Peter Huber Kältemaschinenbau Unichiller 022-H
Peter Huber Kältemaschinenbau Unichiller 022-H — Recirculating chillers with Noise level 65 dB.
The Unichiller 022-H is a single-phase, air-cooled recirculating chiller with an immersion pump and Pilot ONE controller, covering -10 to 100 °C. Within the Unichiller series it is the 2.2 kW-class model, distinguished from the 015 siblings by higher cooling capacity and 65 dB(A) noise. It serves externally closed process loops requiring up to 29 l/min at 1 bar.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 022-H Current | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 65 dB(A) |
| Maximum delivery flow rate | 29 l/min (1 bar) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | Yes |
| Pump type | Immersion pump |
| External sensor connection | Pt100 |
| Temperature range | -10...100 °C |
| Weight | 77 kg |
| Current consumption | 13 A |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 1 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Air-cooled refrigeration circuit using R-449A (0.58 kg, 0.8 t CO2e), IP20 enclosure, 77 kg, free-standing with casters/leveling feet.
- Immersion pump with G3/4 AG male connections and adjustable speed; delivers 29 l/min at 1 bar, 21 l/min at 0.5 bar.
- Compared with the Unichiller 015/015-H siblings (63 dB(A)), the 022-H is the larger-capacity modification at 65 dB(A); the '-H' suffix denotes this hydraulic/refrigerant configuration within the series.
- Intended only for externally closed applications; models with 'P' in the name are the choice for high pressure-drop loops, not this unit.
Behavior under load and media
- Cooling capacity is rated at 20 °C ambient: 2.2 kW at 15 °C, 1.6 kW at 0 °C, 1 kW at -10 °C; capacity falls as ambient temperature rises, so size for actual room conditions.
- Temperature range -10 to 100 °C; for operation near or below 0 °C, mix water with glysantine or ethylene glycol for freeze protection.
- The plastic pump is not resistant to acetone or polyglycols; avoid these fluids or specify a more resistant pump.
- Safety class III/FL per DIN 12876, with classification depending on whether the thermal fluid is combustible.
Installation, control and operation
- Requires 220–240 V 1~ 50 Hz, max. 13 A, 16 A fuse; voltage and frequency tolerances must be met simultaneously (-5% voltage with +2% frequency is not allowed). Delivered with country-specific plug, to be specified at ordering.
- Pilot ONE controller with Ethernet, USB host/device and RS232; external Pt100 sensor connection; display resolution 0.1 K.
- Power-failure response configurable as OFF/Standby, ON, or Power Failure Auto; Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off.
- Indoor use only, 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude; 50–200 cm wall clearance per side for maintenance.
Integration & Operating Notes
Free-standing installation requires 50 to 200 cm wall clearance on either side for maintenance access, and air-cooled heat rejection needs the space around the unit respected per operating conditions. Before switching on, activate parking brakes at the casters and/or unscrew the leveling feet so the unit cannot move.
The unit needs 220–240 V 1~ 50 Hz with a 16 A fuse and draws up to 13 A. Voltage and frequency tolerances must be satisfied simultaneously; a combination of -5% voltage and +2% frequency is not permitted. Specify the country-specific plug at ordering to avoid rework.
The chiller is designed for externally closed applications only. The plastic immersion pump is not resistant to acetone or polyglycols (depending on manufacturer), so these fluids must be avoided or a more resistant pump specified. For freeze protection below 0 °C, mix water with glysantine or ethylene glycol.
Power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles, preventing runaway temperatures.
Any work on the coolant/refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit contains 0.58 kg R-449A (GWP 1397, 0.8 t CO2e), which governs leak-check intervals and refrigerant accounting.
IP20 offers no water protection, so the unit must be installed in a dry location protected from water ingress; electrical lines directly below a water-cooled unit must be protected against condensate. Ambient must stay 5–40 °C, illuminance at least 300 lx, altitude up to 2000 m, and no ATEX zone.
Selection & Integration Q&A
Pick the 022-H when the heat load requires the 2.2 kW class (2.2 kW at 15 °C, 1.6 kW at 0 °C, 1 kW at -10 °C at 20 °C ambient). The 015 siblings are lower-capacity (63 dB(A) vs 65 dB(A)). For high pressure-drop loops, a 'P' model is the correct choice, not this unit.
Provide 220–240 V 1~ 50 Hz with a 16 A fuse; the unit draws up to 13 A. Voltage and frequency tolerances must be met simultaneously (-5% voltage with +2% frequency is not allowed). A country-specific plug is supplied only if specified at ordering.
No. The unit is IP20 and must be installed indoors in a dry location protected from water ingress, at 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, and never inside an ATEX zone. Allow 50–200 cm wall clearance per side for maintenance.
Refrigerant-circuit work must be done by approved refrigeration contractors; the unit holds 0.58 kg R-449A (0.8 t CO2e). For sub-zero operation, glysantine or ethylene glycol must be added to the water by the user. The country-specific power plug must be specified at ordering; no cables or accessories beyond that are stated.