Peter Huber Kältemaschinenbau Unichiller P022
Peter Huber Kältemaschinenbau Unichiller P022 — Recirculating chillers with Noise level 65 dB.
The Unichiller P022 is a recirculating chiller with a plastic pump (type B) and G3/4 male connections, rated for -10 to 40 °C and intended for externally closed circuits with high pressure drop. Its cooling capacity falls from 2.2 kW at 15 °C to 1.0 kW at -10 °C, so sizing must use the capacity at the actual working temperature. It uses flammable R-290 refrigerant and requires a 220–240 V single-phase 50 Hz supply.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P022 Current | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 65 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -10...40 °C |
| Weight | 81 kg |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 1 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The P022 is the high-pressure-drop variant of the Unichiller series, identified by the "P" in the model code; the manual states that models with "P" are particularly suitable for applications requiring high pressure drops.
- It uses a plastic pump (type B) with non-adjustable speed and G3/4 male pump connections.
- Sibling models (Unichiller 015, 015-H, 015-H OLÉ, 015 OLÉ) are listed with 63 dB(A) noise; the P022 is rated 65 dB(A).
- The unit is designed for externally closed applications only.
Thermal behavior and media
- Operating temperature range is -10 to 40 °C. Cooling capacity is 2.2 kW at 15 °C, 1.6 kW at 0 °C, and 1.0 kW at -10 °C; capacity also drops when ambient temperature rises above 20 °C.
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol.
- Minimum filling capacity is 3.8 l with 1.7 l expansion volume.
- The refrigerant is R-290 (A3, H220), flammable; refrigerant charge and room size must be checked at installation.
Installation, control and operation
- Electrical supply: 220–240 V 1~ 50 Hz, max current 8.5 A, 16 A fuse. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and certain combinations (e.g. -5% voltage with +2% frequency) are not allowed.
- Protection rating IP20; indoor use only, illuminance at least 300 lx, altitude up to 2000 m, ambient 5–40 °C.
- Controller: Pilot ONE with display resolution 0.1 K; interfaces Ethernet, USB (host and device), RS232; external sensor connection Pt100.
- Power-failure response configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached.
- Wall clearance of 50 to 200 cm per side required for maintenance on free-standing models. Leveling feet must be activated and parking brakes applied before operation.
Integration & Operating Notes
Capacity falls from 2.2 kW at 15 °C to 1.6 kW at 0 °C and 1.0 kW at -10 °C, and further drops if ambient exceeds 20 °C. Selecting the unit on its 15 °C rating for a -10 °C process will undersize the chiller and risk overtemperature trips.
The standard plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For freeze protection, use water mixed with glysantine or ethylene glycol; verify fluid compatibility before filling the 3.8 l minimum circuit with 1.7 l expansion volume.
The supply must be 220–240 V 1~ 50 Hz with max current 8.5 A and a 16 A fuse. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed; verify site power quality before commissioning.
The unit uses flammable R-290 (A3, H220). The refrigerant charge (see data sheet/rating plate) and the room size must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air; work on the refrigerant circuit must be performed by approved refrigeration contractors.
Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance. The unit must be installed indoors at illuminance of at least 300 lx and up to 2000 m altitude, and must not be placed in an ATEX zone.
The P022 is designed for externally closed applications; open baths or circuits that expose the fluid to atmosphere are outside the intended use. The "P" designation additionally targets loops with high pressure drop, so verify the process pressure drop against the pump curve.
The Pilot ONE allows power-failure response OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles; select the mode that matches the process hazard analysis.
Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit is classified to DIN 12876 with identification depending on whether the thermal fluid is combustible; confirm the safety class (I/NFL) against the fluid used.
Parking brakes must be activated at the casters (if any) and/or leveling feet unscrewed/activated before the unit is put into operation. Pump connections must be counterheld and maximum tightening torques must not be exceeded to avoid leaks.
Selection & Integration Q&A
Choose the P022 when the process loop has high pressure drop, since the "P" model is specifically suited to such applications. The 015/015-H siblings are rated 63 dB(A) versus 65 dB(A) for the P022; select a sibling if noise is the dominant constraint and pressure drop is low.
The pump connection is G3/4 male, so hoses and fittings must match; counterhold connections and do not exceed maximum tightening torques. Fill to at least 3.8 l with 1.7 l expansion allowance, using water with glysantine or ethylene glycol for freeze protection; avoid acetone and polyglycols with the plastic pump.
Install indoors only, at 5–40 °C ambient, illuminance at least 300 lx, altitude up to 2000 m, and never in an ATEX zone. Maintain 50–200 cm wall clearance per side, protect electrical lines below the unit from condensate, and shut off cooling water even for overnight downtimes.
The base unit ships without a country-specific plug unless specified at ordering; single-phase devices are delivered with a power cable but the plug must be requested. Refrigerant circuit service must be performed by approved contractors; no consumables or spare parts are listed in the provided documents.