Peter Huber Kältemaschinenbau Unichiller 040T-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 040T-H

Peter Huber Kältemaschinenbau Unichiller 040T-H — Recirculating chillers with Noise level 69 dB.

The Unichiller 040T-H is a 400 V three-phase, air-cooled recirculating chiller with a 2 kW heater and a -10 to 100 °C working range, controlled by the Pilot ONE. Its 'H' suffix denotes the heating function, distinguishing it from the unheated 040T sibling. It serves externally closed cooling circuits requiring both heat removal and active temperature elevation.

Noise level
69 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller 040T-H Current 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 055T-H 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 055Tw —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Noise level 69 dB(A)
Heating capacity 2 kW
Maximum delivery flow rate 26 l/min (pressure pump max delivery capacity)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 171 kg
Electrical, Power & Drive Specifications
Current consumption 9 A (max)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and Series Positioning

The 040T-H is a free-standing, air-cooled chiller with an integrated 2 kW heater, rated for a -10 to 100 °C temperature range. Within the Unichiller series, the 'H' designation marks the heated variant: the base 040T lacks the 2 kW heating stage, while the 030Tw/030Tw-H are quieter (61 dB(A)) but smaller-capacity models; the 040T-H shares the 69 dB(A) noise level of the 030T and 040T. The unit is classified safety class III/FL per DIN 12876 with adjustable overtemperature protection, and is intended exclusively for externally closed applications. The refrigerant is R-449A (GWP 1397, CO₂ equivalent 2.7 t), and the refrigeration machine is CFC/HCFC-free.

Hydraulic and Thermal Behavior

The circulation pump (type B, non-adjustable speed) delivers a maximum of 26 l/min and 8 l/min at 2.0 bar, so the external circuit pressure drop must be checked against this curve. Minimum filling capacity is 3.5 l, and the atmospheric open expansion tank with digital level indicator requires fluid-level monitoring. Cooling capacity is rated at 20 °C room temperature and derates at higher ambient temperatures; the permissible ambient range is 5 to 40 °C. The 2 kW heater enables active temperature elevation within the -10 to 100 °C envelope.

Installation, Control and Operation

The Pilot ONE controller provides Ethernet, USB (host and device) and RS232 interfaces, plus a Pt100 connection for an external sensor. Power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, rather than switching off all poles. The unit requires a 400 V 3~ 50 Hz supply with a 3×10 A fuse; three-phase devices under 63 A are delivered with a cable but without a plug. Voltage and frequency tolerances must be met simultaneously, and the combination of -5% voltage with +2% frequency is not allowed. The pump connection is G3/4 male, and maximum tightening torques must not be exceeded with connections counterheld. A wall clearance of 50 to 200 cm per side is required for maintenance, and the unit must be used indoors at ≥300 lx and up to 2000 m altitude. Leveling feet must be activated and parking brakes applied before start-up. The unit is EMC class A, group 1 (EN55011), intended for industrial environments.

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing installation requires a wall clearance of 50 to 200 cm on either side to permit maintenance access to the refrigeration circuit and condenser. Insufficient clearance also restricts air flow around the air-cooled condenser, which can reduce cooling capacity and cause overheating.

Unichiller Operation Manual, Section on Installation (page 25
Electrical
Site must provide 3×10 A fusing and a mating plug

The 400 V 3~ 50 Hz supply must be protected by a 3×10 A fuse. Because the unit is delivered with a cable but without a plug (three-phase devices under 63 A), the customer must supply and fit the site plug. Voltage and frequency tolerances must be satisfied simultaneously; a -5% voltage with +2% frequency combination is explicitly not permitted.

Unichiller 040T-H Technical Datasheet, page 2
Process Limits
Externally closed circuit only; check pump curve at 2.0 bar

The unit is designed exclusively for externally closed applications. The pump delivers 26 l/min maximum and 8 l/min at 2.0 bar, so the external loop pressure drop must be verified against this curve. Minimum filling capacity is 3.5 l, and the atmospheric open expansion tank requires fluid-level monitoring via the digital indicator.

Unichiller Operation Manual, page 34; Unichiller 040T-H Technical Datasheet, page 1
Safety
Select Process Safety mode for exothermic reactions

In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature protection trigger value is reached, instead of switching off all poles. This prevents runaway temperatures in exothermic processes. The power-failure response is separately configurable as OFF/Standby, ON, or Power Failure Auto via the Pilot ONE.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work restricted to approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a CO₂ equivalent of 2.7 t, which may trigger periodic leak-check obligations under F-gas rules. Cooling water supply (where applicable) must be shut off even for short downtimes such as overnight.

Unichiller Operation Manual, pages 17 and 28; Unichiller 040T-H Technical Datasheet, page 1
Environment
Indoor use only, 5–40 °C ambient, ≥300 lx illuminance

The unit may only be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude. Ambient temperature must remain within 5 to 40 °C. Cooling capacity is rated at 20 °C room temperature and may drop at higher ambient temperatures, so capacity must be derated for warm rooms. The unit must not be installed or started inside an ATEX zone.

Unichiller Operation Manual, pages 13 and 25; Unichiller 040T-H Technical Datasheet, page 2

Selection & Integration Q&A

When should I choose the 040T-H over the 040T or the quieter 030Tw variants?

Choose the 040T-H when the process requires active heating up to 100 °C in addition to cooling; the base 040T lacks the 2 kW heater. If noise is critical, the 030Tw/030Tw-H at 61 dB(A) are quieter than the 69 dB(A) of the 040T-H, but they are smaller-capacity models.

What external circuit components and power provisions must be supplied by the customer?

The customer must provide a 400 V 3~ 50 Hz supply with 3×10 A fusing and fit a site plug (cable delivered without plug). Hoses and fittings must match the G3/4 male pump connection, and the external loop plus expansion volume must hold at least 3.5 l. The loop pressure drop must be checked against the pump curve (8 l/min at 2.0 bar).

What are the mounting and ambient limits for installing the 040T-H?

Install indoors only, at 5–40 °C ambient and ≥300 lx illuminance, below 2000 m altitude, and never inside an ATEX zone. Allow 50–200 cm wall clearance per side for maintenance and condenser air flow. Activate leveling feet and parking brakes before start-up. Cooling capacity is rated at 20 °C room temperature and derates at higher ambient.

What maintenance and service obligations apply, and what is not included in base delivery?

Refrigerant circuit work must be performed by approved refrigeration contractors; R-449A charge has a CO₂ equivalent of 2.7 t, which may trigger F-gas leak checks. The site plug is not included. Fluid level must be monitored via the digital indicator, and cooling water supply (if applicable) must be shut off even overnight.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 040T-H Technical Datasheet
Datasheet ·93,1 КБ ·2 pp.
View PDF