Peter Huber Kältemaschinenbau Unichiller P075w
Peter Huber Kältemaschinenbau Unichiller P075w — Recirculating chillers.
The Unichiller P075w is a water-cooled recirculating chiller with a 400 V three-phase supply, designed for externally closed circuits and rated for -20 to 40 °C. Its 'P' designation marks it for high-pressure-drop applications, and the E2 pump delivers up to 130 l/min at 5.7 bar. It serves as a central cooling source for process loops requiring stable temperature control under significant hydraulic resistance.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P075w Current | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Expansion volume | 48 l |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E2 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 301 kg |
| Current consumption | 10 A |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 240 l/h (cooling water at 15°C, flow -20°C) cooling water at 15°C, flow -10°C: 270 l/h · cooling water at 15°C, flow 0°C: 330 l/h |
| Cooling Water Pressure | 6 bar |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and Series Positioning
The Unichiller P075w is a free-standing, water-cooled recirculating chiller in the Unichiller series. Unlike the air-cooled 030T/030Tw siblings (69/61 dB(A)), this model uses a cooling water circuit with G1/2 male connections and requires a site supply of 5–20 °C water at 0.5–6 bar differential pressure. The 'P' in the model name specifically denotes suitability for applications with high pressure drop, distinguishing it from standard variants. The refrigerant is R-449A (GWP 1397, charge 0.95 kg, 1.3 t CO2e), and the unit is classified I/NFL per DIN 12876 for externally closed applications.
Hydraulic and Thermal Behavior
The E2 pump is fixed-speed (not adjustable) and delivers up to 130 l/min at a maximum 5.7 bar, but flow falls sharply as external pressure drop rises—system resistance must be checked against the pump curve. Cooling water consumption depends on the required flow temperature: 330 l/h at 0 °C, 270 l/h at -10 °C, and 240 l/h at -20 °C, all referenced to 15 °C cooling water. Warmer cooling water reduces cooling capacity and may increase the required flow rate. The unit has a 48 l expansion volume and requires a minimum fill of 18 l; the external loop must be closed and sized accordingly.
Installation, Control and Operation
The Pilot ONE controller provides Ethernet, USB (host and device) and RS232 interfaces, plus a Pt100 external sensor connection. Power-failure response is configurable (OFF/Standby, ON, or Power Failure Auto), and Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached—critical for exothermic processes. The unit is IP20 and must be installed indoors in a dry environment at 5–40 °C ambient, with at least 300 lx illuminance and a wall clearance of 50–200 cm per side for maintenance. Leveling feet or parking brakes must be engaged before startup, and cooling water must be shut off even for overnight downtimes.
Integration & Operating Notes
The 400 V 3~ 50 Hz supply requires a 3x10 A fuse or breaker, and the unit is delivered with a cable but without a plug for currents below 63 A. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not permitted—verify site power quality before commissioning.
Inlet water below 5 °C or above 20 °C is outside the design envelope; pressure below 0.5 bar risks insufficient flow, while above 6 bar may damage the circuit. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water without aggressive additives may be used. Insulate pipes where condensation can form.
The unit is designed only for externally closed applications; open baths or unsealed loops are not permitted. The E2 pump delivers up to 130 l/min at 5.7 bar, but flow drops sharply at high pressure, so calculate the external circuit pressure drop to ensure the required flow is achievable. Minimum fill volume is 18 l and expansion volume is 48 l.
Selection & Integration Q&A
Choose the P075w when the process loop has high pressure drop (the 'P' designation) and a cooling water supply is available. The air-cooled 030T/030Tw are simpler to install but have lower pump pressure capability and produce 61–69 dB(A) noise; the P075w is water-cooled and requires 5–20 °C cooling water at 0.5–6 bar.
Cooling water: 5–20 °C inlet, 0.5–6 bar differential, G1/2 male connection, compatible with copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Process loop: externally closed only, minimum fill 18 l, expansion volume 48 l, pump connection G1 1/4 AG male, and pressure drop must be checked against the E2 pump curve (max 130 l/min at 5.7 bar).
Refrigerant circuit work must be done by approved contractors; shut off cooling water even overnight. The unit is delivered with a cable but without a plug (for <63 A), so a suitable plug must be provided on site. No external Pt100 sensor is included unless specified; the Pilot ONE interfaces (Ethernet, USB, RS232) are built-in. Regular maintenance includes checking cooling water quality and pipe insulation.