Peter Huber Kältemaschinenbau Unichiller 022-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 022-H

Peter Huber Kältemaschinenbau Unichiller 022-H — Recirculating chillers with Noise level 65 dB.

The Unichiller 022-H is a single-phase, air-cooled recirculating chiller with an immersion pump and Pilot ONE controller, covering -10 to 100 °C. Within the Unichiller series it is the 2.2 kW-class model, distinguished from the 015 siblings by higher cooling capacity and 65 dB(A) noise. It serves externally closed process loops requiring up to 29 l/min at 1 bar.

Noise level
65 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 022-H Current 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 65 dB(A)
Maximum delivery flow rate 29 l/min (1 bar)
Pump connection G3/4 AG male
Pump speed adjustable Yes
Pump type Immersion pump
External sensor connection Pt100
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 77 kg
Electrical, Power & Drive Specifications
Current consumption 13 A
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Display resolution 0, 1 K
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance and level the unit before start

Free-standing installation requires 50 to 200 cm wall clearance on either side for maintenance access, and air-cooled heat rejection needs the space around the unit respected per operating conditions. Before switching on, activate parking brakes at the casters and/or unscrew the leveling feet so the unit cannot move.

Unichiller Operation Manual, Installation
Electrical
Size supply for 13 A draw on a 16 A fuse, single-phase

The unit needs 220–240 V 1~ 50 Hz with a 16 A fuse and draws up to 13 A. Voltage and frequency tolerances must be satisfied simultaneously; a combination of -5% voltage and +2% frequency is not permitted. Specify the country-specific plug at ordering to avoid rework.

Unichiller 022-H Technical Datasheet, Specifications
Process Limits
Use only externally closed loops; avoid acetone and polyglycols

The chiller is designed for externally closed applications only. The plastic immersion pump is not resistant to acetone or polyglycols (depending on manufacturer), so these fluids must be avoided or a more resistant pump specified. For freeze protection below 0 °C, mix water with glysantine or ethylene glycol.

Unichiller Operation Manual, Function Description; Datasheet
Safety
Configure power-failure and OT response for exothermic processes

Power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles, preventing runaway temperatures.

Unichiller Operation Manual, Normal Operation / Safety
Maintenance
Refrigerant circuit work restricted to approved contractors

Any work on the coolant/refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit contains 0.58 kg R-449A (GWP 1397, 0.8 t CO2e), which governs leak-check intervals and refrigerant accounting.

Unichiller Operation Manual, Maintenance
Environment
Indoor, dry location only; IP20 forbids washdown areas

IP20 offers no water protection, so the unit must be installed in a dry location protected from water ingress; electrical lines directly below a water-cooled unit must be protected against condensate. Ambient must stay 5–40 °C, illuminance at least 300 lx, altitude up to 2000 m, and no ATEX zone.

Unichiller Operation Manual, Installation; Datasheet

Selection & Integration Q&A

When should I choose the Unichiller 022-H instead of the 015 or 015-H siblings?

Pick the 022-H when the heat load requires the 2.2 kW class (2.2 kW at 15 °C, 1.6 kW at 0 °C, 1 kW at -10 °C at 20 °C ambient). The 015 siblings are lower-capacity (63 dB(A) vs 65 dB(A)). For high pressure-drop loops, a 'P' model is the correct choice, not this unit.

What supply and protection must be provided for the 022-H, and what about the plug?

Provide 220–240 V 1~ 50 Hz with a 16 A fuse; the unit draws up to 13 A. Voltage and frequency tolerances must be met simultaneously (-5% voltage with +2% frequency is not allowed). A country-specific plug is supplied only if specified at ordering.

Can the 022-H be installed in a washdown area or outdoors?

No. The unit is IP20 and must be installed indoors in a dry location protected from water ingress, at 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, and never inside an ATEX zone. Allow 50–200 cm wall clearance per side for maintenance.

What maintenance and consumables are required, and what is not included in base delivery?

Refrigerant-circuit work must be done by approved refrigeration contractors; the unit holds 0.58 kg R-449A (0.8 t CO2e). For sub-zero operation, glysantine or ethylene glycol must be added to the water by the user. The country-specific power plug must be specified at ordering; no cables or accessories beyond that are stated.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 022-H Technical Datasheet
Datasheet ·95,7 КБ ·2 pp.
View PDF