Peter Huber Kältemaschinenbau Unichiller 075w-H
Peter Huber Kältemaschinenbau Unichiller 075w-H — Recirculating chillers.
The Unichiller 075w-H is a water-cooled recirculating chiller for externally closed applications, rated -20...100 °C with 2 kW heating and a fixed-speed E1 pump. It is distinguished within the series by its water-cooled condenser, requiring a 5...20 °C cooling water supply at 0.5...6 bar. It serves as a temperature-control source for closed process loops in indoor industrial settings.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 075w-H Current | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Expansion volume | 48 l |
| Heating capacity | 2 kW |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E1 |
| External sensor connection | Pt100 |
| Temperature range | -20...100 °C |
| Weight | 300 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 240 л/час (at 15°C, flow -20°C) at 15°C, flow -10°C: 270 л/час · at 15°C, flow 0°C: 330 l/h |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Water-cooled condenser (no air-cooled fan), so heat is rejected to a facility cooling water circuit rather than to room air.
- Fixed-speed pump type E1 with G1 1/4 AG male pump connection; pump speed is not adjustable.
- 48 l expansion volume and 18 l minimum fill volume define the hydraulic buffer of the loop.
- Compared with the air-cooled Unichiller 030T/030Tw/030Tw-H/040T siblings, this model trades room-air heat rejection for a cooling water connection and adds heating (2 kW).
- Controller: Pilot ONE; interfaces Ethernet, USB host/device, RS232; external Pt100 sensor input.
Behavior and media
- Working range -20...100 °C; heating capacity 2 kW.
- Cooling water consumption depends on the required flow temperature at 15 °C cooling water inlet: 330 l/h at 0 °C, 270 l/h at -10 °C, 240 l/h at -20 °C.
- Cooling power falls and cooling water flow rate may rise as cooling water temperature increases; performance must be derated for warmer site water.
- Cooling water circuit materials: copper, stainless steel 1.4401, MS, PA, PPE, PTFE, EPDM — only compatible water may be used.
- Refrigerant R-449A, charge 0.95 kg, GWP 1397, CO2 equivalent 1.3 t.
Installation, control and operation
- 400 V 3~ 50 Hz supply, max current 12.5 A, fusing 3x16 A; delivered with cable but without plug (three-phase devices <63 A).
- Voltage tolerance ±5% only with simultaneous frequency tolerance ±2%; certain combinations are not allowed.
- Cooling water connection G1/2 male; min. differential pressure 0.5 bar, max. pressure 6 bar.
- Power-failure response configurable via Pilot ONE: OFF/Standby, ON, or Power Failure Auto.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, instead of switching off all poles.
- IP20; indoor use only, illuminance ≥300 lx, altitude up to 2000 m; ambient 5...40 °C.
- Overall dimensions 740x1160x1050 mm, net weight 300 kg; wall clearance 50–200 cm per side for maintenance.
Integration & Operating Notes
The water-cooled condenser requires a facility cooling water supply of 5...20 °C intake temperature and a differential pressure of at least 0.5 bar, with 6 bar maximum. Below the condensation point the internal cooling water pipes must be insulated to prevent condensation and electrical risk.
The unit draws up to 12.5 A per phase on 400 V 3~ 50 Hz and is delivered with cable but without a plug. The installer must provide a suitable plug or hardwired connection and 3x16 A fusing. Voltage tolerance is ±5% only with simultaneous frequency tolerance ±2%.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side for maintenance access. Before start-up, parking brakes at the casters must be activated and/or leveling feet unscrewed so the 300 kg unit cannot move during operation.
The chiller is designed for externally closed applications only and must not be installed or started inside an ATEX zone because it is not explosion-protected. Models with 'P' in the name are the ones suited to high pressure-drop loops; this model is not so designated.
Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit contains 0.95 kg R-449A (GWP 1397, CO2 equivalent 1.3 t), so leak checks and environmental reporting apply. Shut off cooling water even for overnight downtimes.
Selection & Integration Q&A
Choose the 075w-H when a facility cooling water circuit (5–20 °C, 0.5–6 bar) is available and heat must not be rejected to room air; it also adds 2 kW heating. The 030T/030Tw are air-cooled and lack the water connection, so they suit sites without cooling water.
Provide a cooling water supply at 5–20 °C and 0.5–6 bar with G1/2 male mating connection, and a closed process loop with G1 1/4 AG male pump fittings. The 400 V 3~ supply needs 3x16 A fusing and a plug (not delivered). Use only water compatible with copper, 1.4401, MS, PA, PPE, PTFE and EPDM.
Indoor use only, illuminance ≥300 lx, altitude ≤2000 m, ambient 5–40 °C, IP20. Allow 50–200 cm wall clearance per side for maintenance, activate caster brakes or leveling feet before start-up, and protect electrical lines below the unit against condensation ingress.
The unit ships with cable but without a plug; the installer supplies the plug or hardwired connection. Refrigerant-circuit service must be by approved contractors. Shut off cooling water even overnight. Insulate internal cooling water pipes if water falls below the condensation point. No accessories or cables beyond the power cable are included.