Peter Huber Kältemaschinenbau Unichiller P007-H OLÉ
Peter Huber Kältemaschinenbau Unichiller P007-H OLÉ — Recirculating chillers with Noise level 58 dB.
The Unichiller P007-H OLÉ is an air-cooled, CFC/HCFC-free recirculating chiller with a plastic pump and G3/4 male connections, rated for -20 to 100 °C. Its 'P' designation targets high-pressure-drop circuits, and the OLÉ controller provides USB and RS232 interfaces. It serves externally closed cooling loops requiring sub-ambient to moderate heating duty.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P007-H OLÉ Current | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 58 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -20...100 °C |
| Weight | 57 kg |
| Current consumption | 14 A |
| Fuse rating | 16 A |
| Power supply | 208-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Air-cooled refrigeration circuit using R-449A (GHS H280, GWP 1397); no CFC or HCFC refrigerants.
- Plastic pump, non-adjustable speed, G3/4 AG male connections; minimum filling capacity 3.8 l with a 1.7 l expansion tank.
- The 'P' in the model name marks this unit as particularly suitable for applications with high pressure drops, distinguishing it from non-P siblings in the Unichiller series.
- OLÉ controller with OLED display, 0.1 K display resolution, USB (Device) and RS232 interfaces.
- IP20 protection, safety class III / FL, 57 kg.
Behavior under load and media
- Operating range -20 to 100 °C. Cooling capacity is 0.7 kW at 15 °C, 0.55 kW at 0 °C, 0.4 kW at -10 °C and 0.2 kW at -20 °C; low-temperature duty therefore requires reduced heat load or a larger unit.
- Capacity figures are quoted at 20 °C room temperature and fall as ambient rises.
- Pump delivers max 25 l/min at max 2.5 bar; flow falls to 6 l/min at 2.0 bar, so high-pressure-drop loops must be checked against the pump curve.
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol rather than used neat.
- Intended only for externally closed applications.
Installation, connection and control
- Supply: 208-240 V 1~/2~ 50/60 Hz, max current 14 A, 16 A fuse. Voltage tolerance ±5% and frequency tolerance ±2% must not combine in the same direction.
- Single/two-phase devices are supplied with a power cable and country-specific plug that must be specified at order.
- EMC Class A, Group 1 to EN55011: intended for industrial environments; may cause interference in residential areas.
- Must not be installed or started up inside an ATEX zone; indoor use only, illuminance at least 300 lx, altitude up to 2000 m.
- Wall clearance of 50 to 200 cm per side required for maintenance on free-standing models; leveling feet must be activated and parking brakes applied before start-up.
- Power-failure response configurable as OFF/Standby, ON, or Power Failure Auto via the Pilot ONE; Process Safety mode releases maximum cooling capacity when the OT trigger value is reached instead of switching off all poles.
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance access. Before switching on, the parking brakes must be activated at the casters and/or the leveling feet unscrewed/activated to prevent movement and crushing injuries.
Voltage tolerance is ±5% and frequency tolerance ±2%, but these must not combine in the same direction. A supply outside these combined limits can damage the compressor. The unit requires a 16 A fuse and draws max 14 A at 208-240 V 1~/2~ 50/60 Hz.
Cooling capacity is quoted at 20 °C room temperature and drops as ambient rises. The unit may only be operated between 5 °C and 40 °C ambient. Air-cooled condensers reject heat to the room, so adequate air flow and ventilation must be provided at the installation site.
The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE controller. For exothermic processes, Process Safety mode releases maximum cooling capacity when the OT trigger value is reached instead of switching off all poles, preventing runaway temperatures.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (GHS H280, GWP 1397); observe the charge amount and room size to avoid exceeding the refrigerant limit per m³ of ambient air.
Single and two-phase devices (100 V to 240 V) are supplied with a power cable and country-specific plug that must be specified when ordering. Missing plug specification leads to a unit that cannot be connected on site.
Selection & Integration Q&A
Choose the P007-H OLÉ for high-pressure-drop circuits (the 'P' designation) and lower noise (58 dB(A) vs 63 dB(A) on 015 models). The 015 series offers higher capacity but is louder; select it when cooling demand exceeds the P007's 0.7 kW at 15 °C.
The pump connection is G3/4 male. Maximum tightening torques must not be exceeded and connections must be counterheld. The pump delivers max 25 l/min at 2.5 bar, falling to 6 l/min at 2.0 bar, so verify your loop's pressure drop against this curve.
Operate only between 5 °C and 40 °C ambient, indoors, at illuminance ≥300 lx and altitude ≤2000 m. Maintain 50–200 cm side clearance. Do not install in an ATEX zone. Cooling capacity derates as ambient rises above 20 °C.
Refrigerant circuit work must be by approved contractors. The power cable and country-specific plug must be specified at order. For freeze protection, glysantine or ethylene glycol is needed. Minimum filling capacity is 3.8 l; expansion tank is 1.7 l.