Peter Huber Kältemaschinenbau Unichiller 055Tw
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 055Tw

Peter Huber Kältemaschinenbau Unichiller 055Tw — Recirculating chillers.

The Unichiller 055Tw is a water-cooled recirculating chiller with a C3 pump and Pilot ONE controller, covering -20 to 40 °C. It is the 055-size 'Tw' variant in the series, distinguished by water cooling and a G1/2 cooling-water connection. It serves externally closed process loops requiring heat removal at up to 6 bar cooling-water pressure.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller 055Tw Current —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040T-H 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 055T-H 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 250 kg
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 180 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 260 l/h · at 15°C, flow 15°C: 330 l/h
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

The Unichiller 055Tw is a free-standing, water-cooled recirculating chiller. Within the series, the 'T' denotes the base air-cooled family, while the 'Tw' suffix indicates water cooling; the 055 code is a size/volume identifier, not a rating. Sibling models such as the 030T and 040T are air-cooled and smaller, with noise levels of 69 dB(A) for the 030T and 040T and 61 dB(A) for the 030Tw. The 055Tw is the largest sibling listed and is water-cooled, so its acoustic profile is not directly comparable to the air-cooled units. The unit is intended only for externally closed applications and is not explosion-protected; it must not be installed in an ATEX zone.

Working range and media behavior

The temperature range is -20 to 40 °C, with an ambient limit of 5 to 40 °C. Cooling water consumption depends on the leaving fluid temperature: 330 l/h at 15 °C flow, 260 l/h at 0 °C flow, and 180 l/h at -10 °C flow, all at a 15 °C cooling-water inlet. The datasheet states cooling power is valid only at 20 °C room temperature, 15 °C cooling-water inlet, and 0.6 bar differential pressure; higher cooling-water temperatures reduce capacity and may increase flow. The cooling-water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible water may be used. The refrigerant is R-290 (A3, H220), requiring flammable-refrigerant safety measures and a check of charge versus room volume.

Installation, control and operation

The unit requires a 400 V 3~ 50 Hz supply with a 3x16 A fuse and maximum current of 7.5 A; three-phase devices under 63 A are delivered with cable but without a plug. Cooling water must be supplied at 5 to 20 °C inlet and 0.6 to 6 bar. The Pilot ONE controller provides Ethernet, USB (host and device), and RS232 interfaces, and supports configurable power-failure response (OFF/Standby, ON, or Power Failure Auto). Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, rather than switching off all poles. Leveling feet or parking brakes must be engaged before startup, and cooling water must be shut off even for overnight downtimes.

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access to the refrigerant circuit and connections. Plan the footprint around the 640 x 660 x 1606 mm dimensions and 250 kg net weight, and ensure the floor can support the unit.

Unichiller Operation Manual, page 25
Electrical
Provide a 3x16 A fused supply and a suitable plug on site

The unit draws a maximum of 7.5 A per phase at 400 V 3~ 50 Hz and is delivered with a cable but without a plug because its current is below 63 A. The installer must fit a compatible plug and ensure voltage tolerance stays within ±5% with frequency within ±2%, avoiding the prohibited combination of -5% voltage and +2% frequency.

Unichiller 055Tw Technical Datasheet, page 2
Process Limits
Cooling water must enter at 5–20 °C and 0.6–6 bar

The chiller is water-cooled and requires a cooling-water differential pressure of at least 0.6 bar and a maximum pressure of 6 bar. Inlet temperature must stay between 5 °C and 20 °C; below the condensation point, internal cooling-water pipes must be insulated to prevent condensation. Shut off cooling water even for short downtimes such as overnight.

Unichiller 055Tw Technical Datasheet, page 2; Operation Manual, page 28
Maintenance
Refrigerant circuit work requires certified contractors

Any work on the refrigerant circuit must be performed only by approved refrigeration/air-conditioning system contractors. The unit uses R-290 (A3, H220) refrigerant, so flammable-refrigerant handling rules apply. Verify refrigerant charge against room volume at installation to avoid exceeding the limit per m³ of ambient air.

Unichiller Operation Manual, pages 15, 17
Environment
Indoor use only, with at least 300 lx illuminance

The unit is rated IP20 and may only be used indoors up to 2000 m altitude, with ambient temperature between 5 °C and 40 °C. Illuminance at the installation site must be at least 300 lx. Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.

Unichiller Operation Manual, pages 25, 28

Selection & Integration Q&A

When should I choose the Unichiller 055Tw over the smaller 030T or 040T siblings?

Choose the 055Tw when you need water cooling and the larger 055 frame; the 030T and 040T are air-cooled and smaller. The 055Tw requires a cooling-water supply at 5–20 °C and 0.6–6 bar, so it suits sites with available cooling water rather than air-cooled spaces.

What cooling-water supply and quality does the 055Tw require from adjacent systems?

Supply cooling water at 5–20 °C inlet, 0.6–6 bar differential pressure, and compatible with copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM. Consumption is 330 l/h at 15 °C flow, 260 l/h at 0 °C, and 180 l/h at -10 °C, all at 15 °C inlet.

What are the mounting and duty-cycle limits for the 055Tw?

Install indoors only, at 5–40 °C ambient, up to 2000 m altitude, with at least 300 lx illuminance. Maintain 50–200 cm side clearance for maintenance. Engage leveling feet or parking brakes before startup, and shut off cooling water even for overnight downtimes.

What maintenance and accessories are required beyond the base delivery?

The unit ships with a cable but no plug, so a suitable 3x16 A plug must be provided. Refrigerant circuit work requires approved contractors. No consumables or spare parts are listed in the provided facts; follow the manual's maintenance section for service intervals.