Peter Huber Kältemaschinenbau Unichiller 070T-H
Peter Huber Kältemaschinenbau Unichiller 070T-H — Recirculating chillers with Noise level 66 dB.
The Unichiller 070T-H is an air-cooled recirculating chiller with a 7 kW cooling capacity at 15 °C and a -10…100 °C operating range. It is the higher-capacity modification in the Unichiller series, distinguished by its 2 kW heating stage and Pilot ONE controller. It serves externally closed process loops requiring precise temperature control.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 070T-H Current | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Noise level | 66 dB(A) |
| Heating capacity | 2 kW |
| Minimum fill volume | 5 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | C3 |
| External sensor connection | Pt100 |
| Temperature range | -10...100 °C |
| Weight | 234 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and Series Positioning
The Unichiller 070T-H is a free-standing, air-cooled recirculating chiller using R-449A refrigerant. Within the Unichiller series, it is positioned above the 030T and 040T siblings, offering greater cooling capacity (7 kW at 15 °C) and an integrated 2 kW heating stage. The 'H' suffix denotes heating capability, while the 'T' indicates the standard tower configuration. The unit is intended for externally closed applications only, as specified in the operation manual.
Performance and Media Behavior
Cooling capacity is strongly temperature-dependent: 7 kW at 15 °C, 4 kW at 0 °C, and 2.3 kW at -10 °C, measured at a 20 °C room temperature. The unit uses a C3 pump with G1 1/4 male connections and a fixed pump speed. The minimum filling volume is 5 l, and the expansion volume is 7.5 l. The temperature range of -10 to 100 °C is managed by the Pilot ONE controller, which supports Pt100 external sensor connection.
Installation, Control and Operation
The chiller requires a 400 V three-phase 50 Hz supply and is delivered with a cable but without a plug for final connection. It is rated IP20 and must be installed indoors in a dry location with at least 300 lx illuminance. Wall clearance of 50 to 200 cm per side is required for maintenance. The Pilot ONE controller provides Ethernet, USB (host and device), and RS232 interfaces. The power-failure response is configurable (OFF/Standby, ON, or Power Failure Auto), and a Process Safety mode is available for exothermic processes.
Integration & Operating Notes
Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow maintenance access and adequate air flow for the air-cooled condenser. Insufficient clearance can lead to overheating and reduced cooling capacity.
The unit accepts ±5% voltage and ±2% frequency tolerance, but these must not be combined in opposite directions. Ensure the site supply meets both conditions simultaneously to avoid compressor damage or invalid operation.
The chiller is delivered with a cable but no plug. The customer must provide a suitable three-phase connection (400 V, 50 Hz) with a current rating below 63 A, and ensure the final connection complies with local electrical codes.
Cooling capacity is 7 kW at 15 °C, 4 kW at 0 °C, and 2.3 kW at -10 °C, based on a 20 °C room temperature. If the ambient temperature exceeds 20 °C, the available cooling capacity may drop further. Size the unit for the actual duty point and expected ambient conditions.
The unit is designed exclusively for externally closed loops. Do not connect it to open tanks or systems where the thermal fluid is exposed to atmosphere, as this can cause contamination, evaporation, and poor temperature control.
The Pilot ONE controller allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For processes where automatic restart is hazardous, select OFF/Standby; for critical cooling, consider Process Safety mode which releases maximum cooling capacity on overtemperature.
Any work on the refrigerant circuit must be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (GHS H280), and handling requires appropriate ventilation and safety precautions.
Selection & Integration Q&A
Choose the 070T-H when you need higher cooling capacity (7 kW at 15 °C) and integrated heating (2 kW). The 030T and 040T offer lower capacity and no heating. The 070T-H is also quieter (66 dB(A)) than the 030T (69 dB(A)). Select siblings for lower loads or where heating is not required.
The pump connection is G1 1/4 male, so mating hoses or fittings must have a G1 1/4 female thread. Use hoses rated for the temperature range (-10 to 100 °C) and compatible with the thermal fluid. Ensure the external loop volume plus the 5 l minimum fill and 7.5 l expansion volume are accommodated.
Install indoors only, with illuminance at least 300 lx and altitude up to 2000 m. Ambient temperature must be 5–40 °C. Maintain 50–200 cm side clearance for maintenance. The unit is IP20, so keep it dry. It is air-cooled, so ensure adequate ventilation for heat rejection.
The unit is delivered with a cable but without a plug; the customer must provide the three-phase connection. Refrigerant circuit work must be by certified contractors. Regular maintenance includes checking refrigerant charge and room size per manual. No specific maintenance intervals are given in the provided facts; consult the manual for details.