the Unichiller 030T (69 dB(A)) or 030Tw (61 dB(A)), the GL 075 is not specified with a noise level in the provided facts; selection should focus on its higher cooling capacity and electrical configuration.
- The unit uses R-744 (CO2) refrigerant (GHS H280) and is classified IP20, requiring a dry indoor installation.
Behavior under load and media
- The operating temperature range is -20 to 40 °C; cooling capacity is 7.5 kW at 20 °C but may drop as ambient temperature rises, so sizing must account for actual room conditions.
- The pump is a fixed-speed pressure pump (not speed-adjustable) with maximum delivery 50 l/min at up to 3.5 bar; external circuit pressure drop must be checked against these limits.
- The unit is designed for externally closed applications only; open-loop or unclosed circuits are not permitted.
Installation, connection and control
- Electrical supply: 460 V three-phase 60 Hz, with voltage tolerance ±5% and frequency tolerance ±2% (not all combinations allowed). External branch circuit protection according to UL 489 is required. Three-phase devices below 63 A are delivered with cable but without a plug.
- Hydraulic connection: G1 1/4 male pump connection; mating hoses or fittings must match this thread. Maximum tightening torques must not be exceeded and connections must be counterheld.
- Control: Pilot ONE controller with Ethernet, USB (Host and Device), and RS232 interfaces; external Pt100 sensor connection available. Power-failure response configurable as OFF/Standby, ON, or Power Failure Auto.
- Installation environment: indoor use only, illuminance at least 300 lx, altitude up to 2000 m; ambient temperature 5 to 40 °C; wall clearance 50 to 200 cm per side for maintenance.
- Safety: not explosion-protected; must not be installed in ATEX zones. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached.
Integration & Operating Notes
The chiller requires a 460 V three-phase 60 Hz supply. Voltage tolerance is ±5% and frequency tolerance ±2%, but not all combinations are allowed. Verify site power quality before installation; a transformer or different supply may be needed.
The electrical design must include a UL 489 listed breaker for branch circuit protection. Three-phase devices below 63 A are delivered with cable but without a plug, so the installer must provide a suitable connection.
A wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. Leveling feet must be unscrewed/activated and parking brakes applied before switching on the unit.
The Pilot ONE controller allows power-failure response to be set as OFF/Standby, ON, or Power Failure Auto. For processes where automatic restart is unsafe, select OFF/Standby; for continuous cooling, Power Failure Auto may be appropriate.
In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature trigger value is reached, instead of switching off all poles. This is critical for exothermic processes where cutting cooling would cause runaway temperatures.
The unit must not be installed or started up inside an ATEX zone because it is not explosion-protected. Ensure the installation location is classified as non-hazardous.
The equipment is Class A, Group 1 for electromagnetic disturbance to EN55011. In residential or sensitive environments, additional EMC measures may be necessary.
Selection & Integration Q&A
Choose the GL 075 when you need 7.5 kW cooling at 20 °C and have a 460 V three-phase 60 Hz supply. Siblings like the 030T offer lower capacity and different noise levels (69 dB(A) vs 61 dB(A) for 030Tw); select based on required cooling capacity and electrical configuration.
The pump connection is G1 1/4 male; mating hoses or fittings must match this thread. The external circuit must be closed and its pressure drop checked against the pump's maximum delivery of 50 l/min at 3.5 bar. Do not exceed maximum tightening torques and counterhold connections.
Refrigerant circuit work must be by approved contractors. Monitor fluid level via digital indicator. Three-phase devices below 63 A are delivered with cable but without a plug; installer must provide a UL 489 breaker and suitable plug. No other accessories are specified in the provided facts.