Peter Huber Kältemaschinenbau Unichiller P100
Peter Huber Kältemaschinenbau Unichiller P100 — Recirculating chillers.
The Unichiller P100 is an air-cooled recirculating chiller with a pressure pump (E2, non-variable speed) and Pilot ONE controller, rated for -20 to 40 °C and 460 V three-phase 60 Hz supply. Its 'P' designation targets externally closed loops with high pressure drop, distinguishing it from the 030T/040T siblings. It serves as a central cooling source for process equipment requiring stable temperature control within its capacity envelope.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Pump connection | Pump type | Safety class | Temperature range, °C | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P100 Current | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller 030T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 460V 3~ 60Hz |
| Unichiller 030Tw | 61 | G3/4 AG male | B | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 040T | 69 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040T-H | 69 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 040Tw | 70 | G3/4 AG male | B | I / NFL | -10–40 | 400V 3~ 50Hz |
| Unichiller 040Tw-H | 70 | G3/4 AG male | B | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 050-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 050w-H | 62 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 055T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 055T-H | 74 | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 055Tw | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 060T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 060Tw-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 070T-H | 66 | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 070Tw-H | — | G1 1/4 AG male | C3 | III / FL | -10–100 | 400V 3~ 50Hz |
| Unichiller 075w | — | G1 1/4 AG male | E1 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 075w-H | — | G1 1/4 AG male | E1 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100-H | 58 | G1 1/4 AG male | E1 | III / FL | -20–100 | 460V 3~ 60Hz |
| Unichiller 100T | — | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller 100T-H | — | G1 1/4 AG male | C3 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller 100Tw | 65 | G1 1/4 AG male | C3 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller GL 035w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 050w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075 | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 075w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz |
| Unichiller GL 100w | — | G1 1/4 AG male | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050 | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w | 62 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P050w-H | 62 | G1 1/4 AG male | E2 | III / FL | -20–100 | — |
| Unichiller P075 | 61 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w | — | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P075w-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100-H | — | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
| Unichiller P100w | 58 | G1 1/4 AG male | E2 | I / NFL | -20–40 | 400V 3~ 50Hz |
| Unichiller P100w-H | 58 | G1 1/4 AG male | E2 | III / FL | -20–100 | 400V 3~ 50Hz |
Full specifications
| Expansion volume | 48 l |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E2 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The P100 is a free-standing, air-cooled chiller with an atmospheric open expansion tank (48 l) and a minimum fill volume of 18 l. The pump connection is G1 1/4 male, and the pump is a fixed-speed E2 type (no speed adjustment).
- Within the Unichiller series, the 'P' in the model name denotes suitability for applications with high pressure drop, whereas the sibling 030T/030Tw/040T models are not specifically designated for such duty. The P100 is therefore selected when the external circuit imposes significant resistance.
- The controller is the Pilot ONE, offering Ethernet, USB (host and device), and RS232 interfaces, plus a Pt100 external sensor connection. Protection rating is IP20, and safety class is I / NFL per DIN 12876.
Performance and load behavior
- The operating temperature range is -20 to 40 °C. Cooling capacity is 10 kW at +20 °C, 8.7 kW at 0 °C, 5.8 kW at -10 °C, and 4 kW at -20 °C, so sizing must use the coldest operating point.
- Capacity data are valid at 20 °C room temperature; higher ambient reduces achievable cooling. The unit is air-cooled and requires adequate airflow and space per the datasheet.
- The refrigerant is R-449A (A1, H280) with GWP 1397, which triggers F-gas reporting and ventilation considerations.
Installation, control and operation
- The unit requires a 460 V three-phase 60 Hz supply with voltage tolerance ±5 % and frequency tolerance ±2 %, not combined unfavorably. External branch circuit protection per UL 489 is mandatory. Three-phase devices below 63 A are delivered with cable but without plug.
- Installation must be indoors, at least 300 lx illuminance, up to 2000 m altitude, and not in an ATEX zone. Minimum ambient temperature is 5 °C. Wall clearance of 50 to 200 cm per side is required for maintenance.
- The Pilot ONE allows configuration of power-failure response (OFF/Standby, ON, or Power Failure Auto) and a Process Safety mode that releases maximum cooling on overtemperature trigger instead of switching off. Refrigerant circuit work must be by approved contractors.
Integration & Operating Notes
Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow maintenance and ensure adequate air flow for the air-cooled condenser. Insufficient clearance can lead to reduced cooling capacity and service difficulty.
The unit requires external branch circuit protection according to UL 489. The three-phase supply (460 V, 60 Hz) is delivered with cable but without a plug, so a matching plug must be provided on site. Voltage and frequency tolerances are ±5 % and ±2 %, not to be combined unfavorably.
The P100 is designed for externally closed applications and is particularly suitable for high pressure drop loops due to the 'P' designation. Open-loop or low-pressure-drop processes may be better served by sibling models without the 'P' suffix.
Cooling capacity falls from 10 kW at +20 °C to 4 kW at -20 °C. The process load must not exceed the capacity at the minimum required temperature. Ambient temperatures above 20 °C further reduce capacity, so the actual installation room temperature must be considered.
The Pilot ONE controller allows selection of power-failure behavior (OFF/Standby, ON, or Power Failure Auto). For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached, preventing runaway. This must be configured according to the process risk assessment.
Any work on the refrigerant circuit must be performed by approved refrigeration/air-conditioning system contractors. The refrigerant R-449A has a GWP of 1397, so F-gas regulations apply. The expansion tank is atmospheric open and must be kept covered and checked periodically.
Selection & Integration Q&A
Choose the P100 when the external circuit has high pressure drop, as indicated by the 'P' in the model name. The 030T/040T are not specifically designated for high pressure drop. Also consider the P100's -20 to 40 °C range and 10 kW cooling capacity at +20 °C; select a sibling if those limits are not required.
The pump connection is G1 1/4 male, so hoses and fittings must match this thread. The circuit must be externally closed. Maximum tightening torques for pump connections must not be exceeded, and connections must be counterheld during installation.
Install indoors only, at 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, and not in an ATEX zone. Maintain 50–200 cm side clearance. The unit is IP20, so keep it dry and protected from dust. Air-cooled operation requires adequate ventilation.
The base delivery includes a cable but no plug; a suitable 460 V three-phase plug must be provided. External branch circuit protection per UL 489 is required. Refrigerant circuit work must be by approved contractors. The expansion tank must be kept covered and checked. No other accessories are specified in the provided documents.