Peter Huber Kältemaschinenbau Unichiller 050-H
Peter Huber Kältemaschinenbau Unichiller 050-H — Recirculating chillers with Noise level 62 dB.
The Unichiller 050-H is a floor-standing recirculating chiller with a 5 kW cooling capacity at 20 °C, a -20 to 100 °C working range, and a 2 kW heater, positioned above the 030/040 siblings in the series. Its E1 pump delivers 48 l/min at zero head and 11 l/min at 3.0 bar through G1 1/4 male connections, serving externally closed process loops.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 050-H Current | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100 | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Noise level | 62 dB(A) |
| Expansion volume | 48 l |
| Heating capacity | 2 kW |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E1 |
| External sensor connection | Pt100 |
| Temperature range | -20...100 °C |
| Weight | 268 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The 050-H is the largest model in the provided sibling set (030T, 030Tw, 030Tw-H, 040T), with a 268 kg net weight and 740×1160×1165 mm footprint.
- Unlike the 'T' siblings, this model carries the 'H' suffix and a 2 kW heating capacity, extending its range to 100 °C for hot-process loops.
- The unit uses the Pilot ONE controller and is classified to DIN 12876 as safety class III / FL, indicating suitability for flammable thermal fluids.
Performance and media behavior
- Cooling capacity is 5 kW at 20 °C but falls to 1.8 kW at -20 °C; the datasheet notes output is valid at 20 °C room temperature and drops as ambient rises.
- The E1 pump is not speed-adjustable; its curve falls from 48 l/min at zero head to 11 l/min at 3.0 bar, so loop pressure drop must be checked against this curve.
- The unit is designed only for externally closed applications; minimum fill is 18 l with a 48 l expansion volume.
Installation and operation
- Requires a 400 V 3~ 50 Hz supply with 3×16 A fusing; three-phase devices below 63 A are delivered with cable but without a plug.
- IP20 protection and a 5–40 °C ambient limit restrict it to indoor, dry plant rooms with at least 300 lx illuminance and up to 2000 m altitude.
- The Pilot ONE offers Ethernet, USB (Host and Device) and RS232 interfaces, plus a configurable power-failure response (OFF/Standby, ON, or Power Failure Auto).
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access to the refrigeration circuit and pump. Verify floor loading for the 268 kg unit and confirm doorway clearance for the 740×1160×1165 mm cabinet before delivery.
The unit is supplied with a cable but without a plug because it is a three-phase device below 63 A. The installer must provide a matching 3×16 A protected supply and fit the site plug; the IP20 enclosure also means the connection point must be protected from liquid ingress.
The E1 pump delivers 48 l/min at zero head but only 11 l/min at 3.0 bar. Because the pump speed is not adjustable, the external circuit's pressure drop at the required flow must be plotted against this curve; a high-resistance loop will reduce flow below the process requirement.
The Pilot ONE power-failure response can be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles; the appropriate mode must be selected during commissioning.
The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. The IP20 rating and 5–40 °C ambient limit rule out washdown areas and hot plant rooms; cooling capacity is quoted at 20 °C room temperature and drops as ambient rises.
Selection & Integration Q&A
Choose the 050-H when you need heating to 100 °C (2 kW heater) and the higher 5 kW cooling capacity at 20 °C. The 030/040T siblings lack the H suffix and heater; select them only for cooling-only duty within their smaller capacity.
Hoses and fittings must match the G1 1/4 male pump connection, and the external loop must be closed with 18–48 l volume. The electrical feed requires a 400 V 3~ 50 Hz supply with 3×16 A fusing and a site-fitted plug, since the unit ships with cable but no plug.
Install indoors only, at 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, with 50–200 cm side clearance for maintenance. Activate leveling feet or parking brakes before start-up, and shut off cooling water even for overnight downtimes.
Refrigerant circuit work must be done by approved refrigeration contractors; R-449A leak checks and CO2-equivalent records apply. The base delivery excludes the site plug and external hoses/fittings; the Pilot ONE interfaces (Ethernet, USB, RS232) are built in.