Peter Huber Kältemaschinenbau Unichiller P010 OLÉ
Peter Huber Kältemaschinenbau Unichiller P010 OLÉ — Recirculating chillers with Noise level 57 dB.
The Unichiller P010 OLÉ is an air-cooled, CFC/HCFC-free recirculating chiller with a plastic pump and G3/4 male connections, rated for -20 to 40 °C. Its 'P' designation targets high-pressure-drop circuits, where flow falls from 21 l/min at 0.5 bar to 6 l/min at 2.0 bar. It serves closed-loop process cooling with the OLÉ controller and USB/RS232 interfaces.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P010 OLÉ Current | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 57 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -20...40 °C |
| Weight | 59 kg (net) |
| Current consumption | 13 A (max) |
| Fuse rating | 16 A |
| Power supply | 110-120V 1~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
The P010 OLÉ is a single-phase, air-cooled chiller in the Unichiller series, distinguished by the 'P' in its model code, which the manual identifies as particularly suitable for applications requiring high pressure drops. It uses a plastic pump (type B, non-adjustable speed) with G3/4 male connections and is rated IP20. Compared with sibling Unichiller 015 variants (63 dB(A)), this model is quieter at 57 dB(A). The refrigerant is R-449A (A1, H280) with a charge corresponding to 0.4 t CO2 equivalent.
Thermal and hydraulic behavior
Cooling capacity is strongly temperature-dependent: 1 kW at 15 °C, 0.8 kW at 0 °C, 0.5 kW at -10 °C and 0.15 kW at -20 °C, valid at 20 °C room temperature. Pump flow also depends on external pressure drop: 21 l/min at 0.5 bar, 17 l/min at 1.0 bar, 11 l/min at 1.5 bar and 6 l/min at 2.0 bar. The minimum filling capacity is 3.8 l and the expansion tank is 1.7 l. The unit is intended for externally closed applications only.
Installation, control and operation
Electrical supply is 110-120 V single-phase 50/60 Hz, max current 13 A, with a 16 A fuse; voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and combined worst-case deviations are not permitted. The OLÉ controller provides an OLED display with 0.1 K resolution and USB (Device) and RS232 interfaces. The unit must be installed indoors at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. Leveling feet or parking brakes must be secured before start-up. The power-failure response is configurable (OFF/Standby, ON, Power Failure Auto), and Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached.
Integration & Operating Notes
At -20 °C the unit delivers only 0.15 kW, versus 1 kW at 15 °C. Processes requiring sustained low-temperature duty must either reduce heat load or select a larger model; the capacity figures are valid at 20 °C room temperature and drop further if ambient rises.
The pump delivers 21 l/min at 0.5 bar but only 6 l/min at 2.0 bar. The external circuit's pressure drop must be calculated against this curve; if the required flow cannot be met at the circuit's backpressure, undercooling or poor temperature stability will result.
The standard plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). Fluid selection must avoid these media or a more resistant pump must be specified; for freeze protection, water should be mixed with glysantine or ethylene glycol.
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%; combined worst-case deviations are not allowed. The circuit must be sized for 13 A max current and protected with a 16 A fuse. Verify site supply quality before commissioning.
The unit is IP20 and must be installed indoors at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude. A wall clearance of 50–200 cm per side is required for maintenance. It must not be installed or started inside an ATEX zone.
Before the unit is put into operation, parking brakes must be activated at the casters (if any) and/or leveling feet unscrewed/activated. This prevents movement and crushing injuries during operation.
The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (A1, H280) with 0.4 t CO2 equivalent, which may trigger F-gas leak-check and documentation obligations.
Selection & Integration Q&A
Choose the P010 OLÉ for high-pressure-drop circuits (the 'P' designation) and where 57 dB(A) is preferred over the 63 dB(A) of the 015 series. The 015 variants may be considered when higher cooling capacity or different configurations are needed, but verify capacity at your setpoint.
The pump connection is G3/4 male, so hoses and fittings must match this thread. Maximum tightening torques must not be exceeded and connections must be counterheld. The circuit must be externally closed, and the loop volume plus thermal expansion must be checked against the 3.8 l minimum filling capacity and 1.7 l expansion tank.
Install indoors at 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, with 50–200 cm wall clearance per side. Secure leveling feet or parking brakes before start-up. Do not install in an ATEX zone. Cooling capacity is valid at 20 °C room temperature and drops if ambient rises.
Refrigerant circuit work must be done by approved refrigeration contractors. For freeze protection, water should be mixed with glysantine or ethylene glycol; these fluids and hoses/fittings are not included. The plastic pump is not resistant to acetone or polyglycols. No specific service interval is stated in the provided digests.