Peter Huber Kältemaschinenbau Unichiller 055T
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 055T

Peter Huber Kältemaschinenbau Unichiller 055T — Recirculating chillers.

The Unichiller 055T is a recirculating chiller for externally closed circuits, rated -20 to 40 °C with R-290 refrigerant and a 400 V three-phase supply. Its cooling capacity falls from 5.5 kW at 15 °C to 0.2 kW at -20 °C, so it suits moderate-temperature process cooling rather than deep-freeze duty. The Pilot ONE controller and G1 1/4 male pump connection integrate it into industrial cooling loops.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller 055T Current —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040T-H 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T-H 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 055Tw —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Minimum fill volume 5 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 281 kg
Electrical, Power & Drive Specifications
Current consumption 7 A
Fuse rating 16 A
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance and ensure adequate airflow. Insufficient clearance can lead to overheating and restricted service access.

Unichiller Operation Manual, Section on Installation (page 25
Electrical
Provide a suitable 16 A three-phase plug on site

The unit is delivered with a cable but without a plug because three-phase devices below 63 A are supplied that way. The installer must fit a plug rated for 400 V 3~ 50 Hz and 16 A, and ensure the supply can deliver 7 A per phase.

Unichiller 055T Technical Datasheet, Electrical Specifications (page 2
Process Limits
Use only in externally closed circuits with at least 5 l fill

The chiller is designed for externally closed applications. The minimum filling capacity is 5 l and the expansion volume is 7.5 l; operating with less fluid or in an open circuit can cause pump cavitation and inadequate cooling.

Unichiller 055T Technical Datasheet, Hydraulic Specifications (page 1
Safety
Do not install in an ATEX zone; R-290 refrigerant is flammable

The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. The refrigerant R-290 (A3, H220) requires that the refrigerant charge and room size be checked to avoid exceeding the limit per m³ of ambient air, and ignition sources must be avoided.

Unichiller Operation Manual, Safety and Installation (pages 13, 15
Control & I/O
Configure power-failure response to match process restart needs

The Pilot ONE controller allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For processes that must not restart automatically, select OFF/Standby; for unattended cooling, Power Failure Auto resumes operation after power returns.

Unichiller Operation Manual, Operation (page 19
Maintenance
Refrigerant circuit work only by certified contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The 4-year warranty requires registration; failure to register may void extended coverage.

Unichiller Operation Manual, Maintenance (page 17); Datasheet (page 1

Selection & Integration Q&A

When should I choose the Unichiller 055T over the smaller 030T or 040T models?

Choose the 055T when you need up to 5.5 kW cooling at 15 °C and can accept the larger footprint and 281 kg weight. The 030T and 040T offer lower capacity but may suffice for smaller loads; the 055T is justified when process heat rejection exceeds their limits.

What are the requirements for the electrical supply and plug for the 055T?

The 055T requires a 400 V 3~ 50 Hz supply with a 16 A fuse and draws up to 7 A. It is delivered with a cable but without a plug, so a suitable three-phase plug must be provided on site. Voltage and frequency tolerances are ±5 % and ±2 %, not simultaneously in opposite directions.

What installation clearances and ambient conditions must be respected?

Install indoors at 5–40 °C ambient and up to 2000 m altitude, with illuminance at least 300 lx. Maintain 50–200 cm wall clearance per side for maintenance. The unit is IP20, so protect from water; if water-cooled, protect electrical lines below against condensate.

What maintenance and accessories are required beyond the base delivery?

The base delivery includes a hose coupling for the G1 1/4 male pump connection but no plug. Refrigerant circuit work must be by certified contractors. The 4-year warranty requires registration. No other consumables are specified; regular maintenance per the manual is required.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 055T Technical Datasheet
Datasheet ·30,4 КБ ·2 pp.
View PDF