Peter Huber Kältemaschinenbau Unichiller P010w
Peter Huber Kältemaschinenbau Unichiller P010w — Recirculating chillers.
The Unichiller P010w is a water-cooled recirculating chiller with a plastic pump (type B) and Pilot ONE controller, covering -20 to +40 °C. Its 'P' designation marks it for high-pressure-drop, externally closed loops. It delivers up to 1 kW cooling at +15 °C, falling to 0.15 kW at -20 °C, for process cooling with site water at 5–20 °C.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P010w Current | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 57 kg |
| Power supply | 220-240V 1~/2~ 50/60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The P010w is a water-cooled chiller with a non-adjustable plastic pump (type B) and G3/4 male pump connections; cooling water connects via G1/2 male threads.
- Within the Unichiller line, the 'P' in the model name denotes suitability for applications requiring high pressure drops, distinguishing it from sibling models such as the Unichiller 015 variants.
- The unit is intended exclusively for externally closed applications and is not explosion-protected (no ATEX zone installation).
Thermal behavior and media
- Cooling capacity is strongly temperature-dependent: 1 kW at +15 °C, dropping to 0.15 kW at -20 °C (at +20 °C ambient).
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol.
- Minimum filling capacity is 3.8 L with 1.7 L expansion volume; the refrigerant is R-449A (A1, H280).
Installation, control and operation
- The Pilot ONE controller provides Ethernet, USB (host and device) and RS232 interfaces, plus a Pt100 external sensor connection.
- Power-failure response is configurable (OFF/Standby, ON, Power Failure Auto); Process Safety mode releases maximum cooling on overtemperature trigger.
- Installation requires 50–200 cm wall clearance per side, indoor use at ≥300 lx, and protection of electrical lines below the unit against condensate.
Integration & Operating Notes
The site water supply must provide a differential pressure of at least 1 bar and no more than 6 bar. Insufficient pressure prevents proper operation, while excessive pressure can damage the unit. Verify the supply before installation.
The supply must meet ±5% voltage with a simultaneous ±2% frequency tolerance. Opposite-sign deviations (e.g., high voltage with low frequency) are not allowed, as they stress the motor and electronics.
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access. The unit must be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude.
Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation. This is a mandatory installation measure to avoid electrical shock hazard.
The cooling water supply must be shut off even for shorter downtimes such as overnight to prevent water damage and corrosion during idle periods.
The Pilot ONE allows the power-failure response to be set as OFF/Standby, ON, or Power Failure Auto. This determines whether the process restarts automatically after a power outage, which is critical for unattended operation.
In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature protection trigger value is reached, instead of switching off all poles. This is essential for exothermic processes where cutting cooling could cause runaway temperatures.
Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant R-449A is stored under pressure (H280).
Selection & Integration Q&A
Choose the P010w when your process loop has high pressure drop, as indicated by the 'P' in the model name. The 015 variants are general-purpose; the P010w is specifically suited for high-pressure-drop applications and offers a -20 to +40 °C range with up to 1 kW cooling at +15 °C.
Cooling water must be 5–20 °C with a differential pressure of 1–6 bar, connected via G1/2 male threads. The pump connections are G3/4 male; matching hose couplings must be provided, and maximum tightening torques must not be exceeded.
The base delivery excludes heat transfer fluid; a minimum of 3.8 L is required, with freeze protection using glysantine or ethylene glycol. Refrigerant circuit service must be by approved contractors. No specific maintenance intervals are given in the provided documents.