Peter Huber Kältemaschinenbau Unichiller P075
Peter Huber Kältemaschinenbau Unichiller P075 — Recirculating chillers with Noise level 61 dB.
The Unichiller P075 is a three-phase, 400 V recirculating chiller with a 130 l/min pump and G1 1/4 male connections, built for externally closed circuits. Its 'P' designation targets high-pressure-drop loops, delivering 20 l/min at 5.5 bar within a -20 to 40 °C range. It serves process cooling where ambient up to 40 °C and IP20 indoor siting apply.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P075 Current | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Noise level | 61 dB(A) |
| Expansion volume | 48 l |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E2 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 309 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The P075 is the high-pressure-drop variant of the Unichiller series; models with 'P' in the name are specifically suited to applications requiring high pressure drops (Operation Manual, p. 34).
- Sibling models 030T, 030Tw, 030Tw-H and 040T are distinguished here by noise level (69 dB(A) for 030T/040T, 61 dB(A) for 030Tw/030Tw-H); the P075 is rated 61 dB(A).
- Hydraulic interface is a single G1 1/4 male pump connection; the pump is type E2, non-speed-adjustable, with 130 l/min maximum delivery.
- The unit is for externally closed applications only (Datasheet p. 1; Manual p. 34) and is not explosion-protected.
Behavior under load and media
- Pump curve: 130 l/min maximum, falling to 20 l/min at 5.5 bar; system pressure drop must be matched to this curve (Datasheet p. 1).
- Cooling capacity is quoted at 20 °C room temperature and may drop as ambient rises (Datasheet p. 2); ambient limit is 5–40 °C.
- Temperature range is -20 to 40 °C; minimum fill 18 l, expansion volume 48 l in an atmospheric open tank with cover.
- Refrigerant is R-449A (A1, H280), GWP 1397; refrigerant charge and room size must be checked against the limit per m³ (Manual p. 15).
Installation, control and operation
- Power: 400 V 3~ 50 Hz, 3x16 A fuse; three-phase devices below 63 A are delivered with cable but without plug (Datasheet p. 2).
- Controller: Pilot ONE with Ethernet, USB host/device and RS232; external Pt100 sensor connection.
- Power-failure response configurable as OFF/Standby, ON or Power Failure Auto (Manual p. 19); Process Safety mode releases maximum cooling at the OT trigger (Manual p. 18).
- IP20, Class A Group 1 EMC; indoor use only, illuminance ≥300 lx, altitude up to 2000 m; wall clearance 50–200 cm per side (Manual p. 25).
Integration & Operating Notes
The unit is IP20 and must not be installed or started inside an ATEX zone. Ambient must stay between 5 and 40 °C, illuminance at least 300 lx, altitude up to 2000 m. Cooling capacity drops if ambient rises above the 20 °C rating point.
Selection & Integration Q&A
Choose the P075 when the process loop has high pressure drop: the 'P' designation targets such applications, with 20 l/min at 5.5 bar from a 130 l/min pump. The 030T/040T are 69 dB(A) siblings; the P075 is 61 dB(A). Select on pump curve match, not nominal capacity alone.
The pump connection is G1 1/4 male, so mating hoses or adapters must match this thread and be counterheld at the maximum tightening torque. The circuit must be externally closed, with at least 18 l fill and allowance for 48 l expansion in the atmospheric tank.
Install indoors only, not in an ATEX zone, at 5–40 °C ambient, ≥300 lx, up to 2000 m altitude, with 50–200 cm clearance per side. Secure leveling feet or parking brakes before start. Check refrigerant charge against room volume and protect lines below against condensate.
Three-phase units below 63 A ship with a cable but without a plug, so the customer supplies and fits it. Refrigerant-circuit work requires approved refrigeration contractors. The expansion tank cover must stay in place and its level monitored; cooling water supply must be shut off even overnight.