Peter Huber Kältemaschinenbau Unichiller 100T
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 100T

Peter Huber Kältemaschinenbau Unichiller 100T — Recirculating chillers.

The Unichiller 100T is an air-cooled recirculating chiller for externally closed loops, operating from -20 to 40 °C with a C3 pump and G1 1/4 male connections. It is the 100-size model in the Unichiller series, distinguished from smaller 030/040 siblings by its larger capacity and 400 V three-phase supply. It serves as the primary cooling source for closed process circuits requiring stable temperature control.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller 100T Current —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040T-H 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 055T-H 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 055Tw —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Expansion volume 7 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 271 kg
Electrical, Power & Drive Specifications
Current consumption 13 A (max)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, connection and control

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow maintenance access to the refrigeration circuit and pump. Insufficient clearance blocks service work and may impede air flow on this air-cooled unit.

Unichiller Operation Manual, Installation
Electrical
Provide a 3x16 A fused three-phase supply and site plug

The unit draws up to 13 A from a 400 V 3~ 50 Hz supply and requires a 3x16 A fuse. Because three-phase devices below 63 A ship with cable but without plug, the installer must procure and fit a matching plug; verify voltage ±5% and frequency ±2% before commissioning.

Unichiller 100T Technical Data, Specifications
Process Limits
Closed-loop circuit only; plan for 8.36 l minimum fill

The chiller is designed exclusively for externally closed applications. The external loop plus expansion volume must accommodate at least 8.36 l filling capacity, while the 7 l expansion volume limits how much thermal expansion the system can absorb without overfilling.

Unichiller 100T Technical Data, Specifications; Operation Manual, Selection
Cooling & Media
Cooling capacity derates above 20 °C room temperature

Published cooling capacity is valid at 20 °C room temperature. If the installation room runs warmer — up to the 40 °C ambient limit — available cooling capacity drops, so sizing margins must reflect actual site conditions rather than the datasheet rating.

Unichiller 100T Technical Data, Specifications
Safety
Select power-failure response before connecting exothermic loads

The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For processes where loss of cooling is hazardous, configure Process Safety mode so maximum cooling is released at the overtemperature trigger instead of all poles switching off.

Unichiller Operation Manual, Normal Operation / Safety
Maintenance
Refrigerant work restricted to approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The R-449A charge has a CO2 equivalent of 5.6 t, which may trigger leak-check and reporting obligations; plan service access accordingly.

Unichiller Operation Manual, Maintenance; Technical Data
Installation
Do not install in an ATEX zone or outdoors

The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. It is rated IP20 and for indoor use only, at illuminance of at least 300 lx and altitude up to 2000 m; check refrigerant charge against room volume to stay within the permissible limit per m³.

Unichiller Operation Manual, Installation

Selection & Integration Q&A

When should I choose the Unichiller 100T instead of the smaller 030T or 040T siblings?

Choose the 100T when the closed-loop heat load and hydraulic volume exceed the capacity of the 030/040 models. It provides a larger expansion volume (7 l) and minimum fill of 8.36 l, and requires a 400 V three-phase 3x16 A supply — confirm your site has this before selecting it over single-phase siblings.

What adjacent system parts must match the 100T's hydraulic and electrical connections?

The external circuit must mate with G1 1/4 AG male pump connections and be a closed loop holding at least 8.36 l. Electrically, provide a 400 V 3~ 50 Hz supply with 3x16 A fuse and a site-fitted plug (cable supplied, plug not). The Pilot ONE offers Ethernet, USB and RS232 for controller integration.

What maintenance and consumables are required, and what is not included in delivery?

Refrigerant-circuit work must be done by approved refrigeration contractors; the R-449A charge has a 5.6 t CO2 equivalent, which may impose leak-check intervals. The unit ships with a power cable but no plug, and no hoses or adapters for the G1 1/4 connections — these must be sourced separately. Shut off cooling water even for overnight downtime if water-cooled auxiliaries are present.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 100T Technical Data
Datasheet ·77,9 КБ ·2 pp.
View PDF