Peter Huber Kältemaschinenbau Unichiller 015w-H OLÉ
Peter Huber Kältemaschinenbau Unichiller 015w-H OLÉ — Recirculating chillers with Noise level 54 dB.
The Unichiller 015w-H OLÉ is a water-cooled recirculating chiller with an immersion pump and OLÉ controller, rated for -20 to 100 °C. It is the water-cooled variant of the 015 series, requiring a cooling water supply of 5–20 °C at ≥1 bar differential pressure. It serves externally closed process loops where heat is rejected to facility cooling water.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 015w-H OLÉ Current | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 54 dB(A) |
| Maximum delivery flow rate | 29 l/min (1 bar) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | Immersion pump |
| Temperature range | -20...100 °C |
| Weight | 63 kg |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 36 l/h (cooling water 15°C, flow -20°C) cooling water 15°C, flow -10°C: 48 l/h · cooling water 15°C, flow 0°C: 60 l/h · cooling water 15°C, flow 15°C: 68 l/h |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Water-cooled condenser (no air-cooled fan), immersion pump with G3/4 AG male pump connection and G1/2 male cooling-water connections.
- OLÉ controller with OLED display, USB (Device) and RS232 interfaces; pump speed is not adjustable.
- Within the 015 series, this is the water-cooled 'w' variant; siblings 015, 015-H, 015-H OLÉ and 015 OLÉ are air-cooled (noise 63 dB(A) vs 54 dB(A) here). The 'H' suffix denotes the high-temperature configuration; the OLÉ controller is shared with 015-H OLÉ and 015 OLÉ.
Behavior under load and media
- Cooling water consumption rises with flow temperature: 36 l/h at -20 °C, 48 l/h at -10 °C, 60 l/h at 0 °C and 68 l/h at 15 °C, all at 15 °C cooling water.
- Cooling power decreases and cooling-water flow rate may increase as cooling-water temperature rises.
- The plastic immersion pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol.
- The unit is designed for externally closed applications only.
Installation, control and operation
- Must not be installed in an ATEX zone; indoor use only, illuminance ≥300 lx, altitude up to 2000 m.
- Wall clearance of 50–200 cm per side for maintenance; leveling feet/parking brakes must be activated before start-up.
- Cooling water supply must be shut off even for short downtimes (e.g. overnight).
- Power-failure response configurable as OFF/Standby, ON or Power Failure Auto; Process Safety mode releases maximum cooling capacity at the OT trigger value.
- Electrical lines directly below the unit must be protected against liquid ingress; cooling-water pipes must be insulated if below condensation point.
Integration & Operating Notes
The manual restricts this chiller to externally closed applications. Designing an open tank or direct immersion circuit violates the intended hydraulic configuration and may cause pump cavitation or overflow.
The datasheet specifies cooling water intake between 5 °C and 20 °C and a minimum differential pressure of 1 bar. Below 1 bar the condenser may not receive adequate flow; above 20 °C cooling capacity drops and flow demand rises.
The immersion pump is plastic and not resistant to acetone or polyglycols. Select an alternative heat-transfer fluid or specify a more resistant pump; otherwise pump damage and leakage can occur.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side. Planning a tighter footprint will block service access to the refrigerant circuit and pump.
Single/two-phase devices are delivered with a power cable and country-specific plug; the plug type must be stated on the order. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and not all combinations are permitted.
The OLÉ controller supports OFF/Standby, ON and Power Failure Auto restart modes. For processes that must not restart automatically after a mains interruption, select OFF/Standby; for exothermic reactions, verify that Process Safety mode is enabled so maximum cooling is released at the OT trigger.
Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. In-house maintenance is limited to non-refrigerant tasks; plan service contracts accordingly.
The cooling water supply must be closed for any downtime, including overnight. Leaving it open risks water damage and corrosion in the cooling circuit during idle periods.
Selection & Integration Q&A
Choose the 015w-H OLÉ when facility cooling water (5–20 °C, ≥1 bar differential) is available and heat rejection to air is undesirable; it is quieter (54 dB(A) vs 63 dB(A)). The air-cooled 015-H OLÉ avoids cooling-water infrastructure and is preferable where water supply or drainage is unavailable.
A cooling-water supply of 5–20 °C with at least 1 bar differential pressure and maximum 6 bar, connected via G1/2 male fittings. Consumption is 36–68 l/h depending on flow temperature. Pipes must be insulated if below condensation point, and electrical lines below the unit protected from liquid ingress.
Indoor use only, 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, and no ATEX zone. Maintain 50–200 cm side clearance for maintenance. Activate leveling feet/parking brakes before start-up. Shut off cooling water for any downtime, including overnight.
Refrigerant-circuit work must be by approved contractors; no user-serviceable refrigerant tasks. The base delivery includes a power cable with country-specific plug (specify at order). The Pt100 sensor connection is a factory-fitted option only, not retrofittable. Freeze protection requires glysantine or ethylene glycol added to water.