Peter Huber Kältemaschinenbau Unichiller 055T-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 055T-H

Peter Huber Kältemaschinenbau Unichiller 055T-H — Recirculating chillers with Noise level 74 dB.

The Unichiller 055T-H is an air-cooled recirculating chiller for externally closed loops, rated -20 to 100 °C with 5.5 kW cooling at 15 °C and 2 kW heating. Its C3 pump and G1 1/4 male connections distinguish it within the 030T/040T series, serving process cooling where load varies with temperature.

Noise level
74 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBPump connectionPump typeSafety classTemperature range, °CPower supply
Unichiller 055T-H Current 74G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 030T 69G3/4 AG maleBI / NFL-10–40460V 3~ 60Hz
Unichiller 030Tw 61G3/4 AG maleBI / NFL-20–40400V 3~ 50Hz
Unichiller 040T 69G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040T-H 69G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 040Tw 70G3/4 AG maleBI / NFL-10–40400V 3~ 50Hz
Unichiller 040Tw-H 70G3/4 AG maleBIII / FL-10–100400V 3~ 50Hz
Unichiller 050-H 62G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 050w-H 62G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 055T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 055Tw —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 060T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 060Tw-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 070T-H 66G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 070Tw-H —G1 1/4 AG maleC3III / FL-10–100400V 3~ 50Hz
Unichiller 075w —G1 1/4 AG maleE1I / NFL-20–40400V 3~ 50Hz
Unichiller 075w-H —G1 1/4 AG maleE1III / FL-20–100400V 3~ 50Hz
Unichiller 100-H 58G1 1/4 AG maleE1III / FL-20–100460V 3~ 60Hz
Unichiller 100T —G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller 100T-H —G1 1/4 AG maleC3III / FL-20–100400V 3~ 50Hz
Unichiller 100Tw 65G1 1/4 AG maleC3I / NFL-20–40400V 3~ 50Hz
Unichiller GL 035w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 050w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075 —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 075w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40460V 3~ 60Hz
Unichiller GL 100w —G1 1/4 AG malePressure pump, speed notI / NFL-20–40400V 3~ 50Hz
Unichiller P050 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w 62G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P050w-H 62G1 1/4 AG maleE2III / FL-20–100—
Unichiller P075 61G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w —G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P075w-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100 —G1 1/4 AG maleE2I / NFL-20–40460V 3~ 60Hz
Unichiller P100-H —G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz
Unichiller P100w 58G1 1/4 AG maleE2I / NFL-20–40400V 3~ 50Hz
Unichiller P100w-H 58G1 1/4 AG maleE2III / FL-20–100400V 3~ 50Hz

Full specifications

Core Performance & Functional Specifications
Noise level 74 dB(A)
Heating capacity 2 kW
Minimum fill volume 5 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 283 kg
Electrical, Power & Drive Specifications
Current consumption 12 A
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, connection and control

Integration & Operating Notes

Process Limits
Closed external circuit only; no open bath

The chiller is designed exclusively for externally closed applications, so the user loop must be sealed and able to withstand the pump pressure. Open vessels or baths are not permitted and would invalidate the intended use.

Unichiller 055T-H Datasheet, Product Overview; Unichiller Operation Manual, Selection
Electrical
Provide a 3x16 A fused supply and a site plug

The unit draws 12 A from a 400 V 3~ 50 Hz supply and requires a 3x16 A fuse. Three-phase devices below 63 A are delivered with cable but without a plug, so the installer must provide a suitable plug and verify voltage/frequency tolerances (±5% / ±2%, not all combinations allowed).

Unichiller 055T-H Datasheet, Technical Specifications
Mounting
Keep 50–200 cm clearance per side and secure the feet

A wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. Before start-up, activate parking brakes and/or unscrew leveling feet to prevent movement. The unit weighs 283 kg and measures 640x937x1606 mm, so floor loading and handling equipment must be planned.

Unichiller Operation Manual, Installation; Unichiller 055T-H Datasheet, Technical Specifications
Environment
Indoor use only, 5–40 °C ambient, no ATEX zone

The unit must not be installed in an ATEX zone because it is not explosion-protected. It is for indoor use at illuminance of at least 300 lx and up to 2000 m altitude. Ambient temperature must stay within 5–40 °C; above 20 °C cooling capacity may drop. IP20 requires protection from water and dust.

Unichiller Operation Manual, Installation; Unichiller 055T-H Datasheet, Technical Specifications
Cooling & Media
Account for R-290 charge and room volume

The refrigerant is R-290 (A3, H220), a flammable natural refrigerant. At installation, check the refrigerant charge on the rating plate against room size to avoid exceeding the limit per m³ of ambient air. Work on the refrigerant circuit must be performed only by approved refrigeration/air-conditioning contractors.

Unichiller 055T-H Datasheet, Product Overview; Unichiller Operation Manual, Installation and Maintenance
Operation
Configure power-failure response for your process

The Pilot ONE allows the power-failure response to be set as OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles; choose the mode that matches the risk of the process.

Unichiller Operation Manual, Normal Operation and Safety

Selection & Integration Q&A

When should I choose the Unichiller 055T-H instead of the 030T or 030Tw variants?

Choose the 055T-H when you need higher cooling capacity (5.5 kW at 15 °C) and heating up to 2 kW over -20 to 100 °C. The 030T/030Tw siblings are smaller-capacity units; the 030Tw variants are quieter (61 dB(A)) but not a substitute for the 055T-H's capacity.

What electrical supply and protection must I provide for this chiller?

A 400 V 3~ 50 Hz supply with a 3x16 A fuse; current consumption is 12 A. The unit comes with cable but no plug (three-phase below 63 A), so provide a suitable plug. Verify voltage/frequency tolerances of ±5% / ±2%, noting not all combinations are allowed.

What are the installation and ambient limits I must respect?

Install indoors only, at 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, and not in an ATEX zone. Keep 50–200 cm clearance per side for maintenance, secure leveling feet/parking brakes, and protect from water/dust (IP20). Cooling capacity may drop above 20 °C ambient.

What maintenance and consumables are required, and what is not included?

Refrigerant circuit work must be done by approved contractors; check R-290 charge against room volume. The base delivery excludes a power plug and process hoses/fittings for the G1 1/4 male connections; minimum fill is 5 l with 7.5 l expansion volume.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 055T-H Datasheet
Datasheet ·30,5 КБ ·2 pp.
View PDF