Peter Huber Kältemaschinenbau Unistat 635w Dynamisches
Peter Huber Kältemaschinenbau Unistat 635w Dynamisches — Temperature control units.
The Unistat 635w Dynamisches is a water-cooled, free-standing temperature control unit with a -60 to 200 °C range, 24 kW heating and a magnetically coupled stainless-steel pump delivering up to 196 l/min. It is the largest water-cooled modification in the Unistat 5xx/6xx series, distinguished by its 400 V 3~ 50 Hz supply, 56 A maximum current and 3x63 A fuse requirement. It serves as a high-capacity circulator for externally closed or open processes requiring precise temperature control with Pilot ONE regulation.
Peter Huber Kältemaschinenbau Unistat Series — Model Comparison & Selection
| Model | Noise level, dB | Display resolution | Heating capacity, W | Pump connection | Pump type | Temperature range, °C |
|---|---|---|---|---|---|---|
| Unistat 635w Dynamisches Current | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 527w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 530w Dynamisches | 59 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 540w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | Pressure pump, variable | -60–200 |
| Unistat 620w Dynamisches | 68 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 640w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 645w Dynamisches | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 650w Dynamisches | 73 | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 680w Dynamisches | — | 0, 01 | 96000 | DN50 PN16 (DIN EN 1092-1 | magnetically coupled, st | -60–200 |
| Unistat GL 530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat P510 Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P520 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P527w Dynamisches | 57 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P530w Dynamisches | 62 | 0.01 | 12000 | M38x1,5 AG male | magnetically coupled, st | -55–250 |
| Unistat P540w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P610 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615 Dynamisches | — | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P620w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P635w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P645w Dynamisches | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat P650w Dynamisches | — | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
Full specifications
| Control output | POKO ONE (potential-free contact) |
| Heating capacity | 24 kW |
| Pump connection | M38x1, 5 AG male |
| Pump speed adjustable | Yes |
| Pump type | magnetically coupled, stainless steel |
| External sensor connection | Pt100 |
| Temperature range | -60...200 °C |
| Weight | 721 kg (net) |
| Current consumption | 56 A (max) |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Maximum viscosity | 100 mm²/s (max permissible) |
| Ambient temperature limit | 5...40 °C (permissible) |
| Cooling water connection | G3/4 male |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The 635w is a water-cooled (w suffix) free-standing unit measuring 918x963x1771 mm and weighing 721 kg, with a stainless-steel magnetically coupled pump and M38x1.5 male pump connections.
- Within the Unistat 5xx/6xx family, it is the highest-capacity water-cooled variant listed; siblings such as the 510w, 515w, 520w and 525 Dynamisches are smaller air-cooled or lower-output models. The 635w is selected when process heat loads and flow requirements exceed the smaller frames.
- It uses R-1270 refrigerant (A3, H220, GWP 0) with a 2.56 kg charge, which imposes room classification and ventilation requirements distinct from air-cooled siblings.
Thermal and hydraulic behavior
- The working range is -60 to 200 °C with 24 kW heating capacity. The pump delivers 196 l/min maximum and 86 l/min at 2.0 bar, with a maximum delivery pressure of 2.5 bar; external circuit pressure drop must be checked against this curve.
- The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s, which limits fluid selection at low temperatures and must be respected to avoid pump overload.
- Rated cooling capacity is valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure; the unit is designed for cooling water intake between 5 °C and 20 °C. Cooling water connections are G3/4 male, with 1–4 bar differential pressure and 6 bar maximum static pressure.
Control, installation and operation
- The Pilot ONE controller provides a 0.01 K display resolution, Ethernet, USB (host and device) and RS232 interfaces, a Pt100 external sensor connection, and a potential-free POKO ONE control output. Pump speed is adjustable.
- The unit requires a 400 V 3~ 50 Hz supply with a 3x63 A fuse and draws up to 56 A; it is delivered with cable but without a plug. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations (e.g. -5% voltage with +2% frequency) are not allowed. Leakage current exceeds 3.5 mA, affecting RCD selection and earthing.
- Installation must be in a dry indoor location (IP20, ambient 5–40 °C), outside ATEX zones. The unit must be transported upright and emptied; casters are not for transport. A drip tray is required below the unit. For externally closed applications the expansion vessel must remain unlocked; for externally open applications it must be locked.
Integration & Operating Notes
The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s, which limits fluid selection at low temperatures and must be respected to avoid pump overload and poor circulation. Minimum filling capacity is 8.9 l and the expansion tank holds 19.9 l, setting the minimum fluid charge and expansion allowance.
Shut off the cooling water supply to the temperature control unit even for shorter downtimes (e.g. overnight) to prevent water damage and unnecessary load on the cooling water circuit. Hoses and connections must be periodically checked for leaks and quality and replaced as needed.
Selection & Integration Q&A
Choose the 635w when your process requires the higher heating capacity (24 kW) and pump flow (196 l/min max) of the largest water-cooled frame, or when cooling water is available and air-cooled siblings cannot meet the heat rejection. The 510w, 515w, 520w and 525 are smaller air-cooled or lower-output models; select them only if their capacity and cooling mode match your load.
The unit requires a 400 V 3~ 50 Hz supply with a 3x63 A fuse and draws up to 56 A. It is delivered with cable but without a plug, so a suitable plug must be provided on site. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and leakage current exceeds 3.5 mA, so RCD selection and earthing must be engineered accordingly.
Install in a dry indoor location with ambient temperature 5–40 °C and IP20 protection, outside ATEX zones. The unit must be transported upright and emptied; casters are not for transport. Allow about 2 hours acclimation after moving between cold and warm environments. A drip tray is required below the unit, and cooling water must be shut off even for overnight downtimes.
Periodically check hoses and connections for leaks and quality and replace as needed; clean liquefier fins and the hat-type strainer/dirt trap; inspect heat transfer fluid and replace or rinse the circuit as required. The base delivery does not include a power plug, a drip tray, or cooling water hoses; these must be provided on site. Refrigerant-circuit work requires approved contractors.