Peter Huber Kältemaschinenbau Unichiller P025w-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P025w-H OLÉ

Peter Huber Kältemaschinenbau Unichiller P025w-H OLÉ — Recirculating chillers with Noise level 60 dB.

The Unichiller P025w-H OLÉ is a water-cooled recirculating chiller with a plastic pump (type B) and OLÉ controller, rated for -10...100 °C in externally closed circuits. Its 'P' designation targets high-pressure-drop loops, and the water-cooled condenser requires 5–20 °C cooling water at 1–6 bar differential. It serves as a compact process chiller for closed-loop heat removal.

Noise level
60 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P025w-H OLÉ Current 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 67 kg
Electrical, Power & Drive Specifications
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 72 l/h (cooling water 15 °C, flow -10 °C)
cooling water 15 °C, flow 0 °C: 84 l/h · cooling water 15 °C, flow 15 °C: 84 l/h
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior and media

Installation, control and operation

Integration & Operating Notes

Cooling & Media
Cooling water must stay within 5–20 °C and 1–6 bar differential

The water-cooled condenser requires a cooling-water intake temperature between 5 °C and 20 °C and a differential pressure of at least 1 bar at the G1/2 male connection, with a maximum of 6 bar. Below the condensation point, cooling-water pipes must be insulated to prevent condensation.

Unichiller P025w-H OLÉ Datasheet, page 1–2
Control & I/O
Configure power-failure response to avoid unintended restart

The OLÉ controller offers OFF/Standby, ON, or Power Failure Auto response after power restoration. For processes where automatic restart is unsafe, select OFF/Standby; for continuous cooling, Power Failure Auto restarts the unit automatically.

Unichiller Operation Manual, page 19; Datasheet, page 1
Safety
Use Process Safety mode for exothermic reactions

In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. This prevents runaway temperatures in exothermic processes but requires the trigger value to be set correctly.

Unichiller Operation Manual, page 18
Maintenance
Refrigerant circuit work only by approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a charge of 0.4 kg (0.6 t CO2 equivalent), and room size must be checked against the refrigerant limit per m³.

Unichiller Operation Manual, pages 15 and 17
Operation
Shut off cooling water even for overnight downtime

Shut off the cooling water supply to the unit even for shorter downtimes such as overnight to prevent water damage and corrosion. Before switching on, activate parking brakes and/or unscrew leveling feet to prevent movement.

Unichiller Operation Manual, pages 28 and 31

Selection & Integration Q&A

When should I choose the P025w-H OLÉ over the Unichiller 015 variants?

Choose the P025w-H OLÉ when you need water cooling, lower noise (60 dB(A) vs 63 dB(A)), and a 'P' pump suited to high pressure-drop loops. The 015 variants are air-cooled and may be preferred where no cooling water is available.

What cooling water supply and connections does the P025w-H OLÉ require?

It requires cooling water at 5–20 °C with a differential pressure of 1–6 bar at G1/2 male connections. Consumption is 84 l/h at 15 °C cooling water and 0 °C flow, 72 l/h at -10 °C flow. Insulate pipes below the condensation point.

What are the installation and duty-cycle limits for the P025w-H OLÉ?

Install indoors only, at 5–40 °C ambient, with 50–200 cm side clearance for maintenance and at least 300 lx illuminance. IP20 requires a dry location; protect electrical lines below the unit from condensation. Not for ATEX zones.

What maintenance and accessories are required, and what is not included?

Refrigerant circuit work must be by approved contractors. Shut off cooling water for downtimes. Base delivery excludes hoses and fittings for G1/2 and G3/4 connections; order suitable hoses and insulation separately. No specific maintenance interval is stated in the provided documents.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P025w-H OLÉ Datasheet
Datasheet ·82,1 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.