Peter Huber Kältemaschinenbau Unichiller P015w-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P015w-H

Peter Huber Kältemaschinenbau Unichiller P015w-H — Recirculating chillers with Noise level 54 dB.

The Unichiller P015w-H is a water-cooled recirculating chiller with a plastic pump and Pilot ONE controller, rated for -20 to 100 °C. Its 'P' designation targets externally closed loops with high pressure drop, distinguishing it from the air-cooled Unichiller 015 siblings. It serves as a precision cooling source for laboratory and pilot-scale processes requiring stable temperature control.

Noise level
54 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P015w-H Current 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 54 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 61 kg
Electrical, Power & Drive Specifications
Current consumption 12 A (max.)
Fuse rating 16 A
Power supply 208-230V 1~/2~ 60Hz V, Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 36 л/час (at 15°C, flow -20°C)
at 15°C, flow -10°C: 48 л/час · at 15°C, flow 0°C: 60 l/h · at 15°C, flow 15°C: 68 l/h
Cooling water differential pressure 1 bar (min.)
Cooling Water Pressure 6 bar (max.)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and Series Positioning

Hydraulic and Thermal Behavior

Installation, Control, and Operation

Integration & Operating Notes

Cooling & Media
Cooling water pressure must stay within 1–6 bar differential

The facility cooling water loop must deliver at least 1 bar differential pressure for the chiller to perform, and must never exceed 6 bar or the unit may be damaged. Verify the supply pressure at the installation site before commissioning, and install a pressure reducer if the site pressure can exceed 6 bar.

Unichiller P015w-H Datasheet, page 2
Cooling & Media
Cooling water inlet temperature limited to 5–20 °C

The unit is designed for cooling water intake between 5 °C and 20 °C. If the facility water can fall below the condensation point, pipes must be insulated to prevent condensation. Published cooling capacities are referenced to 15 °C cooling water inlet; higher inlet temperatures reduce available cooling power, so derate capacity if site water is warmer.

Unichiller P015w-H Datasheet, page 2
Electrical
Avoid -5 % voltage combined with +2 % frequency

Voltage tolerance is ±5 % and frequency tolerance is ±2 %, but the combination of -5 % voltage with +2 % frequency is explicitly not allowed. Check the site power quality against this asymmetric rule before connection; operation outside these limits may compromise safety and warranty.

Unichiller P015w-H Datasheet, page 2
Electrical
Specify plug type at ordering for single/two-phase units

Single/two-phase devices (100–240 V) are supplied with a power cable and country-specific plug; the plug type must be specified when ordering. Three-phase devices below 63 A come with cable but no plug, and the customer must provide the plug and final connection. This unit is 208–230 V 1~/2~, so confirm the plug requirement at purchase.

Unichiller P015w-H Datasheet, page 2
Mounting
Indoor installation only, with 50–200 cm side clearance

The unit must be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude, with ambient temperature between 5 °C and 40 °C. A wall clearance of 50 to 200 cm per side is required for maintenance access. Leveling feet must be unscrewed or parking brakes applied before operation to prevent movement.

Unichiller Operation Manual, page 25 and page 31
Mounting
Protect electrical lines below the unit from condensate

Because this is a water-cooled unit, condensation can form and drip. Electrical lines directly below the temperature control unit must be protected against liquid ingress. Route cables away from the unit or install drip protection to avoid electrical hazard.

Unichiller Operation Manual, page 28
Process Limits
Externally closed loop only; not for ATEX zones

The unit is designed only for externally closed applications and must not be installed or started up inside an ATEX zone because it is not explosion-protected. Ensure the process circuit is closed and non-hazardous. The 'P' model is particularly suitable for applications requiring high pressure drops.

Unichiller Operation Manual, page 34 and page 13
Process Limits
Plastic pump incompatible with acetone and polyglycols

The standard plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For freeze protection, use water mixed with glysantine or ethylene glycol instead. Verify fluid compatibility with the cooling water circuit materials: copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM.

Unichiller P015w-H Datasheet, page 2
Control & I/O
Configure power-failure response for process safety

The Pilot ONE controller allows the power-failure response to be set as OFF/Standby, ON, or Power Failure Auto. For exothermic processes, consider Process Safety mode, which releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. Choose the mode that matches the process risk.

Unichiller Operation Manual, page 18 and page 19
Maintenance
Shut off cooling water even for overnight downtime

The cooling water supply must be shut off even for shorter downtimes such as overnight to prevent water damage and corrosion during idle periods. Incorporate a manual or automatic shut-off valve in the cooling water supply line, and include this step in the site operating procedure.

Unichiller Operation Manual, page 28
Maintenance
Refrigerant circuit work requires certified contractors

Work on the coolant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with GWP 1397 and a charge of 0.25 kg (0.3 t CO2e), so F-gas reporting and leak-check obligations apply. Keep service records for compliance.

Unichiller Operation Manual, page 17 and Datasheet page 1

Selection & Integration Q&A

When should I choose the P015w-H over the air-cooled Unichiller 015 or 015-H?

Choose the P015w-H when a facility cooling water loop is available and the process loop has high pressure drop, since the 'P' model is suited for that. Air-cooled 015 siblings avoid water connections but are louder (63 dB(A) vs 54 dB(A)) and lack the high-pressure-drop capability.

What are the requirements for the facility cooling water supply and the process loop connections?

Cooling water: G1/2 male connection, 1–6 bar differential pressure, 5–20 °C inlet. Process loop: G3/4 AG male pump connection, minimum filling volume 3.8 l, expansion volume 1.7 l. Ensure the external circuit is closed and compatible with copper, stainless steel, PA, PPE, PTFE, and EPDM.

What mounting and ambient conditions must be met for installation?

Install indoors only, at 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, with 50–200 cm side clearance for maintenance. Activate leveling feet or parking brakes before operation. Protect electrical lines below the unit from condensate. Do not install in ATEX zones.

What maintenance and service items are required, and what is not included in the base delivery?

Shut off cooling water even overnight. Refrigerant circuit work only by certified contractors; R-449A charge 0.25 kg requires F-gas records. The base delivery includes a power cable and country-specific plug for single/two-phase units (specify plug at ordering); three-phase units require customer-supplied plug. No process hoses or cooling water valves are mentioned as included.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P015w-H Datasheet
Datasheet ·126,7 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF