Peter Huber Kältemaschinenbau Unichiller P022w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P022w

Peter Huber Kältemaschinenbau Unichiller P022w — Recirculating chillers with Noise level 60 dB.

Water-cooled recirculating chiller with a plastic pump and Pilot ONE controller, rated 2.2 kW at 15 °C and 1 kW at -10 °C over a -10…40 °C range. The 'P' designation marks it for externally closed loops with high pressure drop, distinguishing it from the 015 siblings. It serves as a secondary cooling stage for laboratory and process circuits.

Noise level
60 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P022w Current 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -10...40 °C
Dimensions, Weight & Mechanical Design
Weight 67 kg
Electrical, Power & Drive Specifications
Power supply 208-230V 1~/2~ 60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 77 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 96 l/h · at 15°C, flow 15°C: 95 l/h
Cooling water differential pressure 1 bar
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior across the working range

Control, installation and operation

Integration & Operating Notes

Process Limits
Cooling-water supply must sit between 1 and 6 bar differential

Below 1 bar differential pressure the chiller cannot reject heat correctly; above 6 bar the water circuit and connections are at risk. Verify the site supply with a gauge before installation and fit a pressure reducer if the mains can exceed 6 bar.

Unichiller P022w Datasheet, page 1
Cooling & Media
Cooling-water intake limited to 5–20 °C; insulate below dew point

The unit is designed for cooling-water intake between 5 °C and 20 °C. If the water can fall below the condensation point of the surroundings, pipes must be insulated to prevent condensate; electrical lines directly below the unit must be protected against liquid ingress.

Unichiller P022w Datasheet, page 2; Operation Manual, page 28
Process Limits
Plastic pump incompatible with acetone and polyglycols

The standard plastic pump is not resistant to acetone or polyglycols. For these media a more resistant pump must be ordered; otherwise the fluid must be changed. For freeze protection, mix water with glysantine or ethylene glycol rather than using pure water.

Unichiller P022w Datasheet, page 2
Mounting
Indoor installation only, with 50–200 cm clearance per side

The unit is not explosion-protected and must not be installed in an ATEX zone. It is for indoor use at ≥300 lx and ≤2000 m altitude, with 50–200 cm wall clearance on either side for maintenance. Check refrigerant charge against room volume to stay within the limit per m³ of ambient air.

Operation Manual, pages 13, 15, 25
Maintenance
Refrigerant circuit work restricted to approved contractors

Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The R-449A charge of 0.45 kg (0.6 t CO2e) also triggers leak-reporting obligations; keep the rating-plate data available for service and compliance records.

Operation Manual, page 17; Unichiller P022w Datasheet, page 1
Operation
Shut off cooling water even for overnight downtime

Close the cooling-water supply to the unit for any downtime, including overnight, to prevent water damage and corrosion in the circuit. Before start-up, activate parking brakes and/or unscrew the leveling feet so the unit cannot move during operation.

Operation Manual, pages 28, 31

Selection & Integration Q&A

When should I choose the P022w instead of a Unichiller 015 sibling?

Pick the P022w for externally closed loops with high pressure drop, where the 'P' pump curve (25 l/min, 2.5 bar max) is needed. The 015 variants are the other series configurations; compare their cooling capacity and cooling concept against your process load before deciding.

What must I provide on the hydraulic and electrical side to integrate this chiller?

Provide cooling water at 1–6 bar differential and 5–20 °C intake, with G1/2 male couplings; process loop connects to the G3/4 male pump ports. Electrically, supply 208-230 V 1~/2~ 60 Hz with 2×16 A fusing and fit a site plug, since the cable is supplied without one.

Where can the unit be installed and how must it be set up before operation?

Indoors only, outside ATEX zones, at ≥300 lx and ≤2000 m altitude, with 50–200 cm clearance per side and ambient 5–40 °C. Activate parking brakes or leveling feet before start-up, and protect electrical lines below the unit from condensate.

What maintenance and consumables are not included in the base delivery?

The base unit ships without a mains plug, hose couplings for G3/4 and G1/2 connections, and heat-transfer fluid; the minimum fill is 3.8 l with 1.7 l expansion allowance. Refrigerant-circuit service must be performed by approved contractors; freeze protection requires glysantine or ethylene glycol added on site.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P022w Datasheet
Datasheet ·18,6 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF