Peter Huber Kältemaschinenbau Unichiller P075w-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P075w-H

Peter Huber Kältemaschinenbau Unichiller P075w-H — Recirculating chillers.

The Unichiller P075w-H is a water-cooled recirculating chiller with a 7.5 kW cooling capacity at 20 °C, designed for externally closed applications. Its 'P' designation indicates suitability for high-pressure-drop circuits, and the E2 pump delivers up to 130 l/min at 5.7 bar. It operates from -20 to 100 °C with 2 kW heating, serving as a precise temperature control source for industrial processes.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller P075w-H Current —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040T-H 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 055T-H 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 055Tw —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Expansion volume 48 l
Heating capacity 2 kW
Minimum fill volume 18 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type E2
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 296 kg
Electrical, Power & Drive Specifications
Current consumption 14 A
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 240 л/час (at 15°C, flow -20°C)
at 15°C, flow -10°C: 270 л/час · at 15°C, flow 0°C: 330 l/h
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and Series Positioning

The Unichiller P075w-H is a water-cooled recirculating chiller in the Unichiller series, distinguished by its 'P' model code, which the manual identifies as particularly suitable for applications requiring high pressure drops. Unlike air-cooled siblings such as the Unichiller 030T (69 dB(A)) or 030Tw (61 dB(A)), this model uses a cooling water circuit with G1/2 male connections and does not rely on fan cooling, making its noise profile irrelevant. The unit is built for externally closed applications only, with a minimum filling capacity of 18 l and an expansion volume of 48 l. The E2 circulation pump provides a maximum delivery of 130 l/min at up to 5.7 bar, though flow falls to 20 l/min at 5.5 bar, so system pressure drop must be checked against the pump curve. The refrigerant is R-449A (GWP 1397, 0.95 kg charge, 1.3 t CO2 equivalent).

Behavior Under Load and Temperature Range

The chiller covers a working temperature range of -20 to 100 °C, with cooling power rated at 7.5 kW at 20 °C, 5.3 kW at 0 °C, 3.3 kW at -10 °C, and 1.8 kW at -20 °C. This capacity must be matched to the actual process temperature, as available cooling drops significantly at lower temperatures. The 2 kW heating capacity allows for precise temperature control across the range. The unit requires a cooling water supply with a differential pressure of at least 0.5 bar and a maximum pressure of 6 bar; cooling water consumption varies with flow temperature: 330 l/h at 0 °C, 270 l/h at -10 °C, and 240 l/h at -20 °C (all at 15 °C cooling water intake). The cooling water intake temperature must be between 5 °C and 20 °C; if below the condensation point, internal cooling water pipes must be insulated.

Installation, Control and Operation

The Pilot ONE controller provides Ethernet, USB (Host and Device), and RS232 interfaces, and supports external Pt100 sensors. The power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, rather than switching off all poles. The unit is rated IP20 and must be operated indoors at 5–40 °C ambient and at least 300 lx illuminance, up to 2000 m altitude. A wall clearance of 50–200 cm per side is required for maintenance. Electrical supply is 400 V 3~ 50 Hz with a maximum current of 14 A and a 3x16 A fuse; three-phase devices under 63 A are supplied with cable but without a plug. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and -5% voltage with +2% frequency is not allowed. The unit is not explosion-protected and must not be installed in an ATEX zone. Leveling feet must be activated and parking brakes applied before operation. Cooling water supply must be shut off even for short downtimes.

Integration & Operating Notes

Process Limits
Cooling capacity drops sharply at low temperatures

The chiller delivers 7.5 kW at 20 °C but only 1.8 kW at -20 °C. The process heat load must be checked against the actual operating temperature, not the nominal rating, to avoid insufficient cooling at the low end of the range.

Unichiller P075w-H Datasheet, page 1
Cooling & Media
Cooling water must be within pressure and temperature window

The cooling water supply must provide a differential pressure of at least 0.5 bar and must not exceed 6 bar. Intake temperature must be between 5 °C and 20 °C; if below the condensation point, internal pipes must be insulated to prevent condensation damage.

Unichiller P075w-H Datasheet, page 2
Electrical
Voltage and frequency tolerances are interdependent

A voltage tolerance of ±5% is permitted only with a simultaneous frequency tolerance of ±2%. A -5% voltage combined with +2% frequency is explicitly not allowed. The site power quality must be verified to avoid malfunction or damage.

Unichiller P075w-H Datasheet, page 2
Mounting
Maintain side clearance for maintenance access

A wall clearance of 50 to 200 cm per side is required on free-standing models to allow maintenance access. The unit must be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude.

Unichiller Operation Manual, page 25
Control & I/O
Configure power-failure response for process safety

The Pilot ONE controller allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, instead of switching off all poles.

Unichiller Operation Manual, pages 18-19
Maintenance
Refrigerant circuit work requires certified contractors

Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a charge of 0.95 kg (1.3 t CO2 equivalent), and room size must be checked to avoid exceeding the refrigerant limit per m³.

Unichiller Operation Manual, page 17

Selection & Integration Q&A

When should I choose the P075w-H over an air-cooled Unichiller like the 030T or 030Tw?

Choose the P075w-H when your process has high pressure drop (the 'P' designation) and you have a cooling water supply available. Air-cooled models like the 030T are limited to lower capacities and rely on fan cooling, which adds noise (69 dB(A) for 030T). The P075w-H offers 7.5 kW cooling at 20 °C and is water-cooled, avoiding fan noise but requiring cooling water connections.

What are the requirements for the cooling water supply and the process circuit?

The cooling water supply must provide G1/2 male connection, differential pressure of at least 0.5 bar, maximum pressure 6 bar, and intake temperature between 5 °C and 20 °C. The process circuit must be externally closed with a minimum fill volume of 18 l and accommodate an expansion volume of 48 l. The pump delivers up to 130 l/min at 5.7 bar, so check system pressure drop against the pump curve.

What installation environment and duty-cycle limits apply?

Install indoors only, at 5–40 °C ambient, IP20, at least 300 lx illuminance, up to 2000 m altitude. Maintain 50–200 cm wall clearance per side for maintenance. Do not install in an ATEX zone. Activate leveling feet and parking brakes before operation. Shut off cooling water even for short downtimes. Power-failure response is configurable via Pilot ONE.

What maintenance is required and what accessories are not included?

Refrigerant circuit work must be done by approved refrigeration contractors. The unit is supplied with cable but without a plug for three-phase connection (14 A, 3x16 A fuse). No external Pt100 sensor is included; it must be ordered separately if needed. Regular maintenance includes checking cooling water quality and inspecting for leaks; no specific interval is given in the provided documents.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P075w-H Datasheet
Datasheet ·92,3 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF