Peter Huber Kältemaschinenbau Unichiller P015
Peter Huber Kältemaschinenbau Unichiller P015 — Recirculating chillers with Noise level 63 dB.
The Unichiller P015 is a recirculating chiller with a 'P' designation for high-pressure-drop applications, operating from -20 to +40 °C using R-290 refrigerant. It delivers 1.5 kW at +15 °C but only 0.3 kW at -20 °C, distinguishing it from standard 015 siblings. It serves externally closed industrial cooling loops requiring elevated pump pressure.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P015 Current | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 63 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 61 kg |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~/2~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Refrigerant | R-290 (A3, H220) (1st stage) |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and Series Positioning
The Unichiller P015 is a free-standing recirculating chiller in the Unichiller series (up to 25 kW class). Its 'P' suffix explicitly denotes suitability for applications requiring high pressure drops, per the operation manual. Unlike the standard Unichiller 015, 015-H, or OLÉ variants, the P015 is configured with a pump delivering up to 2.5 bar and 25 l/min, making it the choice for restrictive circuits. The unit uses a plastic pump (type B, non-adjustable speed) with G3/4 male connections and a minimum filling capacity of 3.8 l. Refrigerant is R-290 (A3, H220) with a charge of only 0.16 kg (GWP 0.02).
Thermal Performance and Load Behavior
Cooling capacity is strongly temperature-dependent: 1.5 kW at +15 °C, 1.0 kW at 0 °C, 0.7 kW at -10 °C, and 0.3 kW at -20 °C, all rated at 20 °C room temperature. Capacity may fall if ambient temperature rises above 20 °C. The temperature range is -20 to +40 °C. For freeze protection below 0 °C, water must be mixed with glysantine or ethylene glycol. The plastic pump is not resistant to acetone or polyglycols, so these fluids require a different pump option.
Control, Installation, and Operation
The Pilot ONE controller provides Ethernet, USB (host and device), and RS232 interfaces, plus a Pt100 external sensor connection. Electrical supply is 220–240 V, 1~/2~, 50 Hz, with max current 8.5 A and a 16 A fuse. Voltage and frequency tolerances are ±5% and ±2% but must not be combined unfavorably. Single/two-phase units ship with a country-specific plug (must be specified at order). The unit is IP20, EMC Class A Group 1 (industrial environments only), and must be installed indoors at 5–40 °C ambient, at least 300 lx illuminance, and below 2000 m altitude. A wall clearance of 50–200 cm per side is required for maintenance. Leveling feet or parking brakes must be engaged before operation. The power-failure response is configurable (OFF/Standby, ON, or Power Failure Auto). Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, rather than switching off all poles.
Integration & Operating Notes
Sizing on nominal capacity will undersize the unit at low temperatures: capacity drops from 1.5 kW at +15 °C to 0.3 kW at -20 °C. The required load must be checked at the actual operating temperature, and ambient above 20 °C further reduces available cooling.
Voltage tolerance is ±5% and frequency tolerance ±2%, but the manual explicitly forbids combining -5% voltage with +2% frequency. Verify supply quality before commissioning to avoid compressor and pump damage and warranty voidance.
R-290 is flammable (A3). The refrigerant charge (0.16 kg) and room volume must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air. The unit must not be installed in an ATEX zone.
Install indoors only, at 5–40 °C ambient, at least 300 lx illuminance, and below 2000 m altitude. A wall clearance of 50–200 cm per side is required for maintenance access. Leveling feet or parking brakes must be engaged before start-up.
The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For freeze protection below 0 °C, mix water with glysantine or ethylene glycol. Minimum filling capacity is 3.8 l; pump connections are G3/4 male and must be counterheld at maximum torque.
The Pilot ONE allows power-failure response as OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles. Select the mode that matches the process risk.
Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning contractors. The small A3 charge (0.16 kg) still requires leak-check and service procedures consistent with flammable refrigerant regulations.
Single/two-phase devices (100–240 V) are supplied with a power cable and country-specific plug that must be specified when ordering. Three-phase devices below 63 A come without a plug. Missing specification delays commissioning.
Selection & Integration Q&A
Choose the P015 when the process loop has high pressure drop: the 'P' model provides up to 2.5 bar and 25 l/min, while standard 015 variants target lower-resistance circuits. The 015-H adds a heater; the P015 is cooling-only. Select the P015 for restrictive cooling loops without heating demand.
The pump connection is G3/4 male; hoses must be counterheld and torques not exceeded. Minimum filling capacity is 3.8 l. Electrical supply is 220–240 V, 1~/2~, 50 Hz, 8.5 A max, 16 A fuse, with a country-specific plug specified at order. Voltage/frequency tolerances must not combine unfavorably.
Install indoors at 5–40 °C ambient, at least 300 lx, below 2000 m altitude, with 50–200 cm wall clearance per side. IP20 and EMC Class A mean industrial environments only. A3 refrigerant requires room-volume assessment. Leveling feet or parking brakes must be engaged before operation.
Refrigerant circuit work requires approved contractors. Freeze protection requires glysantine or ethylene glycol; acetone and polyglycols are incompatible with the plastic pump. A country-specific plug must be specified at order. Hoses, expansion volume, and external Pt100 sensor are not included and must be planned separately.