Peter Huber Kältemaschinenbau Unichiller P015w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P015w

Peter Huber Kältemaschinenbau Unichiller P015w — Recirculating chillers with Noise level 54 dB.

Water-cooled recirculating chiller with a plastic pump and fixed-speed drive, rated for -20 to 40 °C and built for externally closed circuits with high pressure drop. The 'P' modification trades flow for head (25 l/min max, 6 l/min at 2.0 bar) and runs quieter than the 015 siblings at 54 dB(A). It serves as the cooling stage for closed process loops.

Noise level
54 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P015w Current 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 54 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -20...40 °C
Electrical, Power & Drive Specifications
Power supply 220-240V 1~/2~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 36 l/h (cooling water at 15°C, flow -20°C)
cooling water at 15°C, flow -10°C: 48 l/h · cooling water at 15°C, flow 0°C: 60 l/h · cooling water at 15°C, flow 15°C: 68 l/h
Cooling water differential pressure 1 bar
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Verify site cooling water pressure between 1 and 6 bar

The chiller needs a minimum cooling water differential pressure of 1 bar and tolerates no more than 6 bar. Insufficient pressure prevents proper operation; excessive pressure can damage the water circuit, so a regulator or pressure-reducing valve may be needed upstream.

Unichiller P015w Datasheet, page 1
Cooling & Media
Insulate cooling water pipes if intake drops below dew point

The unit is designed for cooling water intake between 5 and 20 °C. When the cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated to prevent condensation and possible damage.

Unichiller P015w Datasheet, page 2
Process Limits
Do not use acetone or polyglycol with the plastic pump

The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For freeze protection, use a water mixture with glysantine or ethylene glycol instead, and confirm fluid compatibility with the mixed-material water circuit (copper, 1.4401, MS, PA, PPE, PTFE, EPDM).

Unichiller P015w Datasheet, page 2
Electrical
Do not combine -5% voltage with +2% frequency

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination of -5% voltage with +2% frequency is explicitly not allowed. Check the site supply against this combined envelope before commissioning; the unit draws up to 5.5 A and requires a 10-16 A fuse.

Unichiller P015w Datasheet, page 2
Electrical
Specify country-specific plug at order time

Single/two-phase devices (100-240 V) are delivered with a power cable and country-specific plug that must be specified when ordering. Three-phase devices below 63 A come with cable but without plug, so the site must provide a matching receptacle or plug.

Unichiller P015w Datasheet, page 2
Mounting
Keep 50-200 cm clearance per side for maintenance

Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance access. The unit is for indoor use only at illuminance of at least 300 lx and up to 2000 m altitude, and must not be installed or started inside an ATEX zone.

Unichiller Operation Manual, page 25
Mounting
Protect cables below the unit from condensation

Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation. Also observe the refrigerant charge and room size at installation to stay within the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, page 28
Operation
Shut off cooling water even for overnight downtime

Close the cooling water supply to the unit even for shorter downtimes such as overnight to prevent water damage and corrosion. Before switching on, extend the leveling feet and apply caster parking brakes so the unit cannot move during operation.

Unichiller Operation Manual, pages 28 and 31
Control & I/O
Configure power-failure response for the process

The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON or Power Failure Auto. Choose according to whether the process must restart automatically after a power outage or remain stopped for manual intervention.

Unichiller Operation Manual, page 19
Control & I/O
Use Process Safety mode for exothermic reactions

In Process Safety mode the controller releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. This is critical for exothermic processes where cutting cooling would cause runaway temperatures.

Unichiller Operation Manual, page 18
Maintenance
Refrigerant circuit work only by approved contractors

Work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit uses R-449A with GWP 1397, which also carries regulatory and environmental reporting obligations at the site.

Unichiller Operation Manual, page 17; Datasheet, page 1

Selection & Integration Q&A

When should I choose the P015w instead of the Unichiller 015 or 015-H?

Choose the P015w for closed loops with high pressure drop: the 'P' model is specifically suited to such applications and runs at 54 dB(A) versus 63 dB(A) for the 015, 015-H and OLÉ siblings. The 015 variants suit lower-impedance circuits where their higher flow is usable.

What cooling water supply and piping must the site provide for this water-cooled unit?

Provide cooling water at 5-20 °C intake with differential pressure between 1 and 6 bar, connections G1/2 male. Flow demand at 15 °C water is 36-68 l/h depending on setpoint (-20 to 15 °C). Insulate internal cooling water pipes if intake falls below the condensation point.

What are the installation environment and duty-cycle limits from the manual?

Indoor use only, ambient 5-40 °C, illuminance at least 300 lx, altitude up to 2000 m, IP20, no ATEX zone. Keep 50-200 cm clearance per side, protect cables below the unit from condensation, and shut off cooling water even for overnight downtime.

What is not included in base delivery and what service/accessory items should be planned?

Three-phase units below 63 A ship without a plug; single/two-phase units need the country-specific plug specified at order. Refrigerant circuit service requires approved contractors. Plan a 10-16 A fuse, external Pt100 sensor if needed, and freeze-protection fluid (glysantine or ethylene glycol mix).

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P015w Datasheet
Datasheet ·126,5 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF