Peter Huber Kältemaschinenbau Unichiller P012w-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P012w-H

Peter Huber Kältemaschinenbau Unichiller P012w-H — Recirculating chillers.

The Unichiller P012w-H is a water-cooled recirculating chiller with a plastic pump (type B, non-adjustable) and Pilot ONE controller, covering -20 to 100 °C. Its 'P' designation suits process loops with high pressure drop, and the water-cooled condenser requires 5–20 °C cooling water at 1–6 bar. It serves externally closed circuits as a central cooling source.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P012w-H Current —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -20...100 °C
Electrical, Power & Drive Specifications
Power supply 220-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 48 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 57 l/h · at 15°C, flow 15°C: 60 l/h
Cooling water differential pressure 1 bar
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior and media

Installation, control and operation

Integration & Operating Notes

Cooling & Media
Cooling water must deliver at least 1 bar differential pressure

The water-cooled condenser needs a minimum differential pressure of 1 bar between inlet and outlet; insufficient pressure impairs cooling performance. Supply pressure must not exceed 6 bar, and intake temperature must stay within 5–20 °C.

Unichiller P012w-H Datasheet, page 1–2
Process Limits
Plastic pump excludes acetone and polyglycols from the circuit

The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). Use water with glysantine or ethylene glycol for freeze protection; other fluids require compatibility verification before filling.

Unichiller P012w-H Datasheet, page 2
Electrical
Voltage and frequency tolerances are coupled, not independent

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%; the combination of -5% voltage and +2% frequency is explicitly not allowed. Verify site power quality against this envelope before connection.

Unichiller P012w-H Datasheet, page 2
Mounting
Maintain 50–200 cm wall clearance per side for service access

Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance. The unit is for indoor use only, at illuminance of at least 300 lx and up to 2000 m altitude; IP20 requires a dry, protected location.

Unichiller Operation Manual, page 25
Mounting
Protect electrical lines below the unit from condensate

On water-cooled units, electrical lines directly below the temperature control unit must be protected against liquid ingress from condensation. Route cables accordingly or install a drip shield.

Unichiller Operation Manual, page 28
Operation
Shut off cooling water even for overnight downtime

The cooling water supply must be shut off even for shorter downtimes such as overnight, to prevent water damage and corrosion during idle periods.

Unichiller Operation Manual, page 28
Operation
Configure power-failure response before unattended operation

The Pilot ONE allows power-failure response OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work restricted to approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Refrigerant charge and room size must be checked at installation against the limit per m³ of ambient air (R-449A, GWP 1397).

Unichiller Operation Manual, pages 15, 17

Selection & Integration Q&A

When should I choose the P012w-H over the Unichiller 015-series siblings?

Pick the P012w-H when the process loop has high pressure drop (the 'P' designation) and when a water-cooled condenser is acceptable. The 015-series siblings are the alternative when their configuration better matches the site; the P012w-H is specifically suited to high-pressure-drop applications and externally closed circuits.

What cooling-water supply and mating connections does the P012w-H require from adjacent systems?

Cooling water at 5–20 °C, 1–6 bar, with at least 1 bar differential pressure; consumption 48–60 l/h depending on flow temperature. Cooling-water port G1/2 male; pump port G3/4 male. Insulate internal cooling-water pipes if supply is below dew point.

What installation environment and duty limits apply to the P012w-H?

Indoor use only, 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, IP20 dry location, no ATEX zone. Allow 50–200 cm wall clearance per side. Secure leveling feet/parking brakes before start-up; shut off cooling water even overnight.

What maintenance and consumables are required, and what is not included in base delivery?

Refrigerant-circuit work only by approved contractors; check refrigerant charge vs room size. Minimum fluid charge 3.8 l with 1.7 l expansion volume — heat transfer fluid, hoses/fittings for G3/4 and G1/2, and cooling-water supply are not included and must be provided by the site.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P012w-H Datasheet
Datasheet ·126,5 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF